HomeMy WebLinkAboutLOAD SHORT FORM - 22-00753 - 685 S 2470 W - New SFRCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Sep-20 14:04:38 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF2B17 huntington.rup Calc = MJ8 House faces: NW SF2B17Job:Load Short Form Date:Entire House Vince ByramBy: Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Information InfiltrationClgHtg SimplifiedMethod89-6Outside db (°F) AverageConstruction quality7568Inside db (°F) 0Fireplaces1474Design TD (°F) H-Daily range 5050Inside humidity (%) -3157Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Lennox Make Lennox Trade LENNOX Trade LENNOX Model ML195UH070XP36B-*Cond 13ACXN030-230-** AHRI ref 4805339 Coil CH35-36C++TDR+TXV AHRI ref 7623033 Efficiency 95 AFUE Efficiency 11.0 EER, 13 SEER Heating input Btuh66000 Sensible cooling Btuh20300 Heating output Btuh64000 Latent cooling Btuh8700 Temperature rise °F63 Total cooling Btuh29000 Actual air flow cfm1100 Actual air flow cfm967 Air flow factor cfm/Btuh0.025 Air flow factor cfm/Btuh0.062 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Room7 320 6985 1746 172 108 Room9 288 4865 1901 120 117 Room11 162 1527 725 38 45 Room12 165 3733 1530 92 95 Room14 60 810 115 20 7 Room15 180 4254 1947 105 120 Room16 210 2900 1852 72 114 Room18 363 5399 1522 133 94 Room5 432 7809 2217 193 137 Room6 288 5328 1953 131 121 Room1 105 987 147 24 9 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Sep-20 14:04:38 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 2 S:\High Country\Wrightsoft\SF2B17 huntington.rup Calc = MJ8 House faces: NW Entire House d 2573 44596 15657 1100 967 Other equip loads 3617 684 Equip. @ 0.94 RSM 15360 Latent cooling 0 TOTALS 2573 48212 15360 1100 967 2022-Sep-20 14:04:38 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF2B17 huntington.rup Calc = MJ8 House faces: NW SF2B17Job:Building Analysis Date:Entire House Vince ByramBy: Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7568Indoor temp era ture (°F)Idaho Falls, ID, US 1474Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-31.557.0Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) SimplifiedMethod)H(34-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing OtherCeilings Floors Infiltration Ventilation % of loadBtuhBtuh/ft²Component 39.0188277.6Walls 15.6751124.3Glazing 0.523311.1Doors 4.722691.5Ceilings 10.751643.43.4Floors 22.0105913.8Infiltration 00Ducts 00Piping 00Humidification 7.53617Ventilation0Adjustments 100.048212Total Cooling Walls Glazing Other Ceilings Infiltration Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 11.418570.7Walls 54.5890428.8Glazing 0.4582.8Doors 7.912880.8Ceilings 1.11730.1Floors 6.310260.4Infiltration 00Ducts 4.2684Ventilation 14.42350Internal gains 00Blower 0Adjustments 100.016341Total Latent Cooling Load = 0 Btuh Overall U-va lue = 0.0 78 Btuh/ft²-°F Data entries checked. 2022-Sep-20 14:04:38 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF2B17 huntington.rup Calc = MJ8 House faces: NW SF2B17Job:Component Constructions Date:Entire House Vince ByramBy: Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7568Indoor temp era ture (°F)Idaho Falls, ID, US 1474Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-31.557.0Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) SimplifiedMethod)H(34-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Frm wall, vnl ext, 3/8" wood shth, r-22 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 1660.4716844.8122.00.065350n 3151.09319711.122.00.150288n 1560.4715794.8122.00.065328e 2671.09270511.122.00.150244e 1800.4718284.8122.00.065380s 3421.09346311.122.00.150312s 1660.4716794.8122.00.065349w 2661.09269311.122.00.150243w 18570.74188277.5522.00.1502494all Partitions (none) Windows Double Pane:30710.268822.900.31030n 61C: 61C; NFRC rated (SHGC=0.30)24810.358624.400.33024n 234332.7175024.400.33072e 249632.7186424.400.33076e 98132.773324.400.33030w 253032.7189024.400.33077w 859730.8682324.400.330279all Doors metal: Door, mtl pur core type 582.7823311.16.00.15021w Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 12880.8422691.4850.00.0201533 Floors 19A-30bscp: Part floor, carpet flr fnsh, r-30 ins, frm flr, 12" thkns, 5/8" gypsum board int fnsh 1730.409142.1130.00.034433 2022-Sep-20 14:04:38 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 2 S:\High Country\Wrightsoft\SF2B17 huntington.rup Calc = MJ8 House faces: NW 22B-10cpm: Bg floor, heavy dry or light damp soil, on grade depth, r-10 edge ins, carpet flr fnsh 0015226.310.00.3556 00409826.310.00.355156 00425026.310.00.355162all Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Sep-20 14:04:38 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF2B17 huntington.rup Calc = MJ8 House faces: NW SF2B17Job:Project Summary Date:Entire House Vince ByramBy: Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor:3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Notes: Design Information Idaho Falls, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-6 Outside db °F89Inside db °F68 Inside db °F75 Design TD °F74 Design TD °F14Daily range H Relative humidity %50Moisture difference gr/lb-31 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh44596 Structure Btuh15657 Ducts Btuh0 Ducts Btuh0Central vent (53 cfm)3617 Btuh Central vent (53 cfm)Btuh684 Outside air Outside airHumidificationBtuh0Blower Btuh0 Piping Btuh0Equipment load Btuh48212 Use manufacturer's data n Rate/swing multiplier 0.94InfiltrationEquipment sensible load Btuh15360 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh-427 Ducts Btuh0Central vent (53 cfm)Btuh-951 CoolingHeating Outside air25732573Area (ft²)Equipment latent load Btuh0 2266422664Volume (ft³)Air changes/hour 0.210.41 Equipment Total Load (Sen+Lat)Btuh15360 Equiv. AVF (cfm)79155 Req. total capacity at 0.70 SHR ton1.8 Heating Equipment Summary Cooling Equipment Summary Make Lennox Make LennoxTradeLENNOXTradeLENNOX Model ML195UH070XP36B-*Cond 13ACXN030-230-**AHRI ref 4805339 Coil CH35-36C++TDR+TXV AHRI ref 7623033Efficiency95 AFUE Efficiency 11.0 EER, 13 SEER Heating input Btuh66000 Sensible cooling Btuh20300Heating output Btuh64000 Latent cooling Btuh8700 Temperature rise °F63 Total cooling Btuh29000Actual air flow cfm1100 Actual air flow cfm967 Air flow factor cfm/Btuh0.025 Air flow factor cfm/Btuh0.062Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 1.00 2022-Sep-20 14:04:39 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF2B17 huntington.rup Calc = MJ8 House faces: NW SF2B17Job:AED Assessment Date:Entire House Vince ByramBy: Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7568Indoor temp era ture (°F)Idaho Falls, ID, US 1474Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-31.557.0Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) )H(34-Da ily ra nge (°F) 60-We t bu lb (°F) 7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limit Gl a z i n g l o a d ( B t u h ) Hour of Day 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 18.8%. House has adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 0 Btuh Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Sep-20 14:04:39Right-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1S:\High Country\Wrightsoft\SF2B17 huntington.rup Calc = MJ8 House faces: NW SF2B17Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Entire House Room7 2 Exposed wall 314.0 ft 56.0 ft 3 Room height 8.8 dft 10.0 heat/coolft 4 Room dimensions ft20.0x16.0 5 Room area 2573.0 f t²320.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.814.81 0.470.47 380 350 1683 166 200 200 962 95 .GG Double PaneDouble Pane 0.3100.310 nn 22.9422.94 10.2310.23 30 0 688 307 0 0 0 0 .WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 nn 11.1011.10 1.091.09 312 288 3197 315 0 0 0 0 .GG 61C61C 0.3300.330 nn 24.4224.42 10.3210.32 24 0 586 248 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.814.81 0.470.47 400 328 1579 156 0 0 0 0 GG 61C61C 0.3300.330 ee 24.4224.42 32.6932.69 72 0 1750 2343 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ee 11.1011.10 1.091.09 320 244 2705 267 0 0 0 0 GG 61C61C 0.3300.330 ee 24.4224.42 32.6932.69 76 0 1864 2496 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.814.81 0.470.47 380 380 1828 180 200 200 962 95 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ss 11.1011.10 1.091.09 312 312 3463 342 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.814.81 0.470.47 400 349 1679 166 160 109 524 52 GG 61C61C 0.3300.330 ww 24.4224.42 32.6932.69 30 0 733 981 30 0 733 981 DD metalmetal 0.1500.150 ww 11.1011.10 2.782.78 21 21 233 58 21 21 233 58 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ww 11.1011.10 1.091.09 320 243 2693 266 0 0 0 0 GG 61C61C 0.3300.330 ww 24.4224.42 32.6932.69 77 0 1890 2530 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.481.48 0.840.84 1533 1533 2269 1288 0 0 0 0 FF 19A-30bscp19A-30bscp 0.0340.034 --2.112.11 0.400.40 433 433 914 173 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.2726.27 0.000.00 60 6 152 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.2726.27 0.000.00 1040 156 4098 0 320 56 1471 0 6 c) AED excursion 0 262 Envelope loss/gain 34004 12280 4885 1543 12 a)Infiltration 10591 1026 2100 204 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 5 1150 0 0 Appliances/other 1200 0 Subtotal (lines 6 to 13)44596 15657 6985 1746 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 44596 15657 6985 1746 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 44596 15657 6985 1746 Air required (cfm)Air required (cfm)1100 967 172 108 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Sep-20 14:04:39Right-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 2S:\High Country\Wrightsoft\SF2B17 huntington.rup Calc = MJ8 House faces: NW SF2B17Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room9 Room11 2 Exposed wall 34.0 ft 9.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft18.0x16.0 ft18.0x9.0 5 Room area 288.0 f t²162.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.814.81 0.470.47 0 0 0 0 0 0 0 0 .GG Double PaneDouble Pane 0.3100.310 nn 22.9422.94 10.2310.23 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 nn 11.1011.10 1.091.09 0 0 0 0 0 0 0 0 .GG 61C61C 0.3300.330 nn 24.4224.42 10.3210.32 0 0 0 0 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.814.81 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3300.330 ee 24.4224.42 32.6932.69 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ee 11.1011.10 1.091.09 128 98 1088 107 72 56 618 61 GG 61C61C 0.3300.330 ee 24.4224.42 32.6932.69 30 0 733 981 16 0 399 534 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.814.81 0.470.47 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ss 11.1011.10 1.091.09 144 144 1598 158 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.814.81 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3300.330 ww 24.4224.42 32.6932.69 0 0 0 0 0 0 0 0 DD metalmetal 0.1500.150 ww 11.1011.10 2.782.78 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ww 11.1011.10 1.091.09 0 0 0 0 0 0 0 0 GG 61C61C 0.3300.330 ww 24.4224.42 32.6932.69 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.481.48 0.840.84 288 288 426 242 162 162 240 136 FF 19A-30bscp19A-30bscp 0.0340.034 --2.112.11 0.400.40 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.2726.27 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.2726.27 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -146 -32 Envelope loss/gain 3845 1342 1257 699 12 a)Infiltration 1020 99 270 26 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 2 460 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)4865 1901 1527 725 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 4865 1901 1527 725 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 4865 1901 1527 725 Air required (cfm)Air required (cfm)120 117 38 45 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Sep-20 14:04:39Right-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 3S:\High Country\Wrightsoft\SF2B17 huntington.rup Calc = MJ8 House faces: NW SF2B17Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room12 Room14 2 Exposed wall 26.0 ft 5.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft11.0x15.0 ft5.0x12.0 5 Room area 165.0 f t²60.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.814.81 0.470.47 0 0 0 0 0 0 0 0 .GG Double PaneDouble Pane 0.3100.310 nn 22.9422.94 10.2310.23 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 nn 11.1011.10 1.091.09 88 88 977 96 0 0 0 0 .GG 61C61C 0.3300.330 nn 24.4224.42 10.3210.32 0 0 0 0 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.814.81 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3300.330 ee 24.4224.42 32.6932.69 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ee 11.1011.10 1.091.09 120 90 999 99 0 0 0 0 GG 61C61C 0.3300.330 ee 24.4224.42 32.6932.69 30 0 733 981 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.814.81 0.470.47 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ss 11.1011.10 1.091.09 0 0 0 0 40 40 444 44 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.814.81 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3300.330 ww 24.4224.42 32.6932.69 0 0 0 0 0 0 0 0 DD metalmetal 0.1500.150 ww 11.1011.10 2.782.78 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ww 11.1011.10 1.091.09 0 0 0 0 0 0 0 0 GG 61C61C 0.3300.330 ww 24.4224.42 32.6932.69 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.481.48 0.840.84 165 165 244 139 60 60 89 50 FF 19A-30bscp19A-30bscp 0.0340.034 --2.112.11 0.400.40 0 0 0 0 60 60 127 24 FF 22B-10cpm22B-10cpm 0.3550.355 --26.2726.27 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.2726.27 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -89 -18 Envelope loss/gain 2953 1225 659 101 12 a)Infiltration 780 76 150 15 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 1 230 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)3733 1530 810 115 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 3733 1530 810 115 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 3733 1530 810 115 Air required (cfm)Air required (cfm)92 95 20 7 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Sep-20 14:04:39Right-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 4S:\High Country\Wrightsoft\SF2B17 huntington.rup Calc = MJ8 House faces: NW SF2B17Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room15 Room16 2 Exposed wall 27.0 ft 15.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft15.0x12.0 ft210.0x1.0 5 Room area 180.0 f t²210.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.814.81 0.470.47 0 0 0 0 0 0 0 0 .GG Double PaneDouble Pane 0.3100.310 nn 22.9422.94 10.2310.23 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 nn 11.1011.10 1.091.09 0 0 0 0 8 8 89 9 .GG 61C61C 0.3300.330 nn 24.4224.42 10.3210.32 0 0 0 0 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.814.81 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3300.330 ee 24.4224.42 32.6932.69 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ee 11.1011.10 1.091.09 0 0 0 0 0 0 0 0 GG 61C61C 0.3300.330 ee 24.4224.42 32.6932.69 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.814.81 0.470.47 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ss 11.1011.10 1.091.09 120 120 1332 131 8 8 89 9 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.814.81 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3300.330 ww 24.4224.42 32.6932.69 0 0 0 0 0 0 0 0 DD metalmetal 0.1500.150 ww 11.1011.10 2.782.78 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ww 11.1011.10 1.091.09 96 66 733 72 104 74 821 81 GG 61C61C 0.3300.330 ww 24.4224.42 32.6932.69 30 0 733 981 30 0 733 981 CC 16B-50ad16B-50ad 0.0200.020 --1.481.48 0.840.84 180 180 266 151 210 210 311 176 FF 19A-30bscp19A-30bscp 0.0340.034 --2.112.11 0.400.40 180 180 380 72 193 193 408 77 FF 22B-10cpm22B-10cpm 0.3550.355 --26.2726.27 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.2726.27 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 231 246 Envelope loss/gain 3444 1639 2450 1579 12 a)Infiltration 810 79 450 44 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 1 230 1 230 Appliances/other 0 0 Subtotal (lines 6 to 13)4254 1947 2900 1852 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 4254 1947 2900 1852 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 4254 1947 2900 1852 Air required (cfm)Air required (cfm)105 120 72 114 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Sep-20 14:04:39Right-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 5S:\High Country\Wrightsoft\SF2B17 huntington.rup Calc = MJ8 House faces: NW SF2B17Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room18 Room5 2 Exposed wall 35.0 ft 66.0 ft 3 Room height 8.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft363.0x1.0 ft18.0x24.0 5 Room area 363.0 f t²432.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.814.81 0.470.47 0 0 0 0 0 0 0 0 .GG Double PaneDouble Pane 0.3100.310 nn 22.9422.94 10.2310.23 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 nn 11.1011.10 1.091.09 160 136 1510 149 0 0 0 0 .GG 61C61C 0.3300.330 nn 24.4224.42 10.3210.32 24 0 586 248 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.814.81 0.470.47 0 0 0 0 240 218 1050 104 GG 61C61C 0.3300.330 ee 24.4224.42 32.6932.69 0 0 0 0 22 0 529 708 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ee 11.1011.10 1.091.09 0 0 0 0 0 0 0 0 GG 61C61C 0.3300.330 ee 24.4224.42 32.6932.69 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.814.81 0.470.47 0 0 0 0 180 180 866 85 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ss 11.1011.10 1.091.09 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.814.81 0.470.47 0 0 0 0 240 240 1154 114 GG 61C61C 0.3300.330 ww 24.4224.42 32.6932.69 0 0 0 0 0 0 0 0 DD metalmetal 0.1500.150 ww 11.1011.10 2.782.78 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ww 11.1011.10 1.091.09 120 103 1139 112 0 0 0 0 GG 61C61C 0.3300.330 ww 24.4224.42 32.6932.69 17 0 425 569 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.481.48 0.840.84 363 363 537 305 0 0 0 0 FF 19A-30bscp19A-30bscp 0.0340.034 --2.112.11 0.400.40 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.2726.27 0.000.00 60 6 152 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.2726.27 0.000.00 0 0 0 0 432 66 1734 0 6 c) AED excursion 38 -234 Envelope loss/gain 4349 1420 5333 777 12 a)Infiltration 1050 102 2475 240 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 1200 Subtotal (lines 6 to 13)5399 1522 7809 2217 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 5399 1522 7809 2217 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 5399 1522 7809 2217 Air required (cfm)Air required (cfm)133 94 193 137 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Sep-20 14:04:39Right-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 6S:\High Country\Wrightsoft\SF2B17 huntington.rup Calc = MJ8 House faces: NW SF2B17Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room6 Room1 2 Exposed wall 34.0 ft 7.0 ft 3 Room height 10.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft18.0x16.0 ft7.0x15.0 5 Room area 288.0 f t²105.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.814.81 0.470.47 180 150 721 71 0 0 0 0 .GG Double PaneDouble Pane 0.3100.310 nn 22.9422.94 10.2310.23 30 0 688 307 0 0 0 0 .WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 nn 11.1011.10 1.091.09 0 0 0 0 56 56 622 61 .GG 61C61C 0.3300.330 nn 24.4224.42 10.3210.32 0 0 0 0 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.814.81 0.470.47 160 110 529 52 0 0 0 0 GG 61C61C 0.3300.330 ee 24.4224.42 32.6932.69 50 0 1221 1635 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ee 11.1011.10 1.091.09 0 0 0 0 0 0 0 0 GG 61C61C 0.3300.330 ee 24.4224.42 32.6932.69 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.814.81 0.470.47 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ss 11.1011.10 1.091.09 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.814.81 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3300.330 ww 24.4224.42 32.6932.69 0 0 0 0 0 0 0 0 DD metalmetal 0.1500.150 ww 11.1011.10 2.782.78 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ww 11.1011.10 1.091.09 0 0 0 0 0 0 0 0 GG 61C61C 0.3300.330 ww 24.4224.42 32.6932.69 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.481.48 0.840.84 0 0 0 0 105 105 155 88 FF 19A-30bscp19A-30bscp 0.0340.034 --2.112.11 0.400.40 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.2726.27 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.2726.27 0.000.00 288 34 893 0 0 0 0 0 6 c) AED excursion -235 -22 Envelope loss/gain 4053 1829 777 127 12 a)Infiltration 1275 124 210 20 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)5328 1953 987 147 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 5328 1953 987 147 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 5328 1953 987 147 Air required (cfm)Air required (cfm)131 121 24 9 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Sep-20 14:04:40 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF2B17 huntington.rup Calc = MJ8 House faces: NW SF2B17Job:Loads for Multiple Orientations Date:Entire House Vince ByramBy: Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7568Indoor temp era ture (°F)Idaho Falls, ID, US 1474Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-31.557.0Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) )H(34-Da ily ra nge (°F) 60-We t bu lb (°F) 7.515.0Wind speed (mph) House North Northeast East Southeast South Southwest West Northwest Sensible Load (Btuh)14487 12509 15155 16025 14742 12403 14876 15360 Latent Load (Btuh)0 0 0 0 0 0 0 0 Total Load (Btuh)14487 12509 15155 16025 14742 12403 14876 15360 Heating AVF (cfm)1100 1100 1100 1100 1100 1100 1100 1100 Cooling AVF (cfm)967 967 967 967 967 967 967 967 Building Orientation Cooling Load To t a l C o o l i n g L o a d ( B t u h ) Direction House faces 0 5000 10000 15000 20000 N NE E SE S SW W NW House faces NorthwestCurrent Orientation: House faces SoutheastHighest Cooling Load: Job #: SF2B17 Performed by Vince Byram for: Cody Puzey 3758 Yellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 Kartchner 601 West 1700 South Logan, Utah 84321 Phone: 435-755-7080 Scale: 1 : 67 Page 1 Ri ght -Sui te® Uni v ersal 2 019 19.0.13 RSU20477 2022-Sep-20 14:04:55 ...rightsoft\SF2B17 huntington.rup N Main Room5Room6 Room7 6" Mechanical Damper for Fresh Air 96 cfm66 cfm 86 cfm 96 cfm66 cfm 86 cfm 496 cfm 6 " 14x3.25 2-14x3.25 14x3.25 6 "6 " 6 " 6 "6 " 6 " 6 " 6 " 6 "6 " 4-14x3.25 6 " 6 " 6 " 20 x 8 2-14x3.25 6 " 12 x 8 20 x 8 Job #: SF2B17 Performed by Vince Byram for: Cody Puzey 3758 Yellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 Kartchner 601 West 1700 South Logan, Utah 84321 Phone: 435-755-7080 Scale: 1 : 67 Page 2 Ri ght -Sui te® Uni v ersal 2 019 19.0.13 RSU20477 2022-Sep-20 14:04:55 ...rightsoft\SF2B17 huntington.rup N 2nd floor Room9Room11 Room12 Room14 Room15Room16 Room18 Room1 67 cfm 120 cfm 116 cfm 153 cfm 114 cfm 24 cfm 67 cfm 45 cfm 95 cfm 20 cfm 120 cfm 162 cfm 114 cfm 120 cfm 2022-Sep-20 14:04:41 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF2B17 huntington.rup Calc = MJ8 House faces: NW SF2B17Job:Duct System Summary Date:Entire House Vince ByramBy: Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0.34in H2O0.34 Available static pressure in H2O0.36in H2O0.36 Supply / return available pressure 0.269 / 0.091 in H2O in H2O0.269 / 0.091 Lowest friction rate in/100ft0.079in/100ft0.079 Actual air flow cfm967cfm1100 Total effective length (TEL)ft453 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st2325.013.0ShMt0x06.00.079924987hRoom1 st2325.013.0ShMt0x06.00.0794538725cRoom11 st2325.013.0ShMt0x06.00.07995921530cRoom12 st1325.013.0ShMt0x06.00.079720810hRoom14 325.013.0ShMt0x06.00.0791201051947cRoom15 st2325.013.0ShMt0x06.00.079114721852cRoom16 st2325.013.0ShMt0x06.00.07947672699hRoom18 st2325.013.0ShMt0x06.00.07947672699hRoom18-B st1325.013.0ShMt0x06.00.07968963904hRoom5 st2325.013.0ShMt0x06.00.07968963904hRoom5-A st2325.013.0ShMt0x06.00.07960662664hRoom6 st2325.013.0ShMt0x06.00.07960662664hRoom6-A st2325.013.0ShMt0x06.00.07954863493hRoom7 st2325.013.0ShMt0x06.00.07954863493hRoom7-A 325.013.0ShMt0x06.00.0791171204865hRoom9 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st1 Peak AVF 116 76 0.079 174 6.5 12x8 ShtMetl st2 Peak AVF 759 654 0.079 683 14.2 20x8 ShtMetl 2022-Sep-20 14:04:41 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 2 S:\High Country\Wrightsoft\SF2B17 huntington.rup Calc = MJ8 House faces: NW Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb3 0x 4960 365 115.0 0.079 393 11.1 4-3.25x14 4-10x36 SJSp rt1 rb8 0x 720 114 115.0 0.079 362 6.4 3.25x14 10x9 SJSp rt1 rb1 0x 1580 162 115.0 0.079 257 7.3 2-3.25x14 2-10x18 SJSp rb6 0x 1160 104 115.0 0.079 368 6.5 3.25x14 10x9 SJSp rt1 rb7 0x 1530 101 115.0 0.079 242 7.2 2-3.25x14 2-10x18 SJSp rt1 rb5 0x 1050 120 115.0 0.079 103 6.5 x14 12 ShMt Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 837 685 0.079 754 14.9 20x8 ShtMetl