Loading...
HomeMy WebLinkAboutUPDATED PLANS - 22-00396 - 698 Tanglewood Dr - Solar PanelsGENERAL NOTES SHEET INDEX PAGE #DESCRIPTION PV - 01 TITLE SHEET PV - 02 SITE PLAN / STRING DETAILS PV - 03 ELECTRICAL LINE DIAGRAM PV - 04 RACKING DETAILS PV - 05 ELECTRICAL LABELS 1.ALL MATERIALS AND WORKMANSHIP SHALL CONFORM TO THE LATEST STATE CODE OF REGULATIONS, NATIONAL ELECTRICAL CODE EDITION AND ALL APPLICABLE LOCAL CODES AND REGULATIONS. 2.ALL PANELS, SWITCHES, ETC. SHALL HAVE SUFFICIENT GUTTER SPACE AND LUGS IN COMPLIANCE TO UL REQUIREMENTS TO ACCOMMODATE CONDUCTORS SHOWN. 3.WHERE WIRE SIZES ARE INDICATED ON PLANS, FOR INDIVIDUAL CIRCUITS, THE WIRE SIZE INDICATED SHALL APPLY TO THE COMPLETE CIRCUIT, UNLESS OTHERWISE NOTED. 4.CONTRACTOR SHALL EXTEND WIRING FROM ALL JUNCTION BOXES, SWITCHES, ETC. AND MAKE FINAL CONNECTION AS REQUIRED TO ALL BUILDING EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS. 5.DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK INCLUDED. FOLLOW DRAWING IN LAYING OUT WORK AND CHECK DRAWINGS OR OTHER TRADES RELATING TO WORK TO VERIFY SPACE IN WHICH WORK WILL BE INSTALLED. MAINTAIN HEADROOM AND MINIMUM CODE REQUIRED WORKING CLEARANCES AT ALL TIMES. 6.ALL EXTERIOR ELECTRICAL DEVICES AND EQUIPMENT INCLUDING THOSE THAT ARE EXPOSED TO OUTSIDE ENVIRONMENT SHALL BE WEATHERPROOF TYPE, NEMA 3R. 7.DISCONNECT SWITCHES SHALL BE MOUNTED ON INDIVIDUAL SUPPORTS, OR OTHERWISE DIRECTLY ON EQUIPMENT, PROVIDED. 8.NO MODIFICATION TO EQUIPMENT IS NECESSARY. ALL ELECTRIC MATERIAL SHALL BE LISTED BY "UL" FOR THE TYPE OF APPLICATION AND "UL" LABEL SHALL APPEAR ON ALL ELECTRICAL EQUIPMENT. 9.WIRING METHOD SHALL BE EMT ABOVE GROUND AND MOUNTED IN CONCEALED SPACES (UNLESS APPROVED OTHERWISE) AND SCHEDULE - 40 PVC FOR BELOW GROUND INSTALLATION UNLESS NOTED OTHERWISE. CONTRACTORS LICENSE # & TYPE IDAHO #036784 IDAHO CLASS - B100, E200, E201, E202 APPLICABLE CODES 2020 NATIONAL ELECTRIC CODE (NEC) 2018 INTERNATIONAL RESIDENTIAL CODE (IRC) 2018 INTERNATIONAL BUILDING CODE (IBC) 2018 INTERNATIONAL FIRE CODE (IFC) NABCEP CERTIFICATION MICHAEL GARRISON PV 011818-019231 MODULE(S) MODULE TYPE NUMBER OF MODS MODULE SIZE: WATTS SYSTEM SIZE: WATTS TRINA 22 325 7150 WATTS INVERTER(S) MANUFACTURER MODEL NUMBER OF INVERTERS SYSTEM OUTPUT SOLAREDGE SE7600H 1 31.67 AMPS JOB DETAILS ROOF MATERIAL STANDARD ASPHALT SHINGLE ROOF SQ FT OF ARRAY ARRAY AZIMUTH(S)180°399.1 RACKING TYPE UL LISTED IRONRIDGE RACKING SYSTEM ANCHOR SPACING MAXIMUM 48'' ANCHORED CENTERS INSTALLATION SURFACE ANGLE 33.69° TE L T V E N T U R E S , L L C 1 16" = 1' SHEET # SCALE: RE V I S I O N S : 23 9 1 S . 1 5 6 0 W . S U I T E C WO O D S C R O S S , U T 8 4 0 8 7 PH O N E : ( 8 0 1 ) 3 1 7 - 8 4 4 4 PR O J E C T # 8- 9 - 2 0 2 2 N/ A N/ A N/ A DA T E : 8/ 9 / 2 0 2 2 DE S I G N E R : R F L E M I N G SY S T E M S I Z E : 71 5 0 W A T T S AH J : RE X B U R G TI M O T H Y N G 69 8 T A N G L E W O O D D R I V E RE X B U R G , I D A H O 8 3 4 4 0 12 4 7 0 9 PV-01AERIAL VICINITY SOURCE CIRCUITS # OF OPTIMIZERS 1 11 2 11 SYMBOL:MEANING: MIN 3' FIRE CODE CONCRETE NEMA-4 ROOFTOP JUNCTION BOX METER-MAIN PANEL SE INVERTER AC DISCONNECT EXISTING-INTERIOR SUB PANEL M I D SP M D I 3' 3' SP 1 1 1 1 1 1 1 1111222 2 2 2 2 2 2 2 2 TE L T V E N T U R E S , L L C 1 16" = 1' SHEET # SCALE: RE V I S I O N S : 23 9 1 S . 1 5 6 0 W . S U I T E C WO O D S C R O S S , U T 8 4 0 8 7 PH O N E : ( 8 0 1 ) 3 1 7 - 8 4 4 4 PR O J E C T # 8- 9 - 2 0 2 2 N/ A N/ A N/ A DA T E : 8/ 9 / 2 0 2 2 DE S I G N E R : R F L E M I N G SY S T E M S I Z E : 71 5 0 W A T T S AH J : RE X B U R G TI M O T H Y N G 69 8 T A N G L E W O O D D R I V E RE X B U R G , I D A H O 8 3 4 4 0 12 4 7 0 9 MODULE(S) MODULE TYPE NUMBER OF MODS MODULE SIZE: WATTS SYSTEM SIZE: WATTS TRINA 22 325 7150 WATTS INVERTER(S) MANUFACTURER MODEL NUMBER OF INVERTERS SYSTEM OUTPUT SOLAREDGE SE7600H 1 31.67 AMPS JOB DETAILS ROOF MATERIAL STANDARD ASPHALT SHINGLE ROOF SQ FT OF ARRAY ARRAY AZIMUTH(S)180°399.1 RACKING TYPE UL LISTED IRONRIDGE RACKING SYSTEM ANCHOR SPACING MAXIMUM 48'' ANCHORED CENTERS INSTALLATION SURFACE ANGLE 33.69° PV-02 CONDUIT AND CONDUCTOR SCHEDULE TAG#DESCRIPTION 1 (4) #10 PV WIRE, (1) #6 BARE COPPER EG 2 (1) #10-4 ARMORED CABLE WITH (1) #10 EG 3 (1) MIN 3/4'' EMT, (4) #10 THWN-2 CU, (1) #10 THWN-2 CU EG 4 (1) MIN 3/4'' EMT, (3) #8 THWN-2 CU, (1) #8 THWN-2 CU EG PHOTOVOLTAIC AC OUTPUT AC OUTPUT CURRENT 31.67 AMPS NOMINAL AC VOLTAGE 240 INTERCONNECTION PCC MADE IN EXISTING EXTERIOR 240VAC, 200AAC 1 PHASE METER MAIN PANEL WITH LOAD SIDE CONNECTION USING (1) 40AAC 2 POLE SOLAR BREAKER RATED FOR BACKFEED. THIS CONNECTION SHALL BE MADE IN CONFORMANCE WITH 2020 NEC 705.12(B)(3)(2). BREAKER TO BE LOCATED ON EMPTY SPACE ON 200AAC BUS BAR WITH 200AAC MAIN BREAKER. ((200AAC X 1.2)-200AAC = 40AAC ALLOWABLE SOLAR). INVERTER SPECIFICATIONS MANUFACTURER SOLAREDGE MODEL SE7600H-US MAX DC INPUT VOLTAGE 480 VDC MAX OUTPUT POWER 7600 W MAX DC INPUT POWER 11800 W NOMINAL AC OUTPUT VOLTAGE 240 VAC NOMINAL AC OUTPUT CURRENT 32 A MAX FUSE (OCPD)40 A TOTAL PANELS:22 TOTAL (S440) OPTIMIZERS:22 DC SYSTEM SIZE:7150 WATTS NOTES: 1.THIS SYSTEM MEETS THE REQUIREMENTS OF NEC 690.41 2.THE DC CONDUCTORS ARE NOT BONDED TO GROUND AND THE INVERTERS DO NOT REQUIRE A GEC. 3.NEC 690.43(C) STRUCTURE AS EQUIPMENT GROUNDING CONDUCTOR ALLOWS FOR EQUIPMENT TO BE USED AS THE EGC IN A PHOTOVOLTAIC SYSTEM. 4.THE DEVICES LISTED AND IDENTIFIED FOR GROUNDING THE EQUIPMENT MAY BE STAND-ALONE GROUNDING COMPONENTS OR UL-2703 LISTED MOUNTING HARDWARE. MODULES ARE BONDED TO THE RACKING WITH LISTED AND APPROVED GROUNDING COMPONENTS. 5.EQUIPMENT OPERATING 150 VOLTS OR GREATER SHALL ONLY BE SERVICED OR REPLACED BY QUALIFIED PERSONNEL. FIELD PROTECTION MAY BE IN THE FORM OF CONDUIT, CLOSED CABINET OR AN ENCLOSURE WHICH REQUIRE USE OF TOOLS TO OPEN. 6.SOLAR PHOTOVOLTAIC SYSTEM EQUIPMENT WILL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF ART. 690 OF THE 2020 NEC. 7.LOCAL UTILITY PROVIDER SHALL BE NOTIFIED PRIOR TO USE AND ACTIVATION OF ANY SOLAR PHOTOVOLTAIC INSTALLATION. 8.ALL SOLAR MODULES, EQUIPMENT, AND METALLIC COMPONENTS ARE TO BE GROUNDED IN ACCORDANCE WITH CODE AND THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. 9.WIRING MUST BE PERMANENTLY AND COMPLETELY HELD OFF OF THE ROOF SURFACE PER NEC 110.2, 110.3(A), 110.3(B) & 300.4 10.SYSTEM WILL EITHER BE GROUNDED USING A SOLID #6 COPPER GROUND WIRE TO CONNECT EACH ROW OF RAILS VIA AN OUTDOOR-RATED TIN-PLATED COPPER GROUND LUG TO EACH ROOFTOP JUNCTION BOX AND/OR SYSTEM WILL BE GROUNDED VIA DYNOBONDS CONNECTING EACH PANEL TOGETHER. 1111 NEMA-4SOLADECK J-BOX NEMA 3R JUNCTION BOX 3 2 1 4 SR SE 7600H-US BI-DIRECTIONAL SINGLE PHASE UTILITY METER UTILITY GRID 120/240V EXISTING 200A SERVICE ENTRANCE 40A/2P 200A/2P 60A 120/240V NON-FUSED DISCONNECT WITHIN 5' OF UTILITY METER 4 MODULE SPECIFICATIONS MANUFACURER TRINA MODEL TSM-325DE06M.08(II) MAX POWER-POINT CURRENT (IMP)-AMPS 9.67 MAX POWER-POINT VOLTAGE (VMP)-VOLTS 33.6 OPEN CIRCUIT VOLTAGE (VOC)-VOLTS 40.4 SHORT CIRCUIT CURRENT (ISC)-AMPS 10.30 MAX SERIES FUSE (OCPD)-AMPS 20 MAX POWER (PMAX)325 WATTS TE L T V E N T U R E S , L L C 1 16" = 1' SHEET # SCALE: RE V I S I O N S : 23 9 1 S . 1 5 6 0 W . S U I T E C WO O D S C R O S S , U T 8 4 0 8 7 PH O N E : ( 8 0 1 ) 3 1 7 - 8 4 4 4 PR O J E C T # 8- 9 - 2 0 2 2 N/ A N/ A N/ A DA T E : 8/ 9 / 2 0 2 2 DE S I G N E R : R F L E M I N G SY S T E M S I Z E : 71 5 0 W A T T S AH J : RE X B U R G TI M O T H Y N G 69 8 T A N G L E W O O D D R I V E RE X B U R G , I D A H O 8 3 4 4 0 12 4 7 0 9 PV-03 TYP. IRONRIDGE UFO + END SLEEVE TYP. IRONRIDGE UFO MODULE CLAMP TYP. QUICKBOLTS 5 1/4 " MICRO FLASHING TYP. IRONRIDGE XR10 RAIL TYP. IRONRIDGE L-FOOT TYP. IRONRIDGE UFO + END SLEEVE TYP. IRONRIDGE UFO MODULE CLAMP TYP. QUICKBOLTS 5 1/4 " MICRO FLASHING TYP. IRONRIDGE XR10 RAIL TYP. IRONRIDGE L-FOOT LANDSCAPE INSTALLATION PORTRAIT INSTALLATION MEETS OR EXCEEDS IBC IRC CONSTRUCTION STANDARDS CASE 1 Load Calculations 2X4 Construction 24'' on Center Trusses TRINA 325 Watt PV Panel: < 50 LBS/Panel IRONRIDGE CONNECTION HARDWARE: .735 PLF * 6.66 FT/PANEL = 4.8951 LBS/PANEL SYSTEM INCLUDES 22 PANELS AND IRONRIDGE MOUNTING HARDWARE: 22 X 54.9 = 1207.8 LBS A = L x W (PANEL): 20.07 SQ FT ARRAY: 20.07 SQ FT x 22 = 441.54 SQ FT SNOW LOAD: 441.54 SQ FT x 30 PSF = 13246.2 LBS PULL OUT STRENGTH: 44 5/16 LAG BOLTS 44 x 3'' EMBED x 205 LBS = 27060 LBS TOTAL WEIGHT = PANELS + HARDWARE = 1207.8 LBS 1207.8 LBS / 441.54 SQ FT = 3.02 PSF ROOF LOAD BEARING: 1207.8 LBS / 44 STANDOFFS = 27.45 LBS MAXIMUM 48'' ANCHORED CENTERS QUICKBOLT 5 1/4" MICROFLASHING KIT COMPOSITE SHINGLE ROOF IRONRIDGE UFO MODULE CLAMP IRONRIDGE UFO END SLEEVE IRONRIDGE XR10 RAIL IRONRIDGE RAIL MOUNTING HARDWARE IRONRIDGE SLOTTED L-FOOT QUICKSCREWS 5 1/4"QUICKBOLT QUICKSCREWS 3" MICROFLASHING TE L T V E N T U R E S , L L C 1 16" = 1' SHEET # SCALE: RE V I S I O N S : 23 9 1 S . 1 5 6 0 W . S U I T E C WO O D S C R O S S , U T 8 4 0 8 7 PH O N E : ( 8 0 1 ) 3 1 7 - 8 4 4 4 PR O J E C T # 8- 9 - 2 0 2 2 N/ A N/ A N/ A DA T E : 8/ 9 / 2 0 2 2 DE S I G N E R : R F L E M I N G SY S T E M S I Z E : 71 5 0 W A T T S AH J : RE X B U R G TI M O T H Y N G 69 8 T A N G L E W O O D D R I V E RE X B U R G , I D A H O 8 3 4 4 0 12 4 7 0 9 PV-04 ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND BE WEATHER RESISTANT/SUNLIGHT RESISTANT AND CANNOT BE HAND-WRITTEN CONDUITS, ENCLOSURES, OR MC Cable THAT CONTAIN DC CIRCUITS EVERY 10' LOCATED AT SERVICE PANEL BOARD NEC 690.54 LOCATED ON STRING INVERTER (IF USED) NEC 690.53 LOCATED AT MAIN PV DISCONNECT NEC 690.13(B) LOCATED AT RAPID SHUTDOWN DISCONNECT NEC 690.56(C)(3) LOCATED AT SERVICE PANEL NEC 705.10 LOCATED AT PV BREAKER IN PANEL BOARD NEC 705.12(B)(2)(3)(b) LOCATED AT SERVICE PANEL NEC 690.56(C)(1) 240V LOCATED ON MULTI BRANCH PV SUB-PANEL 480 20 30 240 32 A TE L T V E N T U R E S , L L C 1 16" = 1' SHEET # SCALE: RE V I S I O N S : 23 9 1 S . 1 5 6 0 W . S U I T E C WO O D S C R O S S , U T 8 4 0 8 7 PH O N E : ( 8 0 1 ) 3 1 7 - 8 4 4 4 PR O J E C T # 8- 9 - 2 0 2 2 N/ A N/ A N/ A DA T E : 8/ 9 / 2 0 2 2 DE S I G N E R : R F L E M I N G SY S T E M S I Z E : 71 5 0 W A T T S AH J : RE X B U R G TI M O T H Y N G 69 8 T A N G L E W O O D D R I V E RE X B U R G , I D A H O 8 3 4 4 0 12 4 7 0 9 PV-05 TE L T V E N T U R E S , L L C 1 16" = 1' SHEET # SCALE: RE V I S I O N S : 23 9 1 S . 1 5 6 0 W . S U I T E C WO O D S C R O S S , U T 8 4 0 8 7 PH O N E : ( 8 0 1 ) 3 1 7 - 8 4 4 4 PR O J E C T # 8- 9 - 2 0 2 2 N/ A N/ A N/ A DA T E : 8/ 9 / 2 0 2 2 DE S I G N E R : R F L E M I N G SY S T E M S I Z E : 71 5 0 W A T T S AH J : RE X B U R G TI M O T H Y N G 69 8 T A N G L E W O O D D R I V E RE X B U R G , I D A H O 8 3 4 4 0 12 4 7 0 9 PV-06 TE L T V E N T U R E S , L L C 1 16" = 1' SHEET # SCALE: RE V I S I O N S : 23 9 1 S . 1 5 6 0 W . S U I T E C WO O D S C R O S S , U T 8 4 0 8 7 PH O N E : ( 8 0 1 ) 3 1 7 - 8 4 4 4 PR O J E C T # 8- 9 - 2 0 2 2 N/ A N/ A N/ A DA T E : 8/ 9 / 2 0 2 2 DE S I G N E R : R F L E M I N G SY S T E M S I Z E : 71 5 0 W A T T S AH J : RE X B U R G TI M O T H Y N G 69 8 T A N G L E W O O D D R I V E RE X B U R G , I D A H O 8 3 4 4 0 12 4 7 0 9 PV-06