Corrections in the following table need to be applied before a permit can be issued
Review Report
Approved
# 22-00600
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
Pg 1 Stamp Larry Beesley : Building Open 1 Approved - Building Inspector
Solar Panels
Approval of plans does not constitute approval of variance from code
Powered by TCPDF (www.tcpdf.org)
DATE: 08-11-2022
FOR: Freedom Forever JOB: Kevin Heebner
43445 Business Park Dr 839 Engleman Street
#110 Rexburg, ID 83440
Temecula, CA 92590
USA
To Whom It May Concern
This letter is to certify that we have performed a structural analysis of the existing roof members that are to
support photovoltaic panels, as shown on the attached report. The calculations were performed in accordance
with the latest editions of IBC, NDS, ASCE/SEI, CBC, and IRC, and the latest edition of the building codes
for the state of Idaho.
Our analysis was based on the following design criteria:
Ground Snow (psf) 50 psf
Sloped Snow (psf), reduced per ASCE, Sect. 7.4 47.55 psf
Basic Wind Speed (mph): 115 mph
Roof Slope: 18 degrees
The PV module orientation: Landscape
The maximum horizontal roof mount spacing:2 ft.
The maximum vertical roof mount spacing: 3.417 ft.
Staggered roof mounts required? No
Based on this analysis, we can certify that the individual existing roof framing members that support the
PV panels; and the individual roof members as described in the attached report; are adequate to support the
design loads as required by the various codes. This includes Dead Loads (including the weight of the PV
panels), Live Loads, Snow Loads, and Wind Loads, on the roof members that support the PV panels,
combined as required in the codes.
If you have any questions on this or need further clarification,
please contact us at your convenience.
Sincerely,
Paul Truong, P.E.
NOTE:
1. Prior to commencement of work, the Solar Installer shall verify
that the roof framing sizes, spacing, and spans (between supports),
are as noted in these plans. The Engineer of Record must be
notified if any discrepancies are discovered, before proceeding.
2. These plans are Stamped for Structural Code compliance of
the roof members that support the PV solar system only.
3. These plans are not stamped for rain water leakage prevention.
4. As a precaution, old or wet snow should be removed from the roof,
if the snow builds up to 18" or more.
Phong Truong, P.E.
Date: 2022.08.11 11:15:21 -0700
Date of Report: 08-11-2022 Job Name: Kevin Heebner
Data Input by: Yunjae Shin Job Number: 246630
Contact E-mail: yunjae@solar-roof-check.com Job Address: 839 Engleman Street
Contact Phone: 7143322701 Rexburg, ID 83440
ABSTRACT
This Report is based on Engineering calculations
using the input data supplied by the user, listed
under Current Input Data. The user input has not
been independently reviewed by a licensed
Professional Engineer for appropriateness or
accuracy, unless Stamped by a P.E. This Report
indicates Compliance/Non-Compliance with the
reference Codes listed below. The following items
have been checked for Code Compliance:
- Load Combination #1:
Wind Uplift on the Standoff attachment to
the Roof Framing members: Wind Uplift -
0.6 * DL Solar
- Load Combination #2:
Supporting Rafter Strength with: DL Rf +
DL Solar + Roof Live Load
- Load Combination #3:
Supporting Rafter Strength with: DL Rf +
DL Solar + Wind Down
- Load Combination #4: Supporting Rafter
Strength with: DL Rf + DL Solar + Snow
- Load Combination #5:
Supporting Rafter Strength with: DL Rf +
DL Solar + .75Wind + .75Snow
- Load Combination #6: Check Additional
Seismic Load
- Load Combination #7:
Supporting Rafter Strength with:
Wind Up - 0.6 * (DL Rf + DL Solar)
Job Information
Data Input By:Yunjae Shin
Job Number: 246630
Job Name: Kevin Heebner
Job Address: 839 Engleman Street
City, State: Rexburg, ID 83440
Current Input Data
Payment Method Invoice
Roof Type Truss
Ceiling Type 1/2 gyp. Bd.
Collar Tie Space 0
Coverage % 15.98
Frame Size 2x4@24
Ground Snow (psf) 50
Sloped Roof Snow Load (psf) 47.55
Lag Screw Diam. (in) 5/16
Lag Screw Embed. (in) 2.5
Overall Span (ft) 35
PV Weight (psf) 2.29
PV Module Orientation Landscape
Rafter Span (ft) 6.5
Rail System RailLess
Roof Mean Height (ft) 25
Roof Slope (degrees) 18
Roofing Type Comp. Shingle
Sloped Ceiling No
Max. Horizontal Roof Mount(ft) 2
Max. Vertical Roof Mounts (ft) 3.417
Standoff Staggered No
Wind Exposure C
Wind Speed (mph) 115