Loading...
HomeMy WebLinkAboutREDLINED PLAN - 22-00438 - BYUI - Electrical CabinetAuthor Name Author Email Author Phone No.: Alex Owens Alex.Owens@rexburg.org 208-372-2330 Description : BYUI - Electrical Cabinet Address : 4th S 1st W Application Type : Document Filename : Publication4.pdf Array Comment Author Contact Information: Corrections in the following table need to be applied before a permit can be issued Review Report Revisions Required Page Reference Annotation Type Author : Department Status Page Review Comments Applicant Response Comments Pg 1 Callout Alex Owens : Electrical Open 1 As per Public Works, cabinet cannot be located in this area. Contact Joel Gray (716-1331) for more information. Pg 2 Callout Alex Owens : Electrical Open 2 Exposed conduit must meet article 352.10f requirements (if PVC, schedule 80 will be required above ground). Pg 2 Free text Alex Owens : Electrical Open 2 All electrical work to comply with 2017 NEC standards. Pg 2 Callout Alex Owens : Electrical Open 2 Supplemental grounding electrodes needed as per 250.53a2 # 22-00438 Commercial Electrical Misc. Report Date: 06.27.2022 Approval of plans does not constitute approval of variance from code Page 1 of 1 Powered by TCPDF (www.tcpdf.org) Proposed Cabinet location (see page 2 for detail) Trench and install (1) 3” schedule 40 conduit from cabinet meter base to RMP pole RMP Pole As per Public Works, cabinet cannot be located in this area. Contact Joel Gray (716-1331) for more information. Supplemental grounding electrodes needed as per 250.53a2 All electrical work to comply with 2017 NEC standards. Exposed conduit must meet article 352.10f requirements (if PVC, schedule 80 will be required above ground).