HomeMy WebLinkAboutAHJ RESPONSE LETTER - 21-00656 - 2911 S Frontage Rd - Carpet DirectNovember 1, 2021 Cody Jones | Building Official City of Rexburg | Building Division 35 N 1st E Rexbug, Idaho 834040 Re: Project # 21-00656 PROJECT DESCRIPTION Dear Cody Jones, Please see responses to your comments below: 1.Comment: Special inspector needs to be identified? Per section 1704.2.1 Response: Added special inspector to sheet G-001 2.Comment: Site grading meeting requirements of IBC section 1804.4 Response: Added General note “C.FINISH GRADE TO SLOPE 5% AWAY FROM THE BUILDING 10' MINIMUM” to sheet AS-101 & A-201 3.Comment: Dampproofing/Waterproofing comply with IBC Section 1805 Response: Added General note “WALL OR PORTIONS THEREOF THAT RETAIN EARTH AND ENCLOSE INTERIOR SPACES AND FLOORS BELOW GRADE SHALL BE WATERPROOFED AND DAMPPROOFED IN ACCORDANCE WITH 1805” to sheet A-201 4.Comment: 305 1ST STREET ▪ IDAHO FALLS, ID 83402 ▪ 208.757.5700 ▪ RESINARCHITECTURE.COM Page 1 of 4 Penetrations through fire wall needs to comply with section 714 Response: Added General Note “D. GENERAL CONTRACTOR TO COORDINATE ALL PENETRATIONS THROUGH FIREWALL ARE TO COMPLY WITH IBC 714”on sheet G-101 5.Comment: Fire walls to meet all requirements of section 706. Response: Confir ming that these requirements have been met. 6.Comment: Seating at tables, counters, and work areas comply with section 1109.11 Response: Update counter height at reception desk to be 34” in height. See sheet A-401 7.Comment: Exit lighting and exit signs to comply with section 1008 and 1013 Response: Added General Note “ALL MEANS OF EGRESS PATH SHALL BE ILLUMINATED TO A LEVEL NOT LESS THAN 1 FOOTCANDLE (11 LUX) AT THE WALKER SURFACE, PER IBC 1008” on sheet G-101. Added additional exit signs, see G-101 8.Comment: Area increase due to frontage distance? Response: Added Area Increase Calculation to Sheet G-102, also see calculation below. Increased Areas / Heights: (Section 506) Aa=At +At * If +At * Is Allowable area per story Aa 15,007 9,000 6,007 0 Tabular area per floor from table 506.2 At 9,000 Type V-B S-1 Area increase for frontage If 0.67 Area increase for sprinkler Is 0 None 305 1ST STREET ▪ IDAHO FALLS, ID 83402 ▪ 208.757.5700 ▪ RESINARCHITECTURE.COM Page 2 of 4 Area increase for frontage (equation 5-5)If= [F / P -0.25] *W/30 If 0.67 0.67 1.00 Building perimeter w/20' min. yard width F 556 Building perimeter of entire building P 606 Width of yards W 30 Allowable Actual Single Floor 15,007 11,982 OKAY 9.Comment: Concealed spaces need to be fireblocked/draftstopped per section 718. Draftstopping in attics to limit attic areas to areas no greater than 3000 sq feet. Response: Added note “FIREBLOCK/DRAFTSTOP PER IBC 718” to sheet A-301. 10.Comment: Equipment platfor m accessed by stairs? Response: Current design and drawings show a per manent ladder attached to the wall. See A-101 key not A6. 11.Comment: Access to the equipment platfor m? Response: See sheet A-101 keynote A6 calls out a ladder to access the equipment platfor m. 12.Comment: Need to meet all requirements of section 505. Response: Equipment platfor m complies with section 505. Updated A-101 to show the extent of the equipment platfor m 13.Comment: Roof fire classification as per Chapter 15? 305 1ST STREET ▪ IDAHO FALLS, ID 83402 ▪ 208.757.5700 ▪ RESINARCHITECTURE.COM Page 3 of 4 Response: Per table 1505.1 our roof is to be classified as C . With proposed metal roofing we comply with section 1505.4 Class C Roof Assemblies. 14.Comment: Panic hardware shall be installed per section 1010.10 Response: Panic hardware is not required per section 1010.1.10. Added general note “LABEL EGRESS DOOR WITH THE FOLLOWING NOTE "DOOR TO REMAIN UNLOCKED DURING BUSINESS HOURS" LETTER TO NOT BE LESS THAN 1" IN HEIGHT.” to sheet A-601. 15.Comment: Glass and glazing to meet requirements of Chapter 24. Response: Current drawing indicates where tempered glazing is required, see A-100, A-101, and A-601. 16.Comment: Drinking fountain? Response: Current design and drawing show a drinking fountain. See A-101 Keynote P4, P-2 called out as EWC-1 and P-3 is fixture schedule as EWC-1 Sincerely, Jonathan Gallup 305 1ST STREET ▪ IDAHO FALLS, ID 83402 ▪ 208.757.5700 ▪ RESINARCHITECTURE.COM Page 4 of 4 JattGatty AIA, NCARB