Loading...
HomeMy WebLinkAboutDESIGN CRITERIA & PLANS - 22-00915 - 318 Oaktrail Dr - Solar Panels6949 S High Tech Drive Suite 200 Midvale, UT 84047 P (801) 352-0075 F (801) 352-7989 November 10, 2022 Energy Savers 245 E 2150 N Layton, Utah 84041 Re: Kimball Arritt Residence: 318 Oaktrail Dr., Rexburg, ID 83440 We have been retained to review the feasibility of adding solar panels to the above referenced site. We have reviewed the solar panel installation site plan and conclude that the panels will not negatively affect the structure at the site mentioned above. The solar panels and their respective design, attachments, and connections shall be per the responsibility of the manufacturer/installer and shall be installed and designed in accordance with the 2018 IBC and ASCE 7-16. The structure is adequate to take on the additional lateral loads due to the solar panels for the following reasons: Any increase in wind loads is negligible due to the mounting pattern of the panels being flush with the existing roof. The solar panels weigh 2.5 psf. Per the IEBC section 503.4, the lateral force resisting system need not be adjusted for less than a 10% change in seismic loads. Since the roof dead load is 15 psf, and the solar panels that weigh 2.5 psf affect less than 50% of the roof structure, the increase in seismic lateral loads is less than 9%. The structure is also adequate to resist the gravity loads due to the solar panels for the following reasons: The live loads will be reduced in the areas where the solar panels are added because no roof live loads will be presen t and snow loads will be reduced. Snow loads will be reduced due to the slippery surface of the solar panels and the heat produced by the black surface. The snow will be more likely to melt and slide off of the panels and be reduced due to these elements as per ASCE 7-16 Figure 7.4-1. With these reductions in the live loads, we can conclude that the additional 2.5 psf increase in dead load will be adequately offset by the reductions in the governing live load. All attachments of the solar panels to the roof structure shall be staggered and spaced on various rafters/truss top chords per the rail system manufacturer in order to have the loads shared by multiple roof structural elements. Focus Engineering & Surveying is not responsible for any problems produced due to improper installation. Focus Engineering & Surveying also assumes the structure is in good condition and was adequately designed by the original design professional and assumes no liability for problems existing due to improper original design. Sincerely, Lynn Gray Focus Engineering & Surveying Reviewed By: Matthew S. Hakes, P.E. Project Engineer Focus Engineering & Surveying We have been retained to review the feasibility of adding solar panels to the above referenced site. We have reviewed the solar panel installation site plan and conclude that the panels will not negatively affect the structure at the site mentioned above. The solar panels and their respective design, attachments, and connections shall be per the responsibility of the manufacturer/installer and shall be installed and designed in accordance with the 2018 IBC and ASCE 7-16. The structure is adequate to take on the additional lateral loads due to the solar panels for the following reasons: Any increase in wind loads is negligible due to the mounting pattern of the panels being flush with the existing roof. The solar panels weigh 2.5 psf. Per the IEBC section 503.4, the lateral force resisting system need not be adjusted for less than a 10% change in seismic loads. Since the roof dead load is 15 psf, and the solar panels that weigh 2.5 psf affect less than 50% of the roof structure, th e increase in seismic lateral loads is less than 9%. The structure is also adequate to resist the gravity loads due to the solar panels for the following reasons: The live loads will be reduced in the areas where the solar panels are added because no roof live loads will be presen t and snow loads will be reduced. Snow loads will be reduced due to the slippery surface of the solar panels and the heat produced by the black surface. The snow will be more likely to melt and slide off of the panels and be reduced due to these elements as per ASCE 7-16 Figure 7.4-1. With these reductions in the live loads, we can conclude that the additional 2.5 psf increase in dead load will be adequately offset by the reducti ons in the governing live load. All attachments of the solar panels to the roof structure shall be staggered and spaced on various rafters/truss top chords per the rail system manufacturer in order to have the loads shared by multiple roof structural elements. Focus Engineering & Surveying is not responsible for any problems produced due to improper installation. Focus Engineering & Surveying also assumes the structure is in good condition and was adequately designed by the original design professional and assumes no liability for problems existing due to improper original design. Sincerely, Lynn Gray Focus Engineering & Surveying Reviewed By: Matthew S. Hakes, P.E. Project Engineer Focus Engineering & Surveying Design Criteria & Assumptions: Ground Snow Load – 45 psf Roof Snow Load – 35 psf We have been retained to review the feasibility of adding solar panels to the above referenced site. We have reviewed the solar panel installation site plan and conclude that the panels will not negatively affect the structure at the site mentioned above. The solar panels and their respective design, attachments, and connections shall be per the responsibility of the manufacturer/installer and shall be installed and design ed in accordance with the 2018 IBC and ASCE 7-16. The roof structure is composed of 2x4 prefabricated trusses @ 24” o.c and appears to be in adequate condition. The structure is adequate to take on the additional lateral loads due to the solar panels for the following reasons: Any increase in wind loads is negligible due to the mounting pattern of the panels being flush with the existing roof. The solar panels weigh 2.5 psf. Per the IEBC section 503.4, the lateral force resisting system need not be adjusted for less than a 10% change in seismic loads. Since the roof dead load is 15 psf, and the solar panels that weigh 2.5 psf affect less than 50% of the roof structure, the increase in seismic lateral loads is less than 10%. The structure is also adequate to resist the gravity loads due to the solar panels for the following reasons: Per the IEBC section 503.3, the gravity force system need not be adjusted for less than 5% change in gravity loads. Since the roof snow load is no less than 35 psf, the roof dead load is 15 psf, and the solar panel load is 2.5 psf, the 5% load increase threshold is not reached in any added panel areas and therefore the pre-fabricated metal plated trusses are adequate to resist the additional load of the solar panels. All attachments of the solar panels to the roof structure shall be staggered and spaced on various rafters/truss top chords per the rail system manufacturer in order to have the loads shared by multiple roof structural elements. Focus Engineering & Surveying is not responsible for any problems produced due to improper installation. Focus Engineering & Surveying also assumes the structure is in good condition and was adequately designed by the original design professional and assumes no liability for problems existing due to improper original design. Sincerely, Christian Broberg Focus Engineering & Surveying Reviewed By: Matthew S. Hakes, P.E. Project Engineer Focus Engineering & Surveying 11/11/2022 50 ARRITT RESIDENCE 318 OAKTRAIL DR REXBURG, IDAHO 83440 DESIGNED BY: BRYCE PETERSON ENGINEERING (801) 614-0606 EXT 115 SHEET 1 OF 7 PLANT LOCATION AND INFORMATION SOLAREDGE SE7600H-US INVERTER 25 VIKRAM PREXOS VSMDHT.60.365.05 7.6 KW AC / 9.1 KW DC PHOTOVOLTAIC SYSTEM REVISION 1: PLANT LOCATION: ARRITT RESIDENCE 318 OAKTRAIL DR REXBURG, IDAHO 83440 ENGINEERING (801) 614-0606 EXT 115 SHEET 2 OF 7 SITE PLAN GENERAL NOTES: ALL CONSTRUCTION / INSTALLATION SHALL COMPLY WITH: 2017 NATIONAL ELECTRICAL CODE (NEC) 2018 INTERNATIONAL FIRE CODE (IFC) 2018 INTERNATIONAL BUILDING CODE (IBC) 2018 INTERNATIONAL RESIDENTIAL CODE (IRC) ALL DIMENSIONS SHOWN ARE APPROXIMATE UTILITY HAS 24-HR UNRESTRICTED ACCESS TO ALL PV SYSTEM COMPONENTS LOCATED AT SERVICE ENTRANCE ALL CONDUITS ON ROOF SHALL BE A MINIMUM OF ½” OFF ROOF CONSTRUCTION LIMITS: ALL IMPROVEMENTS AND ACCESS SHALL OCCUR WITHIN PLANT PROPERTY LINES SOLAR BOM NEW SOLADECK JUNCTION BOX (SOLTECTION RJ-1) _1_ QTY NEW JUNCTION BOX (SOLTECTION RU-2LP) _1_ QTY RAIL (SNAPNRACK SERIES 100)= _14_ (14 FT LENGTH) QTY SPLICES (SNAPNRACK SERIES 100)= _6_ QTY MID CLAMP (SNAPNRACK SERIES 100) = 42 QTY END CLAMP (SNAPNRACK SERIES 100) = 16 QTY STANDOFFS FEET AND LAGS (SNAPNRACK SERIES 100) = 50 QTY EACH LIMITS OF CONSTRUCTION SOLADECK JUNCTION BOX (S) ONE PER ARRAY SOLAREDGE SE7600H-US INVERTER (LOCATED NEXT TO SERVICE) APPROX. 40' DC RUN (IN ATTIC WHERE AVAILABLE) DEDICATED PHOTOVOLTAIC SYSTEM AC DISCONNECT (LOCATED WITHIN 3 FEET OF SERVICE) SERVICE ENTRANCE PANELBOARD EMERGENCY STOP DISCONNECT LOCATED IN SIGHT OF ESS CORE ESS LOCATED INSIDE GARAGE ON SIDEWALL SAFE FROM VEHICULAR DAMAGE GENERAL NOTES: ALL CONSTRUCTION / INSTALLATION SHALL COMPLY WITH: 2017 NATIONAL ELECTRICAL CODE (NEC) 2018 INTERNATIONAL FIRE CODE (IFC) 2018 INTERNATIONAL BUILDING CODE (IBC) 2018 INTERNATIONAL RESIDENTIAL CODE (IRC) ALL DIMENSIONS SHOWN ARE APPROXIMATE UTILITY HAS 24-HR UNRESTRICTED ACCESS TO ALL PV SYSTEM COMPONENTS LOCATED AT SERVICE ENTRANCE ALL CONDUITS ON ROOF SHALL BE A MINIMUM OF ½” OFF ROOF CONSTRUCTION LIMITS: ALL IMPROVEMENTS AND ACCESS SHALL OCCUR WITHIN PLANT PROPERTY LINES FOR IDAHO SONNEN AC HUB WITH INTEGRATED DEDICATED BATTERY SYSTEM UTILITY STOP DISCONNECT (LOCATED WITHIN 3 FEET OF SERVICE) ARRITT RESIDENCE 318 OAKTRAIL DR REXBURG, IDAHO 83440 DESIGNED BY: BRYCE PETERSON 200A MAIN M A 200A RATED SONNEN AC HUB 30A/2P 30A/2P 30A/2P 40A/2P 40A/2P 40A/2P 60A/2P 40A/2P 200A/2P B 200A/2P ENGINEERING (801) 614-0606 EXT 115 SHEET 3 OF 7 ONE-LINE DIAGRAMCODE COMPLIANCE: -INTERCONNECTION AT MAIN SERVICE ADHERES WITH NEC 705.12(B)(3)(3)\ -ITEM D AS WELL AS THE PV BREAKER(S) IN ITEM B ADHERE TO RAPID SHUTDOWN REQUIREMENTS IN NEC 690.12 -THE OCPD IN THE AC HUB IS SIZED WITH THE AMPACITY OF THE FEEDER WIRES IN ACCORDANCE WITH NEC 705.12(B)(1)b. -THE BREAKER (ITEM F) FOR SERVICEABILITY IS LOCATED WITHIN SIGHT OF THE ESS IN ACCORDANCE WITH NEC 706.15(A) -THE E-STOP FOR ESS IS BUILT INTO THE SONNEN AC HUB AND COMPLIES WITH NEC 690.12(C) AND NEC 706.15(B) WIRE SIZES: 1 - (2) 3/0 AWG CU / 4/0 AWG AL (1) 3/0 AWG NEUTRAL CU / 4/0 AWG AL (1) 6 AWG EGC CU / 4 AWG AL 2” EMT MIN. W/ THWN-2 /SER CABLE 2 - (2) 6 AWG CU (1) 6 AWG NEUTRAL CU (1) 8 AWG EGC CU ¾” EMT MIN. W/ THWN-2 OUTDOOR / NM CABLE INDOOR 3 - (2) 8 AWG CU (1) 8 AWG NEUTRAL CU (1) 10 AWG EGC CU ¾” EMT MIN. W/ THWN-2 OUTDOOR / NM CABLE INDOOR 4 - (2) 10 AWG CU (1) 10 AWG NEUTRAL CU (1) 10 AWG EGC CU ¾” EMT MIN. W/ THWN-2 OUTDOOR / NM CABLE INDOOR 5 - (2) 14 AWG CU (24V EMERGENCY STOP CIRCUIT) ¾” EMT MIN. W/ THWN-2 OUTDOOR / NM CABLE INDOOR 6 - (3)#14 AWG CU NM CABLE INDOOR DC SOLAR CIRCUITS CONTINUE ON SHEET 4 1 1 2 2 3 3 4 5 COMPONENTS: A - NEW MAIN SERVICE (MBE48B200BTS) B - SONNEN AC HUB C - 60A/2P DISCONNECT (EATON DG222URB) D - SONNEN CORE+ (SCORE-P10) E - EATON BREAKER BOX WITH ONE 40A BREAKER (BR24L70SP) F - HEAT/SMOKE DETECTOR (MODEL DEPENDANT ON AVAILABILITY) G - SOLAREDGE 7600W HD WAVE INVERTER (SE7600H-US) H - EXISTING SUBPANEL (UNMARKED 200A) 6 *WE WILL BE INSTALLING A HEAT/SMOKE DETECTOR ABOVE THE ESS(S). WIRE #6 IS ONLY IF APPLICABLE GC 40A/2P E ESS D H / S F 200A/2P 40A/2P OTHER LOADS 1 - (2) 3/0 AWG CU / 4/0 AWG AL (1) 3/0 AWG NEUTRAL CU / 4/0 AWG AL (1) 6 AWG EGC CU / 4 AWG AL 2” EMT MIN. W/ THWN-2 /SER CABLE 1 - (2) 1/0 AWG CU / 2/0 AWG AL (1) 1/0 AWG NEUTRAL CU / 2/0 AWG AL (1) 6 AWG EGC CU / 4 AWG AL 2” EMT MIN. W/ THWN-2 /SER CABLE 1 - (2) 1 AWG CU / 1/0 AWG AL (1) 1 AWG NEUTRAL CU / 1/0 AWG AL (1) 6 AWG EGC CU / 4 AWG AL 1 ½” EMT MIN. W/ THWN-2 /SER CABLE 1 - (2) 2 AWG CU / 2 AWG AL (1) 2 AWG NEUTRAL CU / 2 AWG AL (1) 8 AWG EGC CU / 6 AWG AL 1 ½” EMT MIN. W/ THWN-2 /SER CABLE TO INTERIOR PANEL H C*-NEW 125A SUBPANEL (EATON BR816L125RP) ARRITT RESIDENCE 318 OAKTRAIL DR REXBURG, IDAHO 83440 DESIGNED BY: BRYCE PETERSON 9125 DC WATT PHOTOVOLTAIC ARRAY (2) - 10 AWG THWN-2 CU PV WIRE PER STRING (1) - 6 AWG BARE CU GND (EGC) BONDED TO RAIL WITH WEEBL 6.7 LUG AND CLIP ASSEMBLIES. REMAINDER OF ARRAY GROUNDED PER MANUFACTURER'S SPECIFICATIONS. NEC.690.43 SOLAR EDGE POWER OPTIMIZERS TO BE GROUNDED WITH SST STAR WASHER PER MANUFACTURER'S SPECIFICATIONS SOURCE CIRCUIT: 12 PANELS: VIKRAM PREXOS VSMDHT.60.365.05 WITH S440 POWER OPTIMIZERS POWER=4380 WATTS DC VMP=417.6 VDC IMP= 10.53 ADC 13 PANELS: VIKRAM PREXOS VSMDHT.60.365.05 WITH S440 POWER OPTIMIZERS POWER=4745 WATTS DC VMP=452.4 VDC IMP= 10.53 ADC TOTAL ARRAY SPECS: 25 PANELS: POWER = 9125 WATTS DC Each DC Panel: VIKRAM PREXOS VSMDHT.60.365.05 TEMPERATURE CORRECTION FOR LARGEST STRING (PER NEC ARTICLE 690.7): VOC = 41.0 VDC TEMPERATURE COEFFICIENT(VOC) = -0.27%/ CVMAX = VOC + [(TLOW** - 25 C) X (-0.27% X VOC)]VMAX = 41.0 VDC + [(-16 C - 25 C) X (-0.27% X 41.0 VDC)]VMAX = 45.5 VDC (<48 VDC) MAXIMUM INPUT DC VOLTAGE FOR SOLAREDGE S440 = 48.0 V DC **SOLARABCS.ORG EXTREME LOW TEMPERATURE FOR OGDEN SUBARRAY #1: MAXIMUM SYSTEM VOLTAGE (VMAX) INVERTER MAXIMUM VOLTAGE RATING = 500 VDC RATED MAXIMUM POWER POINT VOLTAGE (VMPP) FOR 240 VAC GRID CONNECTION = 350 VDC MAXIMUM CIRCUIT CURRENT (IMAX) MAXIMUM INPUT RATING OF THE INVERTER = 15 ADC/STRING FOR 2 STRING SYSTEM = 30 ADC RATED MAXIMUM CIRCUIT CURRENT (IMPP) THE LOWER VALUE OF THE FOLLOWING: 1) SYSTEM POWER (STC)/VMP = 9125 W / 417.6 VDC = 21.85 A 2) INVERTER MAXIMUM OUTPUT CURRENT = 32 A AT 240 VAC Each DC Panel: JAJAM60S03-310/PR SE3000H-US 12. 5 SE3800H-US 16 SE5000H-US 21 SE6000H-US 25 SE7600H-US 32 SE10000H-U S 42 SE11400A-U S 47. 5 Each DC Panel: JINKO JKM375M-6RL3-B ENGINEERING (801) 614-0606 EXT 115 SHEET 4 OF 7 PANEL STRINGING WIRE COLORS DC: NEGATIVE - BLACK POSITIVE - RED WIRE COLORS AC: HOT - BLACK AND RED NEUTRAL - WHITE GROUND: - GREEN OR BARE PMAX (STC)365 W TOLERANCE +3.00% TOLERANCE -0.00% VOC (STC)41.00 V ISC (STC)11.45 A VMP (STC)34.80 V IMP (STC)10.53 A NEW JUNCTION BOX (SOLTECTION RU-2LP) G POS NEG G POS NEG 1 DC 13 DC DC DC DC DC 1 DC DC DC 12 G POS NEG G POS NEG G POS NEG G POS NEG POS NEG G POS NEG NEW SOLADECK JUNCTION BOX (SOLTECTION RJ-1) (2) - 10 AWG THWN-2-CU BLACK (2) - 10 AWG THWN-2-CU RED (1) - 10 AWG THWN-2-CU GREEN ¾”EMT CONDUIT AND/OR ¾” SEALTITE FLEXIBLE CONDUIT, TO BE GROUNDED AT EVERY NON METALLIC JUNCTION WITH GROUND BUSHINGS (2) - 10 AWG MC CABLE (1) - 10 AWG CU GND 1/2" MC CABLE IN ATTIC SECURED ACCORDING TO NEC 690.31 (D)(1) AND TO BE GROUNDED AT EVERY NON METALLIC JUNCTION WITH GROUND BUSHINGS CONTINUATION ON SHEET 3 TO INVERTER *SOLAR EDGE S440 OPTIMIZERS FOR EACH PANEL ARRITT RESIDENCE 318 OAKTRAIL DR REXBURG, IDAHO 83440 DESIGNED BY: BRYCE PETERSON THIS INSTALLATION SHALL COMPLY WITH THE REQUIREMENTS SPECIFIED IN THE UTAH AMENDED SECTIONS OF THE 2018 IRC THAT PERTAIN TO ENERGY STORAGE SYSTEMS INCLUDING SHEET ROCK AND AN INTERCONNECTED FIRE ALARM IN THE ROOM OF THE ENERGY STORAGE SYSTEM ALL ROOF PENETRATIONS MUST BE PROPERLY FLASHED. IRC M2302.2.2. ARRAY SELF WEIGHT 25 VIKRAM 365W PANELS 18.7 kg = 41.2 LBS/PANEL + SNAP-N-RACK RACKING MOUNTING HARDWARE:25 X 41.888 = 1048 A = L x W (PANEL): 69.53” X 41.34 = 19.96 SQ FT X 25 = 499 TOTAL SQ FT OF PLANE VIEW ROOF AREA = 2099 PERCENTAGE OF ROOF AREA COVERED IN SOLAR PANELS = 23.77% (IFC 1204.2.1.2) ARRAY: 1048 LBS / 499 SQ FT = 2.3 PSF MAX WEIGHT PER ANCHOR = 44.6 LBS (FOR 4’0” SPANS) PULL OUT STRENGTH CONNECTOR 5/16 LAG BOLT 50 STANDOFFS (50 LAGS) 50 x 3” EMBED x 210 LBS = 31500 LBS WEATHER LOADING GROUND SNOW: 50PSF WIND SPEED: 160MPH EXPOSURE CATEGORY: B MEETS OR EXCEEDS 2018 IBC IRC CONSTRUCTION STANDARDS CASE 1 Load Calculations 2X4 construction, 24" on center trusses ROOF LOAD BEARING ______ LBS / ___ STANDOFFS = _____LBS TOTAL WEIGHT = PANELS + HARDWARE 1412.5 LBS 1412.5 LBS / 460.75 SQ FT= 3.065 PSF DEDICATED PHOTOVOLTAIC SYSTEM AC DISCONNECT TIMES PANELS BY 630 THIS INSTALLATION SHALL COMPLY WITH THE REQUIREMENTS SPECIFIED IN SECTION 1204 OF THE 2018 INTERNATIONAL FIRE CODE. ROOF RACKING SUPPORT SPACING NOT TO EXCEED 4’ SPACING. ALL SUPPORTS MUST BE STAGGERED FROM ONE ROW OF RACKING TO THE NEXT SO NOT ALL SUPPORTS ARE BEARING ON THE SAME TRUSSES SOLAR PV MODULES CANNOT BE INSTALLED OVER OR BLOCK ANY ATTIC VENTS, PLUMBING VENTS, FURNACES OR WATER HEATER VENTS, ETC. WE WILL RELOCATE ANY OBSTRUCTIONS AS NEEDED. ALL WIRING MUST BE SUPPORTED BY DEVICES OR MECHANICAL MEANS DESIGNED AND LISTED FOR SUCH USE AND WIRING MUST BE PERMANENTLY AND COMPLETELY HELD OFF THE ROOF SURFACE. WE WILL BE OBSERVING IFC 1204.2 EXCEPTION 1TO BE USED WHEN USING A BARN OR NON INHABITED SPACE FOR ROOF TOP INSTALL FOR GRANTSVILLE: WEATHER LOADING GROUND SNOW: 30PSF WIND SPEED: 115MPH EXPOSURE CATEGORY: C FOR BINGHAM COUNTY IDAHO: WEATHER LOADING GROUND SNOW: 42PSF WIND SPEED: 115MPH EXPOSURE CATEGORY: C ENGINEERING (801) 614-0606 EXT 115 SHEET 5 OF 7 ARRAY MOUNTING AND LOADING 36 INCH FIRE DEPARTMENT SETBACK 36” PATHWAYS TO RIDGE ARRITT RESIDENCE 318 OAKTRAIL DR REXBURG, IDAHO 83440 DESIGNED BY: BRYCE PETERSON DUAL INPUT SOURCE SECOND SOURCE IS SOLAR PV SYSTEM ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND NOT HAND-WRITTEN. NEC 110.21(B) SIGN LOCATED AT POINT OF INTERCONNECTION. NEC 690.56(B) AND 705.10 AND 712.10 WARNING: SOLAR POWER SOURCE OUTPUT CONNECTION, DO NOT RELOCATE THIS OVERCURRENT DEVICE SIGN LOCATED NEXT TO SOLAR BACKFEED BREAKERS AT SERVICE PANEL. IF BREAKER FEED AND UTILIZING THE 120% RULE NEC 705.12(B)(2)(3)(b) RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM SIGN LOCATED NEXT TO THE SOLAR AC OR DC DISCONNECT THAT ACTIVATES RAPID SHUTDOWN. NEC 690.56 (C) (3) OR NEXT TO MAIN SERVICE DISCONNECT OR NEXT TO A RSD RELAY SIGNAL BUTTON THE MARKINGS SHALL BE REFLECTIVE WHITE ON RED BACKGROUND WARNING: PHOTOVOLTAIC POWER SOURCE THIS SIGN IS LOCATED ON THE OUTSIDE OF ANY CONDUITS, ENCLOSURES, OR MC CABLE THAT CONTAINS DC CIRCUITS. THE MARKINGS SHALL BE REFLECTIVE AND BE PROVIDED AT EVERY ENCLOSURE, EVERY 10’ ALONG CONDUIT OR MC CABLE, AND AT EACH SIDE OF WHERE THE CONDUIT OR CABLE PASSES THROUGH A WALL, FLOOR, OR ANY OTHER PARTITION. NEC 690.31(G)(3-4) AND IFC 605.11.1.2 PHOTOVOLTAIC ARRAY DC DISCONNECT SWITCH MAX SYSTEM VOLTAGE= 500 VDC MAX CIRCUIT CURRENT= 15 ADC MAX CURRENT FOR POWER OPTIMIZERS= 15 ADC0` THIS SIGN IS LOCATED ON THE OUTSIDE OF EACH DC DISCONNECT. NEC 690.53 and 690.13(B) PV SYSTEM BACKFEEDING THROUGH THIS PANEL AC OUTPUT CURRENT= 32 AAC AC VOLTAGE=240 VAC THIS SIGN IS LOCATED AT THE BACKFEED PANEL BOARD NEC 690.54 1 1 PHOTOVOLTAIC SYSTEM DEDICATED KWH METER THIS SIGN IS LOCATED AT THE DEDICATED KWH METER NOTICE: DO NOT ADD LOADS TO THIS PANEL THIS SIGN IS LOCATED NEXT TO THE BREAKER SLOTS AT THE MAIN SERVICE PHOTOVOLTAIC SYSTEM AC DISCONNECT THIS SIGN IS LOCATED AT THE AC PV SYSTEM DISCONNECT 690.13 (B) THIS SIGN IS LOCATED ON OR WITHIN 3’ FEET OF THE SERVICE METER PANELBOARD AND ON ANY AC DISCONNECT SWITCH ON THE OUTSIDE OF THE BUILDINGS NEC 690.56(C)(1) / IFC 1204.5.1 SE3000H-US 12.5 SE3800H-US 16 SE5000H-US 21 SE6000H-US 25 SE7600H-US 32 SE10000H-US 42 SE11400A-US 47.5 Ansi z535.4 color specific ENERGY STORAGE SYSTEM DISCONNECT NOMINAL AC VOLTAGE=_240_VAC MAX DC VOLTAGE=_112_VDC AVAILABLE FAULT CURRENT= 18.9 ADC SIGN LOCATED AT ENERGY STORAGE SYSTEM DISCONNECTS NEC 706.15(C) CAUTION: MULTIPLE SOURCES OF POWER POWER TO THIS SERVICE IS ALSO SUPPLIED FROM A PV SYSTEM CONNECTED TO THE AC SERVICE PANEL. LITHIUM BATTERY IS LOCATED IN GARAGE THIS DIRECTORY LOCATED AT POINTS OF INTERCONNECTION. NEC 690.56(B) AND 705.10 AND 706.21 AND 710.10 AND 712.10 ALSO PER UTILITY REQUIREMENTS ENGINEERING (801) 614-0606 EXT 115 SHEET 6 OF 7 SIGNAGE WARNING: MULTIPLE SOURCES OF POWER. A PV SYSTEM IS PRESENT. DISCONNECT ALL POWER SOURCES BEFORE SERVICING. FOR ST GEORGE POWER: ALL RED AND WHITE LABELING PLUS THE LABEL BELOW ARRITT RESIDENCE 318 OAKTRAIL DR REXBURG, IDAHO 83440 DESIGNED BY: BRYCE PETERSON ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND NOT HAND-WRITTEN. NEC 110.21(B) 1 1 PHOTOVOLTAIC SYSTEM DEDICATED KWH METER THIS SIGN IS LOCATED AT THE DEDICATED KWH METER NOTICE: PV SYSTEM COMBINER PANEL DO NOT ADD LOADS TO THIS PANEL THIS SIGN IS LOCATED AT THE COMBINER PANEL 9 SE3000H-US 12.5 SE3800H-US 16 SE5000H-US 21 SE6000H-US 25 SE7600H-US 32 SE10000H-US 42 SE11400A-US 47.5 Ansi z535.4 color specific ENGINEERING (801) 614-0606 EXT 115 SHEET 7 OF 7 PLACARDS FOR ROCKY MOUNTAIN POWER REQUIREMENTS PARALLEL GENERATION ON SITE THIS PLACARD IS LOCATED NEXT TO METER SOCKET. 2”X4” ENGRAVED METAL OR RED AND WHITE HARD PLASTIC ⅜” OR LARGER LETTERS MANUAL DISCONNECT FOR BATTERY THIS PLACARD IS LOCATED AT THE AC ESS SYSTEM DISCONNECT. 2”X4” ENGRAVED METAL OR RED AND WHITE HARD PLASTIC ⅜” OR LARGER LETTERS MANUAL DISCONNECT FOR PARALLEL GENERATION THIS PLACARD IS LOCATED AT THE AC PV SYSTEM DISCONNECT. 2”X4” ENGRAVED METAL OR RED AND WHITE HARD PLASTIC ⅜” OR LARGER LETTERS WARNING: MULTIPLE SOURCES OF POWER. A PV SYSTEM IS PRESENT. DISCONNECT ALL POWER SOURCES BEFORE SERVICING. FOR ST GEORGE POWER: ALL RED AND WHITE LABELING PLUS THE LABEL BELOW ARRITT RESIDENCE 318 OAKTRAIL DR REXBURG, IDAHO 83440 DESIGNED BY: BRYCE PETERSON