Conclusion
Page 1 of Christina Allred
letter
Structural Letter of Approval
Terra Engineering Consulting (TEC) has performed a structural analysis for the existing
framing and load conditions and determined that the structure can support the additional load
of the proposed solar panel system. TEC has reviewed the site survey, photographs of the
existing framing, and the proposed PV array. The attached calculations are based off the
assumptions that the existing structural components are in good condition, that they meet
industry standards, and that the site survey provided by the client is accurate. The design
assumptions the calculations are based off are located in the attached References page. The
contractor shall notify TEC of any damage to the roof system encountered at the time of
installation. The design of the solar panel’s mounting hardware is to be provided by the
manufacturer or installer. Structural observation or construction inspections will not be
performed by TEC or their representatives.
The total load of the solar panels is assumed to not exceed 3 psf, and the typical 20 psf live
load will not be present in the area of the panels, as defined per Section 1607.13.5.1 in 2018
IBC. The structural evaluation shows that existing framing is able to withstand the additional
load while meeting current standards, allowing the structure to remain unaltered; see
calculations and span table attached. Regarding lateral loads, the wind load controls, and due
to the low profile of the panels (3” to 6”) as well as PV frame, wiring, conduit, and structural
component below the module causing restriction in airflow which allow it to be considered as
“partially enclosed structure”; thus the additional pressure on the structure is considered
negligible. The addition of total PV system weight result in an increase under 10% of the total
roof weight, and meets the seismic requirements in Section 502.5 of 2018 IEBC.
TEC concludes that the installation of solar panels on existing roof will not affect the
structure, and allows it to remain unaltered under the applicable design standards. These
conclusions are based on the attached calculations.
1863 GOLDENROD WAY / NORTH SARATOGA SPRINGS, UT 84045 / T (801)-616-6204
General Instructions
Best Regards,
Terra Engineering Consulting, PLLC
Ahmad Alshakargi, PE
Civil Engineer
Page 2 of Christina Allred
letter
The solar array mounting system shall be connected to every other truss/rafter (48" maximum
penetration spacing) in order to distribute the load evenly. The installer shall stagger the
connections into the roof framing to not overload any existing structural members. Installation
and waterproofing shall be performed within accepted industry standards.
10/24/2022
1863 GOLDENROD WAY / NORTH SARATOGA SPRINGS, UT 84045 / T (801)-616-6204
References Page 3 of Christina Allred letter
Design Parameter
Risk Category: II
Ground Snow load: 50 psf
Roof Snow load: 35 psf
Design Wind Speed: 115 mph (3 sec gust) per ASCE 7-16
Seismic Design Category: C
Wind Exposure Category: C
Existing Roof Structure
Roof framing: 2x6 Rafters at 24” O.C.
Roof material: Composite shingles
Roof slope: 8°
Roof type: Gable
Solar Panels
Weight: 3 psf
Code: 2018 International Building Code/ International Existing Building Code, ASCE 7-16,
and National Design Specification for Wood Construction (NDS) 2015 Edition
Connections: (1) 5/16” Lag screw with 2.5” min. embedment into the framing at 48” O.C.
spaced along the rail
1863 GOLDENROD WAY / NORTH SARATOGA SPRINGS, UT 84045 / T (801)-616-6204
Date:10/24/2022
Client:Christina Allred
Subject:Gravity load
Gravity load calculations
Snow load (S)Existing w/ solar panels
Roof slope (°):8 8
Ground snow load, pg (psf):50 50 ASCE 7-16, C7.2
Terrain category:C C ASCE 7-16, table 7.3-1
Exposure of roof:Fully exposed Fully exposed ASCE 7-16, table 7.3-1
Exposure factor, Ce:0.9 0.9 ASCE 7-16, table 7.3-1
Thermal factor, Ct:1.1 1.1 ASCE 7-16, table 7.3-2
Risk Category:II II ASCE 7-16, table 1.5-1
Importance Factor, Is: 1 1 ASCE 7-16, table 1.5-2
Flat roof snow load, pf (psf):35.0 35.0 ASCE 7-16, equation 7.3-1
Minimum roof snow load, pm (psf):20 20 ASCE 7-16, equation 7.3-4
Roof Surface type:Other Other ASCE 7-16, C7.4
Roof slope factor, Cs: 1 1 ASCE 7-16, C7.4
Sloped roof snow load, ps [psf]: 35.0 35.0
Roof dead load (D)
Roof pitch/12 1.7
Composite shingles 1.5 psf 1/2" Gypsum clg.psf
1/2" plywood 1 psf Insulation 0.5 psf
Framing 3 psf M, E & Misc 0.5 psf
Roof DL without PV
arrays 6.6 psf
PV Array DL 3 psf
Roof live load (Lr)Existing w/ solar panels
Roof Live Load 20 0 2018 IBC, Section 1607.13.5.1
ASD Load combination:
Existing With PV array
D [psf]6.6 9.6 ASCE 7-16, Section 2.4.1
D+L [psf]6.6 9.6 ASCE 7-16, Section 2.4.1
D+[Lr or S or R] [psf]41.6 44.6 ASCE 7-16, Section 2.4.1
32.9 35.9 ASCE 7-16, Section 2.4.1
Maximum gravity load [psf]:41.6 44.6
ASCE 7-16, equation 7.4-1, Design
Snow Load (S)
D+0.75L+0.75[Lr or S or R] [psf]
Date:10/24/2022
Client:Christina Allred
Subject:
Wind pressure calculations
Basic wind speed (mph) 115
Risk category II
Exposure category C
Roof type Gable
Figure for GCp values ASCE 7-16 Figure 30.3-2A-I
Zone 1 Zone 2 Zone 3
GCp (neg)-0.9 -1.7 -2.6
GCp (pos)0.5 0.5 0.5
zg (ft)900 (ASCE 7-16 Table 26.11-1)
α 9.5 (ASCE 7-16 Table 26.11-1)
Kzt 1 (ASCE 7-16 Equation 26.8-1)
Kh 0.9 (ASCE 7-6 Table 26.10-1)
Kd 0.85 (ASCE 7-16 Table 26.6-1)
Velocity Pressure,qh (psf)25.90 (ASCE 7-16 Equation 26.10-1)
Gcpi 0 (ASCE 7-16 Table 26.13-1)(0 for enclosed buildings)
Zone 1 Zone 2 Zone 3
W Pressure, (neg) [psf]-23.31 -44.03 -67.34
W Pressure, (pos) [psf]12.95 12.95 12.95
W Pressure, (Abs. max) [psf]23.31 44.03 67.34
Connection calculations
Capacity
Connection type:Lag screw Lag screw diameter:5/16
Embedment (in):2.5
Framing grade:SPF#2 G:0.42
Capacity [lbs/in]:205 (2015 NDS table 12.2A)
Number of screws:1
Total capacity [lbs]:512.50
Demand
Anchor spacing:48 in
Anchor spacing in roof corners:48 in
Zone
( 0.6 W
Pressure,
psf), see
Note 1
Max.
tributary
area (ft^2) Max Uplift force (lbs)
1 14.0 11 153.8
2 26.4 11 290.6
3 40.4 11 444.4
(only changes if structure located on
a hill or ridge)
Connection Meets Demand
Wind load and
Connection
Note 1: 0.6W results from dominant ASD combo [0.6D+ 0.6W] (ASCE 7-16 2.4.1).
Date:10/24/2022
Client:Christina Allred
Subject:Beam calculator
Beam Design (Roof)2x6 Rafters at 24 in o.c., span 10 ft max.
Load Combination
Combo DL LL W SL LLR E Sum
1 1.4 9.6 0 0 0 0 0 35 0 0 0 13.44
2 1.2 9.6 1.6 0 0 0 0.5 35 0 0 0 29.02
3 1.2 9.6 1 0 1 0 1.6 35 0 0 0 67.52
4 1.2 9.6 1 0 1 0 0.5 35 0 0 0 29.02
5 1.2 9.6 0 0 0 0 0.2 35 0 1 0 18.52
6 0.9 9.6 0 0 1 0 0 35 0 0 0 8.64
7 0.9 9.6 0 0 0 0 0 35 0 1 0 8.64
Roof
DL 9.6 psf (see Gravity load roof DL)
S 35 psf
W
E
LL 0 psf
RLL 0 psf (see Gravity load LL with PV arrays)
U 67.52 psf
beam spacing 2 ft o.c.
uniform load 135.04 plf
span 10 ft
Mu = w(l^2)/8 1428.7232 lb-ft
Number of joists 1
Flexure design
Cr 1.15 (2015 NDS Supp, p32)
Timber grade DFL#2 (2015 NDS Supp, table 4A)
Fb 900 psi (set SPF#2 as default)
Kf 2.54 (2015 NDS, table 2.3.5)
bending fact.0.85 (2015 NDS, table 2.3.6)
dimension
Cf (table 4A,
NDS supp
2015, p32)
S in^3
(table1B,
NDS supp
2015)
Fbu =
Mu/S
(psf)Fbu (psi)
moment of
inertia in^4
(table 1B,
NDS supp)
2x6 1.3 7.56 326565.3 2267.815 20.8
purlin size
λ (Table N3,
NDS 2015
p184)F'bn (psi) Fbu Fbu < F'bn
2x6 0.8 2323.9476 2267.815 Works
Design for deflection
we going to assume these calculations for U1 only since its clearly higher
we use the following equation to calculation max deflection, minimum interia, and deflection
service load combination:D+S
U 44.6 lb
Uniform load 89.2 plf
*convert all the units in the equaion to inch
max def. (ft)
E psi(Table
4A)w (plf) l (ft)
I (min)
(in^4)
Imin<
Ipurlin
0.038333333 1600000 89.2 9.2 19.53534 Works
Design for Shear
fvu = 1.5V/A V is shear Vu, and A cross sectional area of purlin found in table 1B
uniform load 135.04 plf
Vu 621.184 lb Vu = wl/2
Framing cross section 8.25 in^2
fvu 112.94 psi
Fv 180 psi (for DFL#2)
F'vn 311.04 psi
F'vn > fvu Works
Beam works