HomeMy WebLinkAboutPLANS - 22-00857 - 824 S 2315 W - Solar PanelsADDITIONAL NOTESPLAN SET LEGENDSHEET INDEXVICINITY MAPAPPLICABLE CODESABBREVIATIONSPROJECT INFORMATIONOCCUPANCY: R-3CONSTRUCTION TYPE: V-BUNSPRINKLEREDALL CONDUIT TO RUN ON EXTERIOR OF HOUSE UNLESSOTHERWISE NOTEDPV-1 PROJECT INFORMATION,VICINITY MAPPV-2 SITE PLAN, AERIAL VIEWPV-3 ELECTRICAL LINE DIAGRAMAND NOTESPV-4 REQUIRED SIGNAGEPROJECT INFORMATION,
VICINITY MAP
ISSUED FOR: PERMIT DATE
10/20/2022
www.bigdogenergy.com
SOLAR PHOTOVOLTAIC SYSTEM
RYAN SATRE
DESIGNED BY CONTRACTOR INFORMATION
PV-1824, S 2315 W,
REXBURG, ID 83440
BIG DOG RENEWABLE ENERGY
CONTRACTOR LIC #:IDAHO #017916
620 PHEASANT RIDGE DR
CHUBBUCK, ID 83202
208-242-3352 T
208-232-5935 F X__________________(E)EXISTING(N)NEWEXT EXTERIORINT INTERIOREMT ELECTRICAL METALLIC TUBINGRMT RIGID METALLIC TUBINGFMC FLEXIBLE METALLIC CONDUITVOC VOLTAGE OPEN CIRCUITVMP VOLTAGE AT MAX. POWERISC SHORT CIRCUIT CURRENTIMP CURRENT AT MAX. POWERNTS NOT TO SCALEMSPSUBACDCSLCMINVJBCBBATMAIN SERVICE PANELSUB SERVICE PANELAC DISCONNECTDC DISCONNECTSOLAR LOAD CENTERMONITORING METERINVERTERJUNCTION BOXCOMBINER BOXBATTERYPV PRODUCTION METERRAPID SHUTDOWN DISCONNECTPMRSDRYAN SATRE824 S 2315 W,REXBURG, ID 8344012 - URE FBM400MFG-BB (400W)PHOTOVOLTAIC MODULES1 - SOLAREDGE SE6000H-US WITH PRISMTECHNOLOGY (6000W) INVERTER(S)SYSTEM SIZE: 4.800 KW DC STCARRAY AREA: 252.53 SF1. ALL MODULES WILL BE GROUNDED IN ACCORDANCE WITHTHE CODE AND THE MANUFACTURES INSTALLATIONINSTRUCTIONS.2. ALL PLACARDS REQUIRED BY NEC 2017 CODE MACHINEPRINTED LETTERS IN A CONTRASTING COLOR TO THEPLACARD.3. LIQUID TIGHT FLEXIBLE CONDUIT SHALL BE SUNLIGHTRESISTANT.4. ELECTRICAL INSTALLATION WILL COMPLY WITH NEC 2017CODE.5. ALL SOLAR MODULES EQUIPMENT AND METALLICCOMPONENTS ARE TO BE BONDED.6. ALL PLUMBING AND MECHANICAL ROOF VENTS TO CLEARFROM PHOTOVOLTAIC ARRAY, OR EXTEND ABOVE SOLARPANELS.7. SOLAR PHOTOVOLTAIC SYSTEM TO BE INSTALLED ONRESIDENTIAL STRUCTURE.8.9.10.DESIGN COMPLYING WITH THE IBC 2018 CODE AND ALL LOCAL ORDINANCES AND POLICIES.THE PROJECT HAS BEEN DESIGNED TO WITHSTAND A MINIMUM 115 MPH WIND LOAD.THE SYSTEM WILL NOT BE INTERCONNECTED UNTIL APPROVAL FROM THE LOCAL JURISDICTION AND A UTILITY IS OBTAINED.11. IF THE MAIN SERVICE PANEL DOES NOT HAVE VERIFIABLEGROUNDING ELECTRODE, IT IS THE CONTRACTORSRESPONSIBILITY TO INSTALL SUPPLEMENTAL GROUNDINGELECTRODE.12. EACH MODULE WILL BE GROUNDED USING THE SUPPLIEDCONNECTION POINTS IDENTIFIED ON THE MODULE ANDTHE MANUFACTURERS INSTALLATION INSTRUCTIONS.13. A LADDER SHALL BE IN PLACE FOR INSPECTION INCOMPLIANCE WITH OSHA REGULATIONS.14. PROPER ACCESS AND WORKING CLEARANCE WILL BEPROVIDED "WARNING: PV POWER SOURCE" TO BE PLACEDEVERY 10 FT.15. GFCI PROTECTION IN INVERTER.ALL WORK TO COMPLY WITH THEFOLLOWING CODE:NEC 2017 CODEIBC/IRC/IFC 2018 CODE11/8/2022
MSPMTRACINVAERIAL VIEWSITE PLAN, AERIAL VIEW NISSUED FOR: PERMIT DATE
10/20/2022
www.bigdogenergy.com
SOLAR PHOTOVOLTAIC SYSTEM
RYAN SATRE
DESIGNED BY CONTRACTOR INFORMATION
PV-2824, S 2315 W,
REXBURG, ID 83440
BIG DOG RENEWABLE ENERGY
CONTRACTOR LIC #:IDAHO #017916
620 PHEASANT RIDGE DR
CHUBBUCK, ID 83202
208-242-3352 T
208-232-5935 F X__________________SITE PLANPANEL PLACEMENT MAY DIFFER FROMAPPROVED DESIGN DUE TO UNFORESEENOBSTRUCTIONS OR PERMITTING SETBACKSSOLAR PV MODULEINV INVERTERMSP MAIN SERVICE PANELAC AC DISCONNECTMTR METERABBREVIATIONSSCALE: NTSSCALE: NTSPROPOSED SYSTEMDC SIZE / AC SIZE:4.800 KW-DC / 6.000 KW-ACTOTAL # OF PANELS:12ROOF TYPE:SHINGLEROOF DESCRIPTIONROOF ARRAY PITCHAZIMUTH#124°90°ROOF #1AC DISCONNECTWITHIN 3’ FROM UTILITY METERS 2315 W3'PATHWAY18"CLEARANCE18"CLEARANCE11/8/2022
ELECTRICAL SINGLE LINE DIAGRAMELECTRICAL NOTESSINGLE LINE DIAGRAM RACKING & MODULES ARE GROUNDED VIA ACONTINUOUS #6AWG COPPER CONDUCTORCONNECTED W/ WEEBS - MODULES ARE FACTORYPROVIDED W/ 2 THREADED HOLES TO FACILITATELANDING OF THE LUGSALL EQUIPMENT SHALL BE PROPERLY GROUNDED ANDBONDED IN ACCORDANCE WITH ARTICLE 250. ALLCIRCUITS CONNECTED TO MORE THAN ONE SOURCESHALL HAVE OVERCURRENT DEVICES LOCATED SO ASTO PROVIDE OVERCURRENT PROTECTION FROM ALLSOURCES 690.9 (A)ISSUED FOR: PERMIT DATE
10/20/2022
www.bigdogenergy.com
SOLAR PHOTOVOLTAIC SYSTEM
RYAN SATRE
DESIGNED BY CONTRACTOR INFORMATION
PV-3824, S 2315 W,
REXBURG, ID 83440
BIG DOG RENEWABLE ENERGY
CONTRACTOR LIC #:IDAHO #017916
620 PHEASANT RIDGE DR
CHUBBUCK, ID 83202
208-242-3352 T
208-232-5935 F X__________________ALL MODULES WILL BE GROUNDED IN ACCORDANCEWITH CODE AND THE MANUFACTURER'SINSTALLATION INSTRUCTIONS.MODULE:URE FBM400MFG-BB (400W)Voc= 37.20V Isc= 13.68AVmp= 31.17V Imp= 12.84A1ELECTRICAL LINE DIAGRAMPV-3SCALE: NTSPROPOSED SYSTEMDC SIZE / AC SIZE:4.800 KW-DC / 6.000 KW-ACELECTRICAL EQUIPMENT CALLOUTS4,800W TOTAL SOLAR ARRAY12 URE FBM400MFG-BB (400W) PANELS1 STRING OF 12 MODULES CONNECTED IN SERIES @ INVERTERWIRE AND CONDUIT CALLOUTSSOLADECK MODEL 0783-41 JUNCTIONBOX/ROOF PENETRATION, 600V6.0kW INVERTER UNGROUNDEDSOLAREDGE SE6000H-US WITH PRISMTECHNOLOGY (240V) INVERTER240VAC, 25A, NEMA 3R, UL LISTED,(W/ INTEGRATED DC DISCONNECT)WITH INTEGRATED GFP, W/ INTEGRATED AFP(2) #10 AWG THWN-2(1) #10 AWG THWN-2 GND IN 3/4" EMT/FMCSOLAREDGE S440 OPTIMIZER ONE PER PANELABCDEFSQUARE D SAFETY SWITCH, #D222NRB250 VAC, 60A, NEMA 3R, FUSED, UL, NEMA,CSA, NOM CERTIFIED W/ 40A FUSES123BATTERYDC INPUT_~MPPT 1MPPT 23C12 MODULES IN SERIES1BAONE PER PANEL2STRING 11ELECTRICAL LINE DIAGRAMPV-3SCALE: NTS200A BI-DIRECTIONAL UTILITY METER, 1Ø, 240V(2)#10 AWG PV/RHW-2 IN FREE AIR(1)#6 AWG BARE COPPER GND IN FREE AIR1. PV ARRAYS ARE PER SINGLE LINE.2. PV ARRAY WIRING TO JUNCTION IS #10 AWG USE 2 W/FIELD INSTALLED MC CONNECTORS TO INTERFACE W/MODULES.3. PV ARRAY COMBINER/JUNCTION BOX PROVIDESTRANSITION FROM ARRAY WIRING TO CONDUITWIRING.4. USE UFER GROUND ELECTRODE SYSTEM FROMINVERTER TO EXISTING MAIN SERVICE GROUNDELECTRODE PER N.E.C. 250.58.5. GROUND ELECTRODE CONDUCTOR FROM INVERTERTO GROUND ELECTRODE TO BE MINIMUMPROTECTION OF BARE ARMOR SHEATHED CABLE FORALL CONDUCTOR SIZES.6. ALL GROUND CONNECTED TO MAIN SERVICE GROUNDIN MAIN SERVICE PANEL.7. CONNECTORS SHALL BE POLARIS OR EUROSTRIP ITCONNECTORS.8. INVERTER SHALL BE PER SINGLE LINE, SEE ATTACHEDCUT SHEET.9. INVERTER IS PER SINGLE LINE.10. AC DISCONNECT SHALL BE PER SINGLE LINE.11. EQUIPMENT GROUNDING CONDUCTORS ON AC ANDDC SIDE SIZED ACCORDING TO N.E.C. 690.12. POLE OF PV ARRAY REFERENCED TO GROUND AT THEINVERTER IN SINGLE LINE.13. ALL CONDUCTORS SHALL BE 600V, 90C STANDARDCOPPER. ALL CONDUCTORS IN CONDUIT SHALL BETHWN-2.14. MAXIMUM DC VOLTAGE DROP SHALL BE 2.5%15. ALL CONDUCTORS SHALL BE IN CONDUIT UNLESSOTHERWISE NOTED.16. ALL WORK TO COMPLY WITH NEC 2017 CODE.17. DC ARRAY CONDUCTORS ARE TO REMAIN OUTSIDE OFBUILDING PRIOR TO FUSIBLE COMBINER BOX ORFUSIBLE DC DISCONNECT MEANS.18. EXACT CONDUIT RUN LOCATIONS SUBJECT TOCHANGE.19. 3.0 PSF MAX (.5 PSF FROM RACKING, 2.5 PSF FROMMODULES) DEAD LOAD CONTRIBUTED FROM SOLARARRAY.20. ARC FAULT INSTALLED AT INVERTER OR IN COMBINERBOX.21. DC GROUND FAULT PROTECTION INTEGRATED ININVERTER.22. POINT OF CONNECTION BREAKER TO BE LOCATEDOPPOSITE END OF BUSBAR FROM MAIN UNLESSOTHERWISE NOTED.23. ANY UNDERGROUND WIRING METHODS WILL COMPLYWITH NEC 300.5(J), 300.7(B), 352.44, AND OTHERSECTIONS OF CHAPTER 3 AS APPLICABLE.24. ANY EXPOSED PVC CONDUIT SHALL COMPLY WITHNEC 352.1025. ALL PV SYSTEM DC CIRCUITS RUN INSIDE A BUILDINGSHALL BE CONTAINED IN A METAL RACEWAY INACCORDANCE TO NEC 690.31(G)26. COMPLIES WITH 705.12(B)(2)(3)(B)27. SUPPLY SIDE CONNECTION WITH LISTED INSULATIONPIERCING CONNECTORS IN ACCORDANCE WITH705.12(A) AND 230.8228. CONNECTION AT PANEL SECONDARY SERVICELOCATION29. COMPLIES WITH 705.12(B)(2)(1)(B)(2) #8 AWG THWN-2(1) #10 AWG THWN-2 GND IN 3/4" EMTAC DISCONNECTWITHIN 3’ FROM UTILITY METER250A (E) MAIN SERVICE PANEL SPLIT BUS, 1Ø, 240V(W/ 200A MAIN BREAKER AT LOCALIZED BUSBARCENTER FED & 50A MAX RATED PARALLELDISTRIBUTION BREAKER ONLY SLOT)ENG200A40ABREAKER 28FL1L2NGD3L1L2NGNO BATTERY BACKUPTO BE INCLUDED WITHTHIS PERMIT
REQUIRED SIGNAGEISSUED FOR: PERMIT DATE
10/20/2022
www.bigdogenergy.com
SOLAR PHOTOVOLTAIC SYSTEM
RYAN SATRE
DESIGNED BY CONTRACTOR INFORMATION
PV-4824, S 2315 W,
REXBURG, ID 83440
BIG DOG RENEWABLE ENERGY
CONTRACTOR LIC #:IDAHO #017916
620 PHEASANT RIDGE DR
CHUBBUCK, ID 83202
208-242-3352 T
208-232-5935 F X__________________
REQUIRED SIGNAGE 2. LABEL FOR SOLAR AC DISCONNECT:SYSTEM AC VOLTAGE: 240VTOTAL RATED AC AMPS: 40ASYSTEM AC VOLTAGE: 240V3. THE FOLLOWING SIGNAGE MUST HAVE A MINIMUM OF 3/8"HIGH LETTERING, IN ARIAL FONT (NON-BOLD), WITH CAPITALLETTERS, WHITE ON RED BACKGROUND AND A REFLECTIVE,WEATHER RESISTANT MATERIAL.1. PROVIDE A PLACARD WITH THE FOLLOWING WORKING IN 1/4"HIGH LETTERING PER NEC 690-17.AT THE MAIN SERVICE DISCONNECT PROVIDE A SIGN WITH THEFOLLOWING WORDING: FOLLOWING WORDING:THE SIGN SHOULD BE PLACED ON THE OUTSIDE COVER IF THE MAINSERVICE DISCONNECT IS OPERABLE WITH THE SERVICE PANEL CLOSED.CUSTOMER OWNEDON SITE POWER GENERATIONSYSTEM DISCONNECTDIRECT CURRENT PHOTOVOLTAIC SOURCESYSTEM AC VOLTAGE: 240VMAX AC CIRCUIT CURRENT: 25AMAX DC CURRENT PER OPTIMIZER: 15A8. THE FOLLOWING SIGN MUST BE PROVIDED ON THEOUTSIDE (OR WITHIN 3' OF) THE SERVICEPANELBOARD, AS REQUIRED PER NEC 690.56(C)(1):RAPID SHUTDOWN SWITCHFOR SOLAR PV SYSTEMPHOTOVOLTAIC SYSTEMEQUIPPED WITH RAPIDSHUTDOWNALL SIGNAGE MUST BE PERMANENTLY ATTACHED ANDBE WEATHER RESISTANT/SUNLIGHT RESISTANT AND CANNOT BEHAND-WRITTEN.NEC 110.21(B)FIRE DEPARTMENT REQUIRED SIGNAGE4. LABELS TO BE INSTALLED ON FACE OF THE UTILITY AC DISCONNECT:5. LABEL INSTALLATION AT INTERCONNECT BREAKER:10. SIGNAGE REQUIRED AT STRING INVERTER PER NEC 690.53:9. SIGNAGE REQUIRED AT SERVICE PANELBOARD PER NEC 690.54:7. AT PV DISCONNECT SWITCH AS REQUIRED PER NEC 690.56(C)(3):6. REFLECTIVE PLACARD AT SERVICE STATING:"SOLAR AC DISCONNECT"WARNING:ELECTRICAL SHOCK HAZARD.DO NOT TOUCH TERMINALS. TERMINALSON BOTH THE LINE AND LOAD SIDES MAYBE ENERGIZED IN THE OPEN POSITION.WARNING:INVERTER CONNECTION.DO NOT RELOCATE THISOVERCURRENT DEVICE.10.AT EVERY ENCLOSURE, EVERY 10’ ALONG CONDUIT OR MCCABLE, AN AT EACH SIDE OF WHERE THE CONDUIT OR CABLEPASSES THROUGH A WALL, FLOOR, OR ANY OTHER PARTITION.WARNING:POWER SOURCETHE MARKINGS SHALL BE PERMANENTLY AFFIXED AND VISIBLEAFTER INSTALLATION PER NEC 690.31(G)(3-4).WARNINGDUAL POWER SUPPLYSOURCES: UTILITY GRID ANDPV SOLAR ELECTRIC SYSTEM