Description : BYUI - Electrical Cabinet
Address : 479 S Center St
Record Type : Commercial Electrical Misc.
Document Filename : Publication4.pdf
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report
Approved
# 22-00438
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
Pg 1 Stamp Alex Owens : Electrical Open 1 Approved - Electrical Inspector
Pg 2 Callout Alex Owens : Electrical Open 2 Exposed conduit must meet article 352.10f requirements (if
PVC, schedule 80 will be required above ground).
Pg 2 Free text Alex Owens : Electrical Open 2 All electrical work to comply with 2017 NEC standards.
Pg 2 Callout Alex Owens : Electrical Open 2 Supplemental grounding electrodes needed as per 250.53a2
Pg 2 Line Alex Owens : Electrical Open 2
Pg 2 Line Alex Owens : Electrical Open 2
Pg 2 Stamp Alex Owens : Electrical Open 2 Approved - Electrical Inspector
Pg 2 Free text Alex Owens : Electrical Open 2 As per Joel Gray, location of cabinet is in an acceptable
location.
Commercial Electrical Misc.
Approval of plans does not constitute approval of variance from code
Powered by TCPDF (www.tcpdf.org)
Proposed Cabinet location
(see page 2 for detail)
Trench and install (1) 3”
schedule 40 conduit
from cabinet meter
base to RMP pole
RMP Pole
Supplemental grounding
electrodes needed as
per 250.53a2
All electrical
work to comply
with 2017 NEC
standards.
As per Joel Gray, location of
cabinet is in an acceptable location.
Exposed conduit must meet
article 352.10f requirements
(if PVC, schedule 80 will be
required above ground).