HomeMy WebLinkAboutCOMCHECK - 22-00795 - Madison Station Apartments - Bldg 1COMcheck Software Version 4.1.5.4
Envelope Compliance Certificate
Project Title:
2018 IECC
Project Type:New Construction
Vertical Glazing / Wall Area:12%
Location:Rexburg, Idaho
Climate Zone:6b
Construction Site:
Rexburg, ID 83440
Owner/Agent:
Bart Stevens
Designer/Contractor:
JRW & Associates
Project Information
Energy Code:
Sundance Apartments
Credits: 1.0 Required 1.0 Proposed
High Performance HVAC, 1.0 credit
Additional Efficiency Package(s)
Building Area Floor Area
1-Multifamily : Residential 9549
Envelope Assemblies
Assembly Cavity
R-Value
Cont.
R-Value
Proposed
U-Factor
Budget U-
Factor(a)
Gross Area
or
Perimeter
Roof 1: Attic Roof with Wood Joists, [Bldg. Use 1 - Multifamily]9549 0.0 38.0 0.025 0.021
Floor 1: Slab-On-Grade:Unheated, Vertical 3 ft., [Bldg. Use 1 -
Multifamily] (c)
906 ---10.0 0.510 0.520
NORTH
Interior Wall North: Wood-Framed, 16" o.c., [Bldg. Use 1 - Multifamily]1827 21.0 0.0 0.062 0.051
Door 6: Insulated Metal, Swinging, [Bldg. Use 1 - Multifamily]126 ------0.150 0.370
Exterior Wall North: Wood-Framed, 16" o.c., [Bldg. Use 1 - Multifamily]3862 21.0 0.0 0.062 0.051
Window - Fixed: Vinyl/Fiberglass Frame:Fixed, Perf. Specs.: Product ID
Pending, SHGC 0.25, [Bldg. Use 1 - Multifamily] (b)
175 ------0.200 0.360
Window - Operable: Vinyl/Fiberglass Frame:Operable, Perf. Specs.:
Product ID Pending, SHGC 0.25, [Bldg. Use 1 - Multifamily] (b)
175 ------0.200 0.430
Door 2: Glass (> 50% glazing):Nonmetal Frame, Non-Entrance Door,
Perf. Specs.: Product ID Pending, SHGC 0.25, [Bldg. Use 1 -
Multifamily] (b)
440 ------0.200 0.430
EAST
Interior Wall East: Wood-Framed, 16" o.c., [Bldg. Use 1 - Multifamily]2487 21.0 0.0 0.062 0.051
Door 7: Insulated Metal, Swinging, [Bldg. Use 1 - Multifamily]84 ------0.150 0.370
Breezeway Wall East: Wood-Framed, 16" o.c., [Bldg. Use 1 -
Multifamily]
2620 21.0 0.0 0.062 0.051
Window 5: Vinyl/Fiberglass Frame:Fixed, Perf. Specs.: Product ID NA,
SHGC 0.25, [Bldg. Use 1 - Multifamily] (b)
216 ------0.200 0.360
Exterior Wall East: Wood-Framed, 16" o.c., [Bldg. Use 1 - Multifamily]2981 21.0 0.0 0.062 0.051
Window 4: Vinyl/Fiberglass Frame:Operable, Perf. Specs.: Product ID
Product, SHGC 0.25, [Bldg. Use 1 - Multifamily] (b)
432 ------0.200 0.430
Door 3: Glass (> 50% glazing):Nonmetal Frame, Non-Entrance Door,
Perf. Specs.: Product ID Pending, SHGC 0.25, [Bldg. Use 1 -
240 ------0.200 0.430
Project Title:
Data filename:
Sundance Apartments
S:\Drawings\870-Sweetwater Apartment - Madison Station\870-Madison Station COMcheck.cck
10/24/22Report date:
91 ofPage
Assembly Cavity
R-Value
Cont.
R-Value
Proposed
U-Factor
Budget U-
Factor(a)
Gross Area
or
Perimeter
Multifamily] (b)
SOUTH
Interior Wall South: Wood-Framed, 16" o.c., [Bldg. Use 1 - Multifamily]1827 21.0 0.0 0.062 0.051
Door 5: Insulated Metal, Swinging, [Bldg. Use 1 - Multifamily]126 ------0.150 0.370
Exterior Wall South: Wood-Framed, 16" o.c., [Bldg. Use 1 - Multifamily]3862 21.0 0.0 0.062 0.051
Window - Fixed: Vinyl/Fiberglass Frame:Fixed, Perf. Specs.: Product ID
pending, SHGC 0.25, [Bldg. Use 1 - Multifamily] (b)
216 ------0.200 0.360
Window - Operable: Vinyl/Fiberglass Frame:Operable, Perf. Specs.:
Product ID pending, SHGC 0.25, [Bldg. Use 1 - Multifamily] (b)
216 ------0.200 0.430
Door 1: Glass (> 50% glazing):Nonmetal Frame, Non-Entrance Door,
Perf. Specs.: Product ID Pending, SHGC 0.25, [Bldg. Use 1 -
Multifamily] (b)
440 ------0.200 0.430
WEST
Interior Wall West: Wood-Framed, 16" o.c., [Bldg. Use 1 - Multifamily]2497 21.0 0.0 0.062 0.051
Door 8: Insulated Metal, Swinging, [Bldg. Use 1 - Multifamily]84 ------0.150 0.370
Breezeway Wall West: Wood-Framed, 16" o.c., [Bldg. Use 1 -
Multifamily]
2620 21.0 0.0 0.062 0.051
Window 6: Vinyl/Fiberglass Frame:Fixed, Perf. Specs.: Product ID NA,
SHGC 0.25, [Bldg. Use 1 - Multifamily] (b)
216 ------0.200 0.360
Exterior Wall West: Wood-Framed, 16" o.c., [Bldg. Use 1 - Multifamily]2981 21.0 0.0 0.062 0.051
Window 7: Vinyl/Fiberglass Frame:Operable, Perf. Specs.: Product ID
Pending, SHGC 0.25, [Bldg. Use 1 - Multifamily] (b)
432 ------0.200 0.430
Door 4: Glass (> 50% glazing):Nonmetal Frame, Non-Entrance Door,
Perf. Specs.: Product ID Pending, SHGC 0.25, [Bldg. Use 1 -
Multifamily] (b)
240 ------0.200 0.430
(a)Budget U-factors are used for software baseline calculations ONLY, and are not code requirements.
(b)Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.
(c)Slab-On-Grade proposed and budget U-factors shown in table are F-factors.
Envelope Compliance Statement
Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed envelope systems have been
designed to meet the 2018 IECC requirements in COMcheck Version 4.1.5.4 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Envelope PASSES: Design 16% better than code
Project Title:
Data filename:
Sundance Apartments
S:\Drawings\870-Sweetwater Apartment - Madison Station\870-Madison Station COMcheck.cck
10/24/22Report date:
92 ofPage
Inspection Checklist
Requirements: 0.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.1.5.4
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2018 IECC
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
C103.2
[PR1]1
Plans and/or specifications provide all
information with which compliance
can be determined for the building
envelope and document where
exceptions to the standard are
claimed.
Complies
Does Not
Not Observable
Not Applicable
C402.4.1
[PR10]1
The vertical fenestration area <= 30
percent of the gross above-grade wall
area.
Complies
Does Not
Not Observable
Not Applicable
C402.4.1
[PR11]1
The skylight area <= 3 percent of the
gross roof area.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Sundance Apartments
S:\Drawings\870-Sweetwater Apartment - Madison Station\870-Madison Station COMcheck.cck
10/24/22Report date:
93 ofPage
Section
#
& Req.ID
Footing / Foundation Inspection Complies?Comments/Assumptions
C303.2
[FO4]2
Slab edge insulation installed per
manufacturer’s instructions.
Complies
Does Not
Not Observable
Not Applicable
C303.2.1
[FO6]1
Exterior insulation protected against
damage, sunlight, moisture, wind,
landscaping and equipment
maintenance activities.
Complies
Does Not
Not Observable
Not Applicable
C105
[FO3]2
Installed slab-on-grade insulation type
and R-value consistent with insulation
specifications reported in plans and
COMcheck reports.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.2.4
[FO7]2
Slab edge insulation depth/length.
Slab insulation extending away from
building is covered by pavement or
>= 10 inches of soil.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Sundance Apartments
S:\Drawings\870-Sweetwater Apartment - Madison Station\870-Madison Station COMcheck.cck
10/24/22Report date:
94 ofPage
Section
#
& Req.ID
Framing / Rough-In Inspection Complies?Comments/Assumptions
C303.1.3
[FR12]2
Fenestration products rated in
accordance with NFRC.
Complies
Does Not
Not Observable
Not Applicable
C303.1.3
[FR13]1
Fenestration products are certified as
to performance labels or certificates
provided.
Complies
Does Not
Not Observable
Not Applicable
C402.4.3
[FR10]1
Vertical fenestration SHGC value.Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.4.3,
C402.4.3.
4
[FR8]1
Installed vertical fenestration U-factor
and SHGC consistent with label
specifications and as reported in plans
and COMcheck reports.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.5.1.
2.1
[FR19]1
The building envelope contains a
continuous air barrier that is sealed in
an approved manner and material
permeability <= 0.004 dfm/ft2. Air
barrier penetrations are sealed in an
approved manner.
Complies
Does Not
Not Observable
Not Applicable
C402.5.2,
C402.5.4
[FR18]3
Factory-built fenestration and doors
are labeled as meeting air leakage
requirements.
Complies
Does Not
Not Observable
Not Applicable
C402.5.7
[FR17]3
Vestibules are installed on all building
entrances. Doors have self-closing
devices.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Sundance Apartments
S:\Drawings\870-Sweetwater Apartment - Madison Station\870-Madison Station COMcheck.cck
10/24/22Report date:
95 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C402.5.5,
C403.2.4.
3
[ME3]3
Stair and elevator shaft vents have
motorized dampers that automatically
close. Refernece section C403.7.7 for
operational details.
Complies
Does Not
Not Observable
Not Applicable
C403.7.7
[ME58]3
Outdoor air and exhaust systems have
motorized dampers that automatically
shut when not in use and meet
maximum leakage rates. Check
gravity dampers where allowed.
Reference section language for
operational details.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Sundance Apartments
S:\Drawings\870-Sweetwater Apartment - Madison Station\870-Madison Station COMcheck.cck
10/24/22Report date:
96 ofPage
Section
#
& Req.ID
Insulation Inspection Complies?Comments/Assumptions
C303.1
[IN3]1
Roof insulation installed per
manufacturer’s instructions. Blown or
poured loose-fill insulation is installed
only where the roof slope is <=3 in
12.
Complies
Does Not
Not Observable
Not Applicable
C402.2.1
[IN20]1
Insulation installed on a suspended
ceiling having ceiling tiles is not being
specified for roor/ceiling assemblies.
Continuous insulation board installed
in 2 or more layers with edge joints
offset between layers.
Complies
Does Not
Not Observable
Not Applicable
C303.1
[IN10]2
Building envelope insulation is labeled
with R-value or insulation certificate
providing R-value and other relevant
data.
Complies
Does Not
Not Observable
Not Applicable
C303.2
[IN7]1
Above-grade wall insulation installed
per manufacturer’s instructions.
Complies
Does Not
Not Observable
Not Applicable
C303.2.1
[IN14]2
Exterior insulation is protected from
damage with a protective material.
Verification for exposed foundation
insulation may need to occur during
Foundation Inspection.
Complies
Does Not
Not Observable
Not Applicable
C105
[IN6]1
Installed above-grade wall insulation
type and R-value consistent with
insulation specifications reported in
plans and COMcheck reports.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.2.3
[IN8]2
Installed floor insulation type and R-
value consistent with insulation
specifications reported in plans and
COMcheck reports.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.2.6
[IN18]3
Radiant panels and associated
components, designed for heat
transfer from the panel surfaces to the
occupants or indoor space are
insulated with a minimum of R-3.5.
Complies
Does Not
Not Observable
Not Applicable
C105
[IN2]1
Installed roof insulation type and R-
value consistent with insulation
specifications reported in plans and
COMcheck reports. For some ceiling
systems, verification may need to
occur during Framing Inspection.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.5.1.
1
[IN1]1
All sources of air leakage in the
building thermal envelope are sealed,
caulked, gasketed, weather stripped
or wrapped with moisture vapor-
permeable wrapping material to
minimize air leakage.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Sundance Apartments
S:\Drawings\870-Sweetwater Apartment - Madison Station\870-Madison Station COMcheck.cck
10/24/22Report date:
97 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C402.5.6
[FI37]1
Weatherseals installed on all loading
dock cargo door openings and provide
direct contact along the top and sides
of vehicles parked in the doorway.
Complies
Does Not
Not Observable
Not Applicable
C402.5.8
[FI26]3
Recessed luminaires in thermal
envelope to limit infiltration and be IC
rated and labeled. Seal between
interior finish and luminaire housing.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Sundance Apartments
S:\Drawings\870-Sweetwater Apartment - Madison Station\870-Madison Station COMcheck.cck
10/24/22Report date: