Corrections in the following table need to be applied before a permit can be issued
Review Report
Revisions Required
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
4 SITE PLAN Free text Cody Jones : Building Open 4 As per table 602: A IIB building classified as a S1 occupancy
type, with less then 10' separation distance requires a 1 hour
exterior wall.
4 SITE PLAN Free text Stan Crittenden : Fire Open 4 International fire code requires that the fire department be
able to park and
reach anywhere on the building with a 150' hose. IFC 503.1.1
4 SITE PLAN Free text Stan Crittenden : Fire Open 4 IFC 2018 appendix B requires a IIB construction type building
with a
square footage of 4,600 sq.ft. to have a water source that can
supply
1,500 gpm. for fire suppression efforts. See Table B105.1(2)
# 21-00577
Madison County - Commercial
Report Date: 08.10.2021
Approval of plans does not constitute approval of variance from code
Page 1 of 1
Powered by TCPDF (www.tcpdf.org)
SITE MAP
VICINITY MAP
Date:
Connect Engineering
APPROVAL SIGNATURES:
of
DEVELOPMENT DRAWINGS FOR:
STATE MAP
SHEET NO.
PLOT DATE: 6/17/2021 11:46
AM
Date:
The Civil Connection
1150 Hollipark Dr. Idaho Falls, ID 83401
208.881.0081
1 6
THORNTON STORAGE
THORNTON, ID
MADISON COUNTY
THORNTON, ID
N0
°
0
6
'
5
3
"
E
48
6
.
2
5
'
S89° 59' 05"E
354.02'
L =6 0 2 .2 8 '
R =5 2 9 5 .0 0 '
D =6 °3 1 '0 2 "
C =S 3 6 °0 8 '1 4 "W
N0
°
0
6
'
5
3
"
E
48
6
.
2
5
'
S89° 59' 05"E
354.02'
L =6 0 2 .2 8 '
R =5 2 9 5 .0 0 '
D =6 °3 1 '0 2 "
C =S 3 6 °0 8 '1 4 "W
-2
.
0
3
%
-2
.
4
3
%
-3.47%
-2.20%
-2
.
3
2
%
-2
.
3
4
%
-2.2
6
%
-2.
9
4
%
-3.47%
-2
.
8
1
%
-2.02%
-2
.
7
3
%
-0.22%
-0.20%
-1.
1
3
%
-0.
4
4
%
-0.22%
-0.21%
-2
.
7
6
%
-
3
.
3
5
%
-
3
.
2
1
%
-3
.
1
2
%
-3.44%
-3
.
3
5
%
-3.86%
48
5
6
4856
FG: 4855.83
FG: 4855.83
FG: 4855.83
FG: 4855.88-0
.
5
0
%
-0
.
9
0
%
-2.
2
0
%
FF: 4856.00
FF: 4856.00
FF: 4856.00
FF: 4856.00
4855.33
GRATE
4855.34
GRATE
4855.23
GRATE
4855.21
GRATE
4855.45
GB
4855.37
GB
4855.54
GB
4855.49
GB
4856.01
EXIST
BOUNDARY EL.
4855.10
EXIST
BOUNDARY EL.
4854.23
EXIST
BOUNDARY EL.
4854.86
EXIST
BOUNDARY EL.
4853.95
EXIST
BOUNDARY EL.
4854.81
EXIST
BOUNDARY EL.
FG: 4855.83 FG: 4855.83 FG: 4855.83
FG: 4855.83
4
8
5
5
FG: 4855.83
FG: 4855.83
FG: 4855.83
FG: 4855.83 FG: 4855.83
FG: 4855.83
FG: 4855.83
FG: 4855.83
FG: 4855.83
FG: 4855.83
4854.00
BTM
4854.00
BTM
48
5
5
4854.45
EXIST
BOUNDARY EL.
CHECK BY
SHEETS
DRAWN BY
JOB NO:
DATE:
OF
SHEET
BDJTT
SH
E
E
T
N
A
M
E
:
PR
O
J
E
C
T
:
LO
C
A
T
I
O
N
:
2020-134
DATE:DATE: June 17, 2021
DA
T
E
RE
V
I
S
I
O
N
S
CL
I
E
N
T
:
Th
e
C
i
v
i
l
C
o
n
n
e
c
t
i
o
n
11
5
0
H
o
l
l
i
p
a
r
k
D
r
.
I
d
a
h
o
F
a
l
l
s
,
I
D
8
3
4
0
1
20
8
.
8
8
1
.
0
0
8
1
PRELIMINARY FOR
REVIEW ONLY
4
6
TH
O
R
N
T
O
N
S
T
O
R
A
G
E
SI
T
E
P
L
A
N
TH
O
R
N
T
O
N
,
I
D
INSTALL INFILTRATION CATCH BASIN DETAIL PER SHEET 3602-3
140.00'
20
.
0
0
'
20.00'
230.00'
20
.
0
0
'
2
0
.
0
0
'
110
.
0
0
'
160.00'
50
.
0
0
'
30
.
0
0
'
602-3
602-3
602-3
602-3
29.94'
2
6
.
2
5
'
20.00'
60
.
0
0
'
24
.
9
9
'
41
.
6
8
'
EX
I
S
T
I
N
G
B
U
I
L
D
I
N
G
EXISTING BUILDING
100-1
100-1
RETAIN AND PROTECT100-1
FF: 4855.56
FF: 4856.88
4" DEPTH CRUSHED 3 4" MINUS
AGGREGATE LEVELING COURSE
COMPACTED TO 95% ASTM D698
12" DEPTH UNCRUSHED
AGGREGATE SUBBASE COURSE
COMPACTED TO 95% ASTM D698
SUBGRADE EARTH COMPACTED
TO 95% ASTM D698
DRIVE AISLE SECTION
8.77 ft
6.
4
4
f
t
As per table 602: A IIB building classified as a S1 occupancy type, with less then
10' separation distance requires a 1 hour exterior wall.
International fire code requires that the fire department be able to park and
reach anywhere on the building with a 150' hose. IFC 503.1.1
IFC 2018 appendix B requires a IIB construction type building with a
square footage of 4,600 sq.ft. to have a water source that can supply
1,500 gpm. for fire suppression efforts. See Table B105.1(2)