HomeMy WebLinkAboutREDLINED PLAN - 22-00438 - BYUI - Electrical CabinetAuthor Name Author Email Author Phone No.:
Alex Owens Alex.Owens@rexburg.org 208-372-2330
Description : BYUI - Electrical Cabinet
Address : 4th S 1st W
Application Type :
Document Filename : Publication4.pdf Array
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report
Revisions Required
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
Pg 1 Callout Alex Owens : Electrical Open 1 As per Public Works, cabinet cannot be located in this area.
Contact Joel Gray (716-1331) for more information.
Pg 2 Callout Alex Owens : Electrical Open 2 Exposed conduit must meet article 352.10f requirements (if
PVC, schedule 80 will be required above ground).
Pg 2 Free text Alex Owens : Electrical Open 2 All electrical work to comply with 2017 NEC standards.
Pg 2 Callout Alex Owens : Electrical Open 2 Supplemental grounding electrodes needed as per 250.53a2
# 22-00438
Commercial Electrical Misc.
Report Date: 06.27.2022
Approval of plans does not constitute approval of variance from code
Page 1 of 1
Powered by TCPDF (www.tcpdf.org)
Proposed Cabinet location
(see page 2 for detail)
Trench and install (1) 3”
schedule 40 conduit
from cabinet meter
base to RMP pole
RMP Pole
As per Public Works,
cabinet cannot be located in
this area. Contact Joel Gray
(716-1331) for more
information.
Supplemental grounding
electrodes needed as
per 250.53a2
All electrical
work to comply
with 2017 NEC
standards. Exposed conduit must meet
article 352.10f requirements
(if PVC, schedule 80 will be
required above ground).