SPRINKLER MONITORING RE-SUBMITTAL - 10-00177 - K-Mart - Fire Suppression System
Sprinkler Monitoring Re -Submittal Prepared for Kmart 125 Valley River Drive Rexburg, ID Submitted By Tyco/ADT Fire & Security 2950 S. Victory View Way Boise, ID 83709 208-368-6995 Prepared By Tyco/ADT Fire & Security National Accounts Group 9201 E. 63rd Street Raytown, MO 64133 Green, Greg S. Systems Application Manager Phone (816) 309-6845 03/09/10 GIBBENS DRAKE SCOTT, INC 9201 E. 63rd STREET, SUITE 100 RAYTOWN, MISSOURI 64133 ENGINEERING 3 /a _ Zo 10 Table of Contents Part One System Overview Outline Part Two Battery Calculations Part Three U.L. Certificates Part Four Equipment Data Sheets Part Five Floor Plan Layout Part one System Overview Outline System Outline I. Location Kmart 125 Valley River Drive Rexburg, ID II. Codes A. 2002 NFPA 72 Chapters 1-7 as Applicable(Remote Station) B. 2002 NEC Articles 250. 725, 760 C. Local, City, State III. Control A. 1 Unimode 2000DLS Fire Control Panel B. 4 FCPS24FS8 Signal Power Expander IV. Contol Modules A. 4 ADT MMF300 Monitor Module 44 Box V. Fire Alarm Initialing Devices A. 1 SD355 Smoke Detector Photo B. 1 ADT BG12LX Manual Pull Station Addressable C. 3 Water Flow Connection Only, Provided by Sprinkler Contractor D. 11 D355PL Addressable Duct Detector VI. Fire Alarm Indicating Devices A. 1 ADT-LCD-80F LCD Annunciator 80 Character B. 9 P2R Multi Candela Horn/Strobe, Wall Mid. C. 41 PC2R 24 vdc Horn/Strobe Multicandela, Ceiling Mtd. D. 15 SCR 24 vdc Strobe multicandela, Ceiling Mtd. E. 2 SR Multi Candela Strobe, Wall Mid. F. 1 P2RK 75cd Multi Candela Horn/Strobe, Wall Mtd. Weatherproof VI. Zones Per drawings VII. Wiring All Circuits and Wiring Shall be "Power Limited" Initiating/SLC Shall be 14/2 FPLP Cable, Class B Indicating Circuits Shall be 14/2 U.L. FPLP Cable System Ground Shall be 14 THWN Green Conductor Under Ground and Outside Wire shall be 14 THWN in Approved Raceway Vill. Listings A. All Equipment Shall Be U.L. Listed and Compatible IX. Power Supply A. Primary - 110 VAC Dedicated 20 Amp Circuit B. Secondary -18 Amp Hour Battery X. Alarm Supervision A. Human B. Remote Station Installing Branch/Contractor ADT Tyco Fire & Security ADT Tyco Fire & Security 14200 Exposition Blvd. 2950 S. Victory View Way Aurora, CO 80012 Boise, ID. 83709 800428-7124 208-368-6995 UUFX-S994-183 d m -oo N x 7 O N a m 0 a N x x x x J E O 2 O R i U O c x x x x x x C i Q O N O 'o x C) c N m w d W o E a � Q a v r V U � O U F- _O f7 o d m p E'er d • 0 m E cn > > (n Q m F- m .Q a cn N O U N N 7 Part Two Battery Calculations Standby Battery Calculations ADT Unimode 200 UDLS Kmart Rexburg, ID `.Standby '�Gbrr6 t ;::Alarm :: current Part Number:�� Description .. . , . � 4uaripty.:: Per�,Device :AII Devices: Device �:� Alt Devices Unimode 200 UDLS Fire Alarm Control Addressable 1 0.0800 0.080 0.5000 0.5000 ADT-LCD-80F LCD Annunciator 80 Character 1 0.0650 0.065 0.1020 0,1020 ADT MMF300 Monitor Module 4x4 Box 4 0.0070 0.028 0.0510 0.2040 SD355 Smoke Detector Photo 1 0.0200 0.020 0.0300 0.0300 ADT BG12LX Manual Pull Station Addressable 1 0.0020 0.002 0.0020 0.0020 D355PL Addressable Duct Detector 11 0.0020 0.022 0.0070 0.0770 0.000 0.0000 0.000 0.0000 0.000 0.0000 0,000 0.0000 0.000 0.0000 0.000 0.0000 Total Aux currrent Max 8 Amps 0.217 Alarm 0.9150 Signal Circuits Alarm:::: Curent5. Quantity. -:,:Per Device AII Devices Circuit 1 FCPS24FS8 4 0,048 0.192 0.000 0.000 0.000 Total 1 0.192 Circuit 2 0.000 0.000 0.000 0.000 Total 2 0.000 Totals Maximum 6 Amps 0.192 Circuit 1 Circuit 2 Max Wire Run Distance For AWG 14 2036 Actual Wire run Distance 10 Voltage Drop for 14 AWG wire 0.012 Voltage Drop = 2 ' Wire Run Distance3.07 Ohms Per 1000 ft 14 AWG ' Total Current for Circuit / 100 Standby Hours 24 Standby Battery Draw 0.217 Standby Amp Hrs 5.208 Alarm Current 1.107 Alarm Current 5 Min 0.092 Size Required 7 A.H lBattery with 5 Min. Alarm Time 6 A.H. and 20 % Reserve 6.095 Battery Size Supplied 18 A.H. 0000r0000roN000ao&o «#I \ % G %222 ?3< \ ci 6 a a 2w v&» § O � \ \ D m .9 : //E ] E q f� �000000000 oe�oo=LO=o = » ~® I a/ \U2\ q 7 � § © C) w w § m �a ?£ coO 7 on L 2 � 2 00000 000&oo\ooaz#o fE a 6 b \ 66 »< LL o 0 § I . g J \ � e E o00000000\o%\��SG\/SS32 CD @ 'It CD C) & \ ww\( \ 2 / o » k ® > / f ® 0 a 5053W f B4eefn0� § O$OOs71Q o \\0§/�.$ . E ._ p � _ ? \\0"� n- fR g e r m=$ (� e»= r _ ) EQ�CNCIJ §m°~2°©»�C) \ /ceaeeeaeeae&\C)CD 00\/\ / k>/k� R j $ I O�\\��222\£7\\\\22\2 LOoLo Co, «MwzU) Cl) c C,a�NIm�=w mC,4m�s� Ra��a±oQoeo000e EIIIImmEmEElmmm N i� co U) LL It N to a c.i LL I- O 4- U) C O V U O_ O L d R r O O O r O O N O M 0 I- M= CO = O N V' Q O O r CO (O — (D (o NM V'rti (V N c m 7 0 0 0 0 0 0 0 0 0 O O r 0 0 N 0 f— O C r(n00 O O r M r U ` N N U m U A O O O O O O O O O r O N (n O O tl- (!) Ln O I- in O (D co O) O O M N N M O r O O r N M Go 't It co O Cl) 00 C m Q O O O O O O O O O r O O r 0 0 N M O 0 0 0"t N I� r(Dra00N(!) c Cl O r CO Lo a- r 0 O NMO(D r N N '-' Ur = -- N N N T 7 7 7 m m =O a � O O=y0 U U U >> TU O� oocm� "- LL c c c _ ate•-m0 c a o ;-- c 3 O M Ln w v m to Lo M co U) m O" T m fn m � m c� n co o rn r� m o 0o u) U p p Q O 5 Ui N N N N 0 0 0 th -r N �- .- — Q Q U p o 0 0 0 0 0 0 0 0 0 0 0 0 0 o U O wj = Q Fu m C/) c U o>> om w o c ��a•v is J 3 0] U N N -O a _0'0 a iU Q U U U O (n U -0 pU') -0 r-0 �� U U U)0Lo c) C) Ur Uf-r(nu) r O r- ��2�NrNnNO'Q'(' NNNNN��Ud'UQ'UUUU N M O O O O o O 0 to 0 m 0 0 0 Lo m M 0 N M= M N Nmr-O NmQ r O r r r cO O O r rM r1'r~ L L 7 U � o H U L N N r M 4) N a) T � • Q' tZ N Q_ C U D 7 E 0 �wa� N m N O m000000000U')0oN U-)m0 _ I't CD m M a)N N N CDNLO— m M p= O O O O O M It U M U N `- r OD N ap U o M N m o 0 LL IRt a N 0 0 0 0 00 0 0 0 Cl 0 (n o o (n LO r CD r- CDLnoo a N O)Nmr Ca v 0 0 LL U U 4-- N U U _ a N � N N m U S > N r V U � M a 0 0 0 0 0 0 0 0 0 0 O O r o o N N M O O O V- N rNr-(D00NLn C O 0 r N 0) r 0 r tm N O M m (D •- r r m 7 }' U O •� o U L U > 7 m m -0 > ` � - O a O O = (II UQaUU» T� 0- 00 C m� LL C C C 0- O C 3 0 �n in u� co v rn cp u'� in cD u� m L LO c� cl Ln cD CD r- cD Ln r- o m �D L U C) Q N L L N N N N O O O M N N 7 L — Q Q U Up o 0600000000000 oCi O �p 7Q 5 U L O 3 :5i d m> O U U a O U 0 'aa a Uaaa Q N aa-O U O-pa 0-0LO U U U-pa U U 0o� UC:) LO r-��LOLO �oUnro N N N N N W U U U U U U U U U ILdILrZa_U)U)rlU)0-ddr)(1)CO O O O O O O O O O N N L L U N o U U � co O OONLOU')O (D(D= (DO a)r.< r M r 7 D� N M O o 0 0 0 0 W O O LoO (O O O O M LO N O C co (O r- N (D (O O fII N Oco �}• N d• �~ U .j L T (V M .- U C� O tnOOOo 0OON000001-m o00 tt LO 01 00 0 �M A' 00 LO � O o � 0 0 c E L �Q U L) � U c w CD m A � � IQ O r 0 0 0 0 0 0 o O N 0 0 0 0 0- to 0 0 0 0 d' N N "TO00oNU') C•"' LO N N 0 � QJ O M N (D .- �- N c-- L 7 U •� o U � L U O "6 � C) 't o o = ccu �U) lJ 0— O O C O.0 V-- •� LL � c c _ C U O_ O_ ._ m O C o �n Lo in oo v m co m c- (o Lo oo � LO OL �' 6 N m N u'1 cD o rn r w m m� Cl o0 LL U Q 0 O_ N r- N N N N 0 0 CD. M. �-- N .- .- 7 Q Cl U U Q o 0 0 0 0 0 0 6 M. 0 0 0 0 o U 0 o 0= O > U) L c U 0 m c � •U fE J O N m U U U U O LO U -0 LO U LO Ln Ln U U �LOo to�O U LO Mr- (O CD ry c`- MNNNND 0_ 0_ 0_ 0_ U 0 0_ 0 m M 0- U 0 U Part Three U.L. Certificates &Underwriters Laboratories Inc.:R; Northbrook. IL San Jose, CA Melville, NY A not -for -profit organization dedicated to public safety and committed to quality service Applicant ID No: 360682.009 Service Center No 768 Expires: 31-MAR-2010 CERTIFICATE OF COMPLIANCE THIS IS TO CERTIFY that the Alarm Service Company indicated below is included by Underwriters Laboratories Inc. (UL) in its Product Directories as eligible to use the UL Listing Mark in connection with Certificated Alarm Systems. The only evidence of compliance with UL's requirements is the issuance of a UL Certificate for the Alarm System and the Certificate is current under UL's Certificate Verification Service. This Certificate does not apply in any way to the communication channel between the protected property and any facility that monitors signals from the protected property unless the use of a UL listed or Classified Alarm Transport Company is specified on the Certificate. Listed Service From: AURORA, CO Alarm Service Company: (360682-221) Service Center: (360682-2211 ADT SECURITY SERVICES INC ADT SECURITY SERVICES INC 14200 E EXPOSITION BLVD 14200 E EXPOSITION BLVD AURORA CO 80012 AURORA CO 80012 The Alarm Service Company is Listed in the following Certificate Service Categories: File - Vol No. CCN Listing Category BP34 - 192 CPVX [Burglar Alarm Systems] Central Station S994 - 183 UUFX [Signal and Fire Alarm Equipment and Services] (Protective Signaling Services) Central Station ***THIS CERTIFICATE EXPIRES ON 31-MAR-2010 *** "LOOK FOR THE UL ALARM SYSTEM CERTIFICATE" v 2008 UL Form CS -CC Part Four Equipment Data Sheets ADT-Unimode 200 Addressable Fire Alarm Control Panel UL FM S232 OX9A3.AY (Unimode 200) (Unimode 200) California State Fire ' Marshal 7165-0085:172 CS68/ML266 (Unimode 200) zones or 198 points to a Central Station. • Optional ADT-LCD40 Series alphanumeric, 40-character, backlit remote serial annunciators operate over high-speed EIA-485 port. Up to 32 may be supported by ADT-Unimode 200 (requires panel firmware #Unimode2OO v3.0 or greater). • Optional printer interface — UL listed for permanent attachment. • Integral 40-character LCD display with backlighting. • Keypad programmable on panel, with two user -defined pass- words, plus an Autoprogram feature. • Custom English labels per point may be manually entered or selected from an internal library file. • Autoprogram and Walk Test features identify two or more devices set to same address. • Real-time clock/calendar. • History file with 500-event capacity. • Waterflow or supervisory selec- tion per monitor point. • System alarm verification, smoke only. • Presignal delay option per NFPA 72. • Silence Inhibit and Auto Silence timer options. • Battery charger for up to 60 hours of standby power. • Fuseless, power -limited technol- ogy meets new UL power -limiting requirements. (Unimode 200C) M EA 16-94-E Vol.11 (Unimode 200) Made in U.S.A The ADT-Unimode 200 is a com- pact, cost-effective, addressable fire alarm control panel with a capacity of 198 Fire•Lite 300 Series devices. A single SLC (Signaling Line Circuit) loop sup- ports up to 99 smoke detectors and 99 control or monitor modules. The panel uses surface -mount technol- ogy and is designed for ease of installation and programming. It features the latest in fire protection technology, including maintenance alert and automatic detector test. FEATURES • Includes larger enclosure capable of housing 12.0 AH batteries. • SLC supports up to 198 address- able devices (99 detectors and 99 monitor or control modules). • SLC can be configured for Style 4, 6, or 7 operation. • Dual Integral NACs (Notification Appliance Circuits), Style Y or Z (Class B or A). • 3.0 Amp Notification Appliance (bell, signal) power, expandable to 6.0 Amperes. • NACs may be programmed for Steady, March Time, Temporal or California Code (requires #Unimode2OO v3.0 or greater). • Alarm, trouble and supervisory relays, standard. • Maintenance alert warns when smoke detector dust accumula- tion is excessive. • Optional ADT-UNICOM Digital Alarm Communicator reports 56 Dimensions th x w x dl Door: 17,1 1 " x 14,71 " x 0.375" {43.46 x 37.36 x 0.95 cm}, Backbox: 16.90" x 14.50" x 4.50" (42.93 x 36.83 x 1 1 .43 cm). Trim Ring: 20.02" x 1 7.62" 150.$5 x 44.75 cm). Ordering Guide ADT-Unimode 200 Addressable Fire Panel. Includes display, single printed circuit board. and cabinet. ADT-Unimode 200C Same as above with ULC listing and DP- 1- R dead -front panel. DP-1-R Full-length internal dead - front panel (required for FM applications; included when ordering ADT-Unimode 2O0C). ADT-UNICOM Digital Alarm Communicator Transmitter (see data sheet DA-45133 for more information) . XRM-24 120 VAC, 100 VA Transformer. Expands system power supply. Expands Notification Appliance power from 3.0 amps to 6.0 amps. ADT-PK-U200 Programming Kit for Windows` -based PC computer. TR-4-R Trim Ring for semi -flush mounting. tyco Fire & Security System Peripherals and Wiring 24 VDC EIA-485 Interface (DIM485) built into the motherboard - 4 wires (New as of 9/l/01) 0 0 0 ©v ADT-LCD40 Up to 6,000 ft. (1,8Z between each ADT-1 in the EIA-485 loop between each ADT-I and the FACP 24 VDC EIA-485 i \� Mode (2 ■ ■ ANNUNCIATOR SERIES ADT-AFM ■ ■ ADT-ACM ■ ■ ADT-LDM 24 VDDCC. ® o " FRO o _ 0 ® o 0 ono ❑DODO ❑DODO ❑❑❑00 ❑❑OOD o0o 0 ADT-UNICOM 'EIA-485 and EIA-232 Interface built into the MS-9200 Rev.PC-D Wiring Requirements The SLC requires use of a specific wire type to ensure proper circuit operation. It is recommended that all SLC wiring be twisted -pair shielded to minimize the effects of electrical interference. Wire size should be no smaller than 18 AWG (0.75 mm2) and no larger than 12 AWG (3.25 mm2) wire. The wire size depends on the length of the SLC circuit. Use the table below to determine the specific wiring requirements for the SLC. Wire Requirements Twisted -pair shielded 4410, 4408, 4406, 4402, Untwisted, unshielded wire, inside conduit or not inside conduit Distance in Feet (meters) 10,000 (3,048) 8,000 (2,438) 4,875 (1,486) 3,225(983) 1,000 (305) Typical Wire Tvpet 12 AWG - Belden 9583, Genesis Signal 98230, WPW 999 14 AWG - Belden 9581, Genesis Signal 98430, WPW 995 16 AWG - Belden 9575, Genesis & 4606, Signal 98630, WPW 991 18 AWG - Belden 9574, Genesis & 4602, Signal 98300, WPW 975 12 - 18 AWG OKE DETECTORS AD350 CP350 SD350 SD350T MM0101 DUCT DETECTORS D350P D350RP MONITORS MMF-300 MMF-302 M D F-300 C M F-300 C R F-300 1300 11 MINI MONITOR MMF-301 PULL STATION ADT-BG-I2LX 1. AWG wire size conversion to metric size: 12 AWG = 3.25mm2; 14 AWG = 2.00mmz; 16 AWG = 1.30mm2; 18 AWG = 0.75mm2 1#1347 Al-100 Page 2 of 4 2001 ADT Security Services, Inc. Section: Addressable 11 /20/01 • Detector sensitivity printout. • Rapid poll algorithm for manual stations. Responds to alarm/ activation in less than two seconds. • Operates with untwisted, unshielded wire (up to 1,000 ft./ 304.8 m) for retrofit applications (U.S. Patent 5,210,523). • 300 Series addressable devices feature decimal address selec- tion. Address of each device can be easily set in the field by use of a screwdriver. • Remote Acknowledge/Silence/ Reset/Drill via MMF 300 modules. • SLC loop maximum length 10,000 ft. (3,048 m) @ 12 AWG (3.25 mm2) twisted/shielded. Compatible Addressable Devices All feature a polling LED and rotary ad- dress switches. AD350 Adapt Multi -Sensor Smoke Detector. CP350 Addressable Ionization Smoke Detector. SD350/SD350(T) Addressable Photoelectric Smoke Detector (T = with thermal sensor). 13350/113350113P Addressable Duct Detector (R = with relay). B224RB Relay detector base. B224RI Isolator detector base. B501 BH/B501 BHT Base with sounder (T = with temporal sounder). Compatible Modules MMF-300 Addressable Monitor Module for one zone of normally - open dry -contact initiating devices. Mounts in standard 4" (10.16 cm) box. Includes plastic cover plate and end -of -line resistor. Module may be configured for either a Style B (Class B) or Style D (Class A) initiating device circuit. MDF-300 Dual Monitor Module. Same as MMF-300 except it operates in Style B (Class B) only. MMF-301 Miniature version of MMF-300. Excludes LED and Style D option. Connects with wire pigtails. May mount in device backbox. MMF-302 Similar to MMF-300, but may monitor up to 20 conventional two -wire detectors. Requires external 24 VDC power. Consult ADT Device Compatibility Document (P/N 51352) for compatible smoke detectors. CMF-300 Addressable Control Module for one Style Y/Z (Class B/ A) zone of supervised polarized Notification Appliances. Mounts directly to a 4" (10.16 cm) electrical box. NAC option requires external 24 VDC to power notification appliances. CRF-300 Addressable relay module containing two isolated sets of Form-C contacts, which operate as a DPDT switch. Mounts directly to a 4" (10.16 cm) box, surface mount using the SMB500. ADT-BG-12LX Addressable manual pull station with interface module mounted inside. 1300 This module isolates the SLC loop from short circuit conditions (required for Style 7 operation). Compatible with legacy Fire-Lite 300 Se- ries devices. Please consult factory for further information on all the 300 series devices: CP300, SD300, SD300(T), C304, M300, M301, M302, C304, and BG-10LX. NOTES: 1) "A "suffix should be included only when ordering ULC listed units (e.g. SD350A, MMF- 300A). 2) For more on ADT- Unimode 200 Compatible Address- able Devices, please see the follow- ing data sheets (document num- bers): SD350/SD350T (11338), CP350 (11339), MMF-300 Series/ MDF-300 Monitor Modules U 1340) and ADT-BG-12LX U 1337). EIA-232 Port/RS-485 PIM-24 Printer/PC Interface Module, Cable, D139F Connector for panels manufactured prior to 9/1 / 01. DIM-485 ADT-LCD-40 Display Interface Module. NOTE: PIM-24 and DIM-485 options are not available simultaneously. Compatible Devices/ Annunciators, EIA-485 Ports ADT-UNICOM: Digital Alarm Communicator Transmitter. ADT-LCD40 Series: 40-character, backlit LCD-type fire annunciators capable of displaying English - language text. Requires one DIM-485 per ADT-Unimode 200 panel (for boards manufactured before 9/1 /01) to interface with up to 32 ADT-LCD40 annunciators. ADT-AFM/AFM-X Series: LED -type fire annunciators capable of providing up to 56 software zones of annunciation. Available in increments of 16 or 32 with expandable (AFM-X Series) and non -expandable (ADT-AFM Series) configurations to meet a variety of applications. ADT-LDM Series: Lamp Driver Module series for use with custom graphic annunciators. NOTE: For more detailed information on Compatible EIA-485 Port Devices for use with the ADT-Unimode 200, please see the following data sheets (document numbers): ADT UNICOM (DA-45193), ADT-LCD40 (DA-45834), ADT-AFM Se- ries (DA-43882), and ADT-LDM Series (DA-46502). Field -Programming Features Off -Line Programming: Create entire program in your office using a WindowsO'-based PC computer (order programming kit ADT-PK- U200 separately). Upload/Down- load system programming locally to the ADT-Unimode 200 in less than one minute. Auto -Programming: Command the ADT-Unimode 200 to program itself (takes less than 30 seconds). In the Auto -Program mode, the ADT- Unimode 200 scans for all possible devices at all addresses, stores the device types, and addresses found, and then loads default values for all options (General Alarm). It also checks for two or more devices set to the same address. On -Line Edit: While still providing fire protection, the ADT-Unimode 200 may be programmed from the front panel. Simple menu trees displayed on the LCD allow the trained user to perform all functions without referring back to the programming manual. English Label Library: Quickly select labels from a standard library of more than 50 adjectives/nouns, such as "FLR 3 HALLWAY," or enter custom labels letter -by -letter. Use recall function to repeat previ- ously used label. Program Check: Automatically catch common errors, such as relays not linked to any zone or point. Detector Sensitivity Testing The new ADT-Unimode 200 feature allows the control panel to monitor and print out the sensitivity of each addressable smoke detector in the system. This eliminates the need for a service person to physically connect a test device to each smoke detector in the field. The printout will include the detector's address, type (photo or ion), cham- ber value and the respective time/ date. Maintenance Alert The ADT-Unimode 200 continually monitors each smoke detector and responds to a reading of 80% of the 1#1347 2001 ADT Security Services, Inc. Al-100 Page 3 of 4 Section: Addressable 11/20/01 detectors alarm threshold. If the detector continually reports an 80% threshold reading (8/10 of what is required to be an alarm condition) for 24 hours, a trouble condition is created. This reduces the risk of false alarms due to dust and dirt by alerting a trouble (maintenance) condition rather than initiating a false alarm. Automatic Test Operation The ADT-Unimode 200 performs an automatic test of each detector every two hours. Failure to meet the test limits causes an AUTO TEST FAIL trouble type. System Reset clears this trouble. NFPA Standards The ADT-Unimode 200 complies with the following NFPA 72 Fire Alarm Systems requirements: • LOCAL (Automatic, Manual, Waterflow, and Sprinkler Supervi- sory). • AUXILIARY (Automatic, Manual, and Waterflow) (requires RTM- 8F) . • REMOTE STATION (Automatic, Manual, and Water -flow) (re- quires RTM-8F o r AD T- UNI COM) . • PROPRIETARY (Automatic, Manual, and Waterflow). • CENTRAL STATION (Automatic, Manual, and Waterflow) (requires ADT-UNICOM). System Capacity • Total programmable input/output points: 198 • Addressable Detectors: 99 • Addressable monitor or control modules: 99 • NACs in panel: 2* • Programmable software zones: 56 • ADT-AFM/LDM/LCD-40 Series Annunciators per System: 32 • ADT-UNICOM Digital Alarm Communicator Transmitter: 1 *NOTE. NA Cs can be added using CMF-300 control modules. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. 1#1347 2001 ADT Security Services, Inc. Controls and Indicators LED Indicators 1. AC POWER (green) 2. FIRE ALARM (red) 3. SUPERVISORY (yellow) 4. ALARM SILENCE (yellow) 5. SYSTEM TROUBLE (yellow) Membrane Switch Controls 1. ACKNOWLEDGE/STEP 2. ALARM SILENCE 3. DRILL 4. SYSTEM RESET (lamp test) 5-16. 12-key pad with full alphabet 17-20. 4 cursor keys 21. ENTER LCD Display 40 characters (2 x 20) with long - life LCD display, backlit. Specifications • Primary input power: 120 VAC, 50/60 Hz, 2.3 Amps. • Total 24 V system power: 3.6 A (expandable to 6.6 A). • Standard Notification Circuits: 2 (Style Y or Z). • Expansion Notification Circuits: up to 99 (using CMF300 Module). • Notification Appliance Power: 3.0 A (expandable to 6.0 A with XRM-24). • Four -wire detector power: 300 mA. * • Non-resettable regulated power: 300 mA. * • Non -regulated power: 2.5 Amps maximum.* *NOTE: Subtract from total 24 VDC source. • Battery charger range: 7 AH - 18 AH(BB-17F battery cabinet for 12 - 18 AH batteries). • Remote charge (panel charger disabled): 25-120 AH (use ADT- CHG- 120). • Charge float rate: 27.6 V. • Charger current limited to 0.8 A. • Control panel Alarm, Trouble, Supervisory Relay contact ratings: 2.0 A @ 30 VDC. Ordering Guide - Peripherals RTM-81F Plug-in Relay Transmitter Option Module. Provides 8 Form-C relays, plus municipal box & remote station connections. PIM-24 Printer Interface Module required to connect a 40- or 80- column printer. (Needed for panels manufacured prior to 9/1 /01 .) DIM-485 Display Interface Module required to convert EIA-232 to EIA- 485 for use with the ADT-LCD40. (Needed for panels manufacured prior to 9/1 /01 .) BB-17F Battery box, required to mount PS-12120 or PS-12180 batteries. BB-55F Battery box, required to house two (2) PS-12250 batteries and one (1) ADT-CHG-120 battery charger. For batteries greater than 25 AH, consult factory for housing/ mounting arrange -meets. ADT-CHG-120 Remote battery charging system. Required for charging 25 to 120 AH batteries. PS-1270 Battery, 12 volt, 7.0 AH, (two required). PS-12120 Battery, 12 volt, 12.0 AH, (two required). PS-12180 Battery, 12 volt, 18.0 AH, (two required). PS-12250 Battery, 12 volt, 25 AH, (two required). PS-12550 Battery, 12 volt, 55 AH, (two required). FCPS-24F Remote Power Supply expands NAC outputs by 6 Amps or total system power by 4 Amps. Windows a is a registered trademark of Microsoft Corporation. tgCO Fire & Security , One Town Center Road Boca Raton, FL 33486 www.adt.com Al-100 Page 4 of 4 Section: Addressable 11 /20/01 HreiffeOAL arms www. rireli re, coil) GENERAL The Fire-Lite Alarms SD355 and SD35ST addressable, low -profile plug-in photoelectric detectors use a state-of- the-art photoelectric sensing chamber with communica- tions to provide open area protection and are used exciu sivelywith Fire-Lite's MS-9200, MS-92000D, and MS-9600 Addressable Fire Alarm Control Panels (FACPs). The SD355f adds thermal sensors that will alarm at a fixed temperature of 135"F (57°C). Since these detectors are addressable, they will help emergency personnel quickly locate a fire during its early stages, potentially saving pre- cious rescue time while also reducing property damage. Two LEDs on each sensor light to provide a local, visible sensor indication. Remote LED annunciator capability is available as an optional accessory (P/N RA40OZ). FEATURES SLC loop: Two -wire loop connection. Urtit uses base for wiring, detector head plugs -in Addressing: • Addressable by device. Direct Decade 01 — 99 (MS-9200, MS-920000) and 01 — 159 (MS-9600) entry of address. Architecture: Lhlique single-sowce, dual-chambel design to respond quickly and dependably to a broad range of fires. Steel<, low -profile design. Integral communications and built-in type identification. Built-in tamper -resistant feature. Removable cover and insect -resistant screen for simple field cleaning. Operation: Withstands air velocities up to 1,500 feet-per-nlirnite (7.6 rn/sec.) without triggering a false alarm. Factory preset at 1.5% nominal sensitivity for panel alarm threshold level. • Visible LED "blinks" when the unit is addressed (com- municating with the fire panel) and latches on in alarm. Mechanicals: • Sealed against back pressure. • Direct surface mounting or electrical box mounting. • Mounts to: single -gang box, 3.5" (6.59 ern) or 4.0" (10.16 cm) octagonal box, or 4.0" (10.16 cm) square electrical box (using a plaster ring — included). .IUly 14, 20C4 DI=-52384 • f-:.•160 AddrressaWe� PhCu'uveleC;r�viiici; Saaolk.e Detectors section: Addressable Devices I California State Fire Marshal sr� 1272-0075:194 JN WED 51059 � RA �. A Q, APPROVED Other system features: • Fully coated circuit boards and superior IRF/transient pro- tection. 94-VO plastic flammability rating. Low standby current. Options. • Remote I-ED output connection (P/N RA40OZ). APIPUCATI @ DNS Use photoelectric detectors in life -safety applications to pro- vide a broad range of fire -sensing capability, especially where smoldering fires are anticipated. Ionization detec- tors are often better than photoelectric detectors at sens- Ing fast, flaming fires. Thisclocute@ Alarms is a Honeywell t company, ��� �o®� This document is rat intended to be used for installation purposes. We try to keep our product information up-to-dato and accurate. We cannot cover all specific applications or anticipate all roquircmonts. All specifications are subject to chanpc without notice. For more information, contact Fire-Lite Alarms, One Fire-Lite Place, Northford, Connecticut 06472, ENC WHIM & 61ANURC111110 Phone: (800) 627-3473, Toll -Free FAX: (877) 699-4105. QUALITY SYSTEMS DF-62384 • 07114l04 — Pago 1 of 2 CONSTRUCTOON 1-hese detectors are constructed of off-white LEXANO. SD355('T) plug-in, low -profile smoke detectors are designed to commercial standards and offer an attractive appear- ance. LEXANQ is a registered trademark of GE Plastics, a subsidiary of General Electric Company. INSTALLATION SD350(1-) plug-in detectors use a detachable mounting base to simplify installation, service and maintenance. Mount base on box which is at least 1.5 inches (3.81 cm) deep. Suitable boxes include: 4.0" (10.16 cm) square box with plaster ring. 4.0" (10.16 cm) octagonal box. 3.5" (8.89 cm) octagonal box. . Single -gang box. NOTE; Because of the inhetent supervision provided by the SLC loop, end -of -Aire resistors are not required. Wiring `T-taps" or branches are permitted for Style 4 (Class B) hiring only, OPER tl BAN Each SD355(?) uses one of 99 possible addresses on the MS-9200 and MS-92000D Signaling Line Circuit (SLC), or LIP to 310 (159 on each loop) on the MS-9600 SI..C. It ie- spends to regular polls from the systern and reports its type and status. The SD355(T) addressable photoelectric sensor's unique unipolar chamber responds quickly and uniformly to a broad range of smoke conditions and can withstand wind gusts LIP to 1,500 feet -per -minute (7.6 m/sec.) without sending an alarm level signal. Because of its unipolar chamber, the SD355('1-) is approximately two times more responsive than rriost photoelectric sensors. This makes it a more stable detector. Each detector can have their sensitivity tested (required per NI=PA 72, Chapter 7 on Inspection, 7-esting and Main- tenance) when installed/connected to an MS-9200, MS., 9200UD, or MS-96DO addressable fire alarm control panel. 1'he results of the sensitivity test can be printed off the MS- 9200, MS-92000D, or MS-9600 for record keeping. SPIr,wCPFICAa' NS Voltage range: 15 - 32 VDC (peak). Standby current: 300 itA @ 24 VDC. LLD current: 6.5 mA @ 24 VDC (latched "UN"). Air velocity: 1,500 ft./min. (7.6 m/sea) maximum. Diameter: 6.1" (15,5 cm) installed in B3501-P base. Height: 2.1" (5.33 cm) installed in B3501-P base. Weight: 3.6 oz. (102 g). Operating 'temperature range: for SD355: 0°C to 49"C (32°F to 120°F) SD350; for S0355T: 0°C to 38°C (32°F to 100°I:), Temperature: 0'C - 49°C (32°F - 120°F). Relative humidity: 10%- 93%, non -condensing. Parle 2 or 2 -- D1=-521114 • 0711 VO4 PRODUCT UINFE IlNFORMA` CINI NOrl: ; "A" suffix indicates 01-C-Listed model. SD355 Addressable photoelectric detector (1335OLP base included). SD355A Same as SD355 with ULC Listing (1335OLFIA base included), SD355T Same as SD355 but with thermal element (3350LP base included). SD355TA Same as SD355T with tJL.0 Listing 03350LPA base included). RA400Z(A) Remote LED. Mounts to a single -gang box. B350Lf (A) Plug-in detector base (included), Dimen- sions: 6,1" (15.5 cm). Mounting: 4.D" (10.16 cm) square box with or without plastic ring, 4,0" (10.16 crn) octagonal box, 3.5" (8,89 cm) octagonal box, or single -gang box. Ail mount- ing boxes have a minimum depth of 1.5" (3.81 cm). B224RB(A) Plug-in System Sensor relay detector base. Diameter: 6.2" (15.75 cm). Mounting: 4.0" (10.16 cm) square box with or Without plastic; ring, 4,0" (10,16 cm) octagonal box, or 3.5" (8.89 cm) octagonal box. All mounting boxes have a Minimum depth of 1.5" (3.81 cm). B224BI(A) intelligent isolator base, isolator SLC from shorts on the loop. 13501BFI(A) Plug-in System Sensor sounder detector base. Diameter: 6.W (15.24 cm). Mounting: 4.0" (10.16 cm) square box with of without plastic ring. Mounting box has a minirnurn depth of 1.5" (3.81 cm). B501CiHT(A) Same as R50113BI-i(A), but includes tempo.. rat sounder. Accessories: RA4007(A) Remote LED annunciator. 3 -- 32. VDC. Fits U.S. single -gang electrical box. For use with 8501(A) and 3350LP(A) bases only. SMK400 Surface mounting kit provides for entry of surface wiring conduit. For use with 8501(A) base only. RMK400 Recessed mounting kit. Foruse with 8501(A) base only. M02-04-01 Test magnet XR-2 Detector removal tool. Allows installation and/ or removal of detector heads from bases in high ceiling applications. XP-4 Extension pole for XR-2. Comes in three 5-ft. (1.524 m) sections, InnovairFlex Intelligent Non -Relay Photoelectric Duct Smoke Detector The Fire-Lite InnovairFlex D355PL intelligent non -relay photo- electric duct smoke detector and DNRW watertight non -relay photoelectric duct smoke detector feature a pivoting housing that fits both square and rectangular footprints capable of mounting to a round or rectangular duct. DNRW duct smoke detector, with its NEMA-4 rating, is listed as a watertight enclosure providing protection against falling dirt, rain, and windblown dust, splashing and hose directed water, allowing operators to use the detector in the most extreme envi- ronments. These units sense smoke in the most challenging conditions, operating in airflow speeds of 100 to 4,000 feet per minute, tem- peratures of -4 degrees F to 158 degrees F, and a humidity range of 0 to 95 percent (non -condensing.) An improved cover design isolates the sensor head, which allows for ease of maintenance. A cover tamper feature indi- cates a trouble signal for a removed or improperly installed sen- sor cover. The Fire-Lite InnovairFlex housing provides a 3/4- inch conduit knockout and ample space to facilitate easy wiring and mounting of a relay module. The Fire-Lite InnovairFlex duct smoke detector can be custom- ized to meet local codes and specifications without additional wiring. The new InnovairFlex product line is compatible with all previous Innovair models, including remote test accessories. Features • Photoelectric, integrated low -flow technology • Air velocity rating from 100 ft/min to 4,000 ft/min (0.5 m/s to 20.32 m/s) • Versatile mounting options: square or rectangular configura- tion • Broad ranges for operating temperature (-4F to 158F) and humidity (0 % to 95% non -condensing) • Patented sampling tube installs from front or back of the detector with no tools required • Cover tamper signal • Increased wiring space with a newly added 3/4" conduit knockout • Available space within housing to accommodate mounting of a relay module • Easily accessible code wheels on sensor head (sold sepa- rately) • Clear cover for convenient visual inspection • Remote testing capability • Requires com line power only • Accommodates the installation of an addressable relay mod- ule, sold separately, (CRF-300) for applications requiring a form-C relay df-60430:a • E-650 (a Flre•ure,aLarms by Honeywell Intelligent Addressable Devices Specifications Size: (Rectangle) 14.38 in (37 cm) Length; 5 in (12.7 cm) Width, 2.5 in (6.6 cm) Depth Size: (Square) 7.75 in (19.7 cm) Length; 9 in (22.9 cm) Width; 2.5 in (6.35 cm) Depth Weight: 1.6 lb (0.73 kg) Environmental Rating: NEMA-4 (DNRW) only Operating Temperature Range: -4 degrees F to 158 degrees F (-20 degrees C to 70 degrees C) Storage Temperature Range: -22 degrees F to 158 degrees F (-30 degrees C to 70 degrees C) Operating Humidity Range: 0% to 95% relative humidity (non -condensing) Air Duct Velocity: 100 to 4,000 ft/min (0.5 to 20.32 m/s) Accessories Fire-Lite provides system flexibility with a variety of accessories, including two remote test stations and different means of visible and audible system annunciation. As with our duct smoke detec- tors, all duct smoke detectors accessories are UL listed. ACCESSORY CURRENT LOADS AT 24 VDC Device Standby Alarm RA400Z OmA 12 mA Max RTS451/ RTS451KEY OmA 12mA Max Agency Listings and Approvals Consult product manual for lists of compatible UL-Listed devices. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Con- sult factory for latest listing status. • UL Listed: 268A df-60430:a • 02/09/09 — Page 1 of 2 Product Line Information D355PL: Intelligent non -relay photoelectric low flow smoke detector housing. DNRW: Watertight intelligent non -relay photoelectric low flow duct smoke detector housing. . SD355: Addressable low -profile photoelectric smoke detector DCOIL: Remote test coil required with RTS451/RTS451 KEY DST1: Metal sampling tube duct width up to 1 ft (0.3m) DST1.5: Metal sampling tube duct widths up to 1 ft to 2 ft (0.3 to 0.6 m) DST3: Metal sampling tube duct widths up to 2 ft to 4 ft (0.6 to 1.2 m) DST5: Metal sampling tube duct widths up to 4 ft to 8 ft (1.2 to 2.4 m) DST10: Metal sampling tube duct widths up to 8 ft to 12 ft (2.4 to 3.7 m) DH4000E-1: Weatherproof enclosure ETX: Metal exhaust tube duct, width 1 ft (0.3 m) M02-04-00: Test magnet P48-21-00: End cap for metal sampling tubes RA40OZ: Remote annunciator alarm LED RTS451: Remote test station RTS451 KEY: Remote test station with key lock Important Notes • The use of either RTS451 or RTS451 KEY requires the instal- lation of an accessory coil, DCOIL, sold seperately. Please refer to the DNR or DNRW installation manual for more infor- mation. • The RTS451 / RTS451 KEY test coil circuit requires an exter- nal 24VDC power supply which must be LIL listed. Fire•LiteO Alarms is a registered trademark of Honeywell International Inc. VisorALARM® is a registered trademark of the Teldat Corporation. ©2009 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. 'SO 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. ENGINEERING A MANUFACTURING QUALITY SYSTEMS All specifications are subject to change without notice. For more information, contact Fire-Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www.firelite.com Page 2 of 2 — df-60430:a • 02/09/09 ADT-BG-12LX Series Addressable Manual Pull Station for use with the Unimode 200 and 9600 The ADT-1313-12LX is a state-of-the- art, dual -action (i.e., requires two motions to activate the station) pull station that includes an interface which provides an addressable alarm initiating input to a Unimode 200 and Unimode 9600 intelligent control panel. Because the ADT-BG- 12LX is addressable, the control panel can display the exact location of the activated manual station. This leads fire personnel quickly to the location of the alarm. Features • Maintenance personnel can open station without causing an alarm condition. • Built-in LED, visible through the handle of the station, flashes in normal operation and latches steady red when in alarm, • Handle latches in down position and the word "ACTIVATED" ap- pears to clearly indicate the sta- tion has been operated. • Captive screw terminals wire -ready for easy connection to SLC loop (accepts up to 12 AWG/3.25 mm2 wire). • Can be surface (with SB-10) or semi -flush mounted. Semi -flush mount to a standard single -gang, double -gang, or 4" (10.16 cm) square electrical box. S S285 Made in the U.S.A. • Smooth dual -action design. • Within ADA 5 lb. pull force. • Highly visible. • Attractive shape and textured fin- ish. • Key reset. • Includes Braille text on station handle. • Optional trim ring (BG-TR). • Meets UL 38, Standard for Manu- ally Actuated Signaling Boxes. • Up to 99 ADT-BG-12LX stations on Unimode 200 systems and up to 159 stations per loop on Unimode 9600 systems. Operation Pushing in, then pulling down on the handle causes it to latch in the down/ activated position. Once latched, the word "ACTIVATED" (in bright yellow) appears at the top of the handle, while a portion of the handle protrudes from the bottom of the station, To reset the station, simply unlock the station with the key and pull the door open. This action resets the handle; closing the door automatically resets the switch. Each manual station, on command from the control panel, sends data to the panel representing the state of the manual switch. Two rotary decimal switches allow address settings 01-99 (Unimode 200) and 01-159 (Unimode 9600). Specifications Normal operating voltage: 24 VDC. Maximum SLC loop voltage: 28.0 VDC. Maximum SLC loop current: 230 NA. Construction • Shell, door, and handle are molded of durable LEXAW' (or polycarbonate equivalent) with a textured finish. • Cover features white lettering and trim. Installation The ADT-BG-1 2LX will mount semi -flush into a single -gang, double -gang, or standard 4" (10.16 cm) square electrical outlet box, or will surface mount to the Model SB-10 surface backbox. if the ADT- BG-12LX is being semi -flush mounted, then the optional trim ring (BG-TR) may be used. The BG-TR is usually needed for semi -flush mounting with 4" (10.16 cm) or double -gang boxes (not with single -gang boxes). Ordering Guide ADT-BG-12LX Dual -action addressable pull station. Includes key locking feature. SB-10 Surface backbox. BG-TR Optional trim ring. tyco Fire & Security 5C A Architectural/Engineering Specifications Manual Fire Alarm Stations shall be non -coded, with a key- operated reset lock in order that they may be tested, and so designed that after actual Emergency Operation, they cannot be restored to normal except by use of a key. An operated station shall automatically condition itself so as to be visually detected as activated. Manual stations shall be constructed of red -colored LEXAN° (or polycarbonate equivalent) with clearly visible operating instructions provided on the cover. The word FIRE shall appear on the front of the stations in white letters, 1 .00 inches (25.4 mm) or larger. Sta- tions shall be suitable for surface mounting on matching backbox SB- 10; or semi -flush mounting on a standard single -gang, double -gang, or 4" (10.16 cm) square electrical box, and shall be installed within the limits defined by the Americans with Disabilities Act (ADA) or per national/local requirements. Manual Stations shall be Underwrit- ers Laboratories listed. Manual stations shall connect with two wires to one of the control panel SLC loops. The manual station shall, on command from the control panel, send data to the panel representing the state of the manual switch. Manual stations shall provide address setting by use of rotary decimal switches. The loop poll LED shall be clearly visible through the front of the station. The LED shall flash while in the normal condition, and stay steadily illuminated when in alarm. LEXAN° is a registered trademark of GE Plastics, a subsidiary of General Electric Company. tyco Fire & Security 110 One Town Center Road Boca Raton, FL 33486 www.adt.com 1# 1337 E-450 4/30/01 2001 ADT Security Services, Inc. Page 2 of 2 MMF-300 Series/MDF-300 Addressable Monitor Modules for use with Unimode 200 and Unimode 9600 Four different monitor modules are available for the Unimode 200 and Unimode 9600 intelligent fire alarm control panels to suit a variety of applications. Monitor modules are used to supervise a circuit of dry - contact input devices, such as conventional heat detectors and pull stations, or monitor and power a circuit of two -wire smoke detec- tors (MMF-302). MMF-300 (Replaces M300) — The MMF-300 Monitor Module is a standard -sized module (typically mounts to a 4" [101.6 mm] square box) that supervises either a Class A (Style D) or Class B (Style B) circuit of dry -contact input devices. MMF-301 (Replaces M301) — The MMF-301 is a Miniature Monitor Module (a mere 1.3" (33.02 mm) H x 2.75" (69.85 mm) W x 0.5" (12.70 mm) D) used to supervise a Class B (Style B) circuit. Its com- pact design allows the MMF-301 to be mounted in a single -gang box behind the device it is monitoring. MMF-302 (Replaces M302) — The MMF-302 Interface Module is a standard -sized module used to monitor and supervise compatible two -wire, 24 volt, smoke detectors on a Class A (Style D) or Class B (Style B) circuit. MDF-300 (New) — The MDF-300 Dual Monitor Module is a standard- RWRMMM Made in the U.S.A. sized module (typically mounts to a 4" [101.6 mm] square box) that supervises two Class B (Style B) circuits of dry -contact input de- vices. MMF-300 Monitor Module • Built-in type identification auto- matically identifies this device as a monitor module to the control panel. • Powered directly by two -wire SLC loop. No additional power required. • High noise (EMF/RFI) immunity. • SEMS screws with clamping plates for ease of wiring. • Direct Decade 01 — 99 (Unimode 200) and 01-159 (Unimode 9600) entry of address. • LED flashes red during normal operation and latches on steady red to indicate alarm. The MMF-300 Monitor Module is intended for use in intelligent, two - wire systems, where the individual address of each module is selected using the built-in rotary switches. It provides either a two -wire or four - wire Class A or Class B fault - tolerant Initiating Device Circuit (IDC) for normally -open -contact fire alarm and supervisory devices. The MMF-300 can be used to replace M300 modules in existing systems. Installation MMF-300, MMF-302 and MDF- 300 modules mount directly to a standard 4" (101 .6 mm) square, 2.125" (53.975 mm) deep, electrical box. They may also be mounted to the SM8500 sur- face -mount box. Mounting hardware and installation instructions are provided with each module. All wiring must conform to applicable local codes, ordinances, and regula- tions. These modules are in- tended for power -limited wiring only. The MMF-301 module is in- tended to be wired and mounted without rigid connections inside a standard electrical box. All wiring must conform to appli- cable local codes, ordinances, and regulations. Ordering Guide MMF-300 Monitor Module. MMF-301 Mini Monitor Module. MMF-302 Two -Wire Detector Monitor Module. MDF-300 Dual Monitor Module. SMS500 Optional Surface - Mount Backbox. Tyco Fire & Security MMF-300 Applications — Use to monitor a zone of four -wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally -open dry -contact alarm activation devices. May also be used to monitor normally -open supervisory devices with special supervisory indication at the control panel. Monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class D) Initiating Device Circuit. A 47K ohm End -of -Line Resistor (provided) terminates the Style B circuit. No resistor is required for supervision of the Style D circuit. Maximum IDC resistance is 1,500 ohms. MMF-300 Operation — Each MMF- 300 uses one of 99 (Unimode 200) or one of 159 (Unimode 9600) available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop). MMF-300 Specifications Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.1 mA (LED on). Average operating current: 400 /iA (LED flashing). EOL resistance: 47K ohms. Temperature range: 32 IF to 120 IF (01C to 490C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x 1 .25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x 2.125" (53.975 mm) deep box. MMF-301 Mini Monitor Module • Built-in type identification auto- matically identifies this device as a monitor module to the Unimode 200 or Unimode 9600. • Powered directly by two -wire SLC Loop. No additional power required. • High noise (EMF/RFI) immunity. • Tinned, stripped leads for ease of wiring. • Direct -dial entry of address 01-99 (Unimode 200) and 01-159 (Unimode 9600). The MMF-301 Mini Monitor Module can be installed in a single -gang junction directly behind the moni- tored unit. Its small size and light weight allow it to be installed without rigid mounting. The MMF- 301 is intended for use in intelli- gent, two -wire systems where the individual address of each module is selected using rotary switches. It provides a two -wire initiating device circuit for normally -open -contact fire alarm and supervisory devices. The MMF-301 can be used to replace M301 module in existing systems. 1415 0 1 ADDRESS 0 1 13 2 � 2 11 O q LOOP O 4 109 8 7 65 098 7 65 TENS ONES MMF-301 Applications — Use to monitor a single device or a zone of four -wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally -open dry - contact devices. May also be used to monitor normally -open supervi- sory devices with special supervi- sory indication at the control panel. Monitored circuit/device is wired as an NFPA Style B (Class B) Initiating Device Circuit. A 47K ohm End -of - Line Resistor (provided) terminates the circuit. MMF-301 Operation — Each MMF- 301 uses one of 99 (Unimode 200) or one of 159 (Unimode 9600) available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC). MMF-301 Specifications Nominal operating voltage: 15 to 32 VDC. Average operating current: 375 /iA maximum. EOL resistance: 47K ohms. Temperature range: 3 2 1 F to 1200F (0°C to 490C). Humidity range: 10% to 93% noncondensing. Dimensions: 1.3" (33.02 mm) high x 2.75" (69.85 mm) wide x 0.5" (12.70 mm) deep. Wire length: 6" (152.4 mm) mini- mum. MMF-302 Interface Module • Supports compatible two -wire smoke detectors. • Supervises IDC wiring and connection of external power source (resettable). • High noise (EMF/RFI) immunity. • SEMS screws with clamping plates for ease of wiring. • Direct -dial entry of address (01- 99 for Unimode 200, 01-1 59 for Unimode 9600). • Requires resettable 24 VDC, regulated. • LED flashes during normal opera- tion. • LED latches steady to indicate alarm on command from control panel. The MMF-302 Interface Module is intended for use in intelligent, addressable systems, where the individual address of each module is selected using built-in rotary switches. This module allows intelligent panels to interface and monitor two -wire conventional smoke detectors. It transmits the status (normal, open, or alarm) of one full zone of conventional detectors back to the control panel. All two -wire detectors being monitored must be UL compatible with the module. MMF-302 Applications — Use the MMF-302 to monitor a zone of two - wire smoke detectors. The moni- tored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 3.9 K ohm End -of -Line Resistor (provided) terminates the end of the Style B or D (class B or A) circuit (maximum IDC loop resistance is 25 ohms). Install ELR across terminals 8 and 9 for Style D application. MMF-302 Operation — Each MMF- 302 uses one of 99 (Unimode 200) or one of 159 (Unimode 9600) available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop). MMF-302 Specifications Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.1 mA (LED on). Average operating current: 270 /jA (LED flashing). IN 1340 2001 ADT Security Services, Inc. E-325 Page 2 of 3 Section: Addressable Devices 10/8/01 EOL resistance: 3.9K ohms. External supply voltage (between Terminals T3 and T4): DC voltage: 18 to 28 volts power limited. Ripple voltage: 0.1 VRMS maximum. Current: 90 mA per module maxi- mum. Requires regulated, resettable 24 VDC power. Temperature range: 321F to 120eF WC to 491C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x 1 .25" (31.75 mm) deep. Mounts to a 4" (101 .6 mm) square x 2.125" (53.975 mm) deep box. MDF-300 Dual Monitor Module • Built-in type identification auto- matically identifies this device as two monitor modules to the control panel. • Powered directly by the two -wire SLC loop. No additional power required. • High noise (EMF/RFI) immunity. • SEMS screws with clamping plates for ease of wiring. • Direct -dial entry of address 01 — 159 on the Unimode 9600. • LED flashes red during normal operation and latches on steady red to indicate alarm. The MDF-300 Dual Monitor Module is intended for use in intelligent, two -wire systems, where the individual address of each module is selected using the built-in rotary switches. It provides two independant two -wire fault -tolerant Initiating Device Circuits (IDCs) at two separate, consecutive ad- dresses. It is capable of monitoring normally open -contact fire alarm and supervisory devices, or either normally open or normally closed devices for non -fire applications. MDF-300 Applications - Use to monitor a zone of four -wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally -open dry -contact alarm activation devices. May also be used to monitor normally -open supervisory devices with special supervisory indication at the control panel. Monitored circuit may be wired as an NFPA Style B (Class B) Initiating Device Circuit. The 47K ohm End -of -Line Resistors (pro- vided) terminate the Style B circuit. Maximum IDC resistance is 1,500 ohms. MDF-300 Operation - Each MDF- 300 uses two of 99 (Unimode 200) or two of 159 (Unimode 9600) available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop). MDF-300 Specifications Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.1 mA (LED on). Average operating current: 750 NA (LED flashing). EOL resistance: 47K ohms. Maximum IDC wire resistance: 1,500 Ohms. Temperature range: 32 ° F to 120 e F (01C to 491C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x 1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x 2.125" (53.975 mm) deep box. Accessories: SMB500 electrical box. I T Mounting Diagram for standard -sized modules 1-11 1=_1 t qCO Fire & Security 110 One Town Center Road Boca Raton, FL 33486 www.adt.com 1# 1340 2001 ADT Security Services, Inc, E-325 Page 3 of 3 Section: Addressable Devices 10/8/01 July 8, 2004 DF-52310 - D-05G FI " -LIT+ "ALarms FCPS-24FSS 24 Vok 8 .Ante Remote Pcrrrtrer Supply www.frelhe.coni Section- Power Supplies/Accessories GENERAL The FCPS-24PSB is a compact, cost-effective, 8-amp re- mote power supply with battery charger- The FCPS-24FS8 may be connected to any 12- or 24-volt Fire Alarm Control Panel (FRCP) or may stand alone. Primary applications include Notification ;Appliance (bell) Circuit (NAC) expan- sion (to support ADA requirements and NAC synchroniza- tion) or auxiliary power to support 24-volt .system acces- sories. The FCPS-24FS8 provides regulated and filtered 24 VDC power to four Notification Appliance Circuits con- figured as either four Class B (Style Y) or Class A (Style Z, with ZNAC-4 option module)- Alternately, the four outputs may be configured as all non-resettable or all resettable or two non-resettable and two resettable. The FCPS- 24FS8 also contains a battery charger capable of charg- ing up to 18 Amp Hour batteries. "ATURES • UL Listed NAC Synchronization using System Sensor, Wheelock, or Gentex (Commander Series) appliances. • Cascadable up to 10 power supplies (four with Gentex) with strobe timing maintained - Operates as a sync follower or sync generator (default), * See note on reverse side. • Contains two, fully -isolated input/control circuits (trig- geredfrom FRCP Notification Appliance Circuit [NAC expander mode] or jumpered permanently on [stand- alone mode]). • Optional mounting kit, PIN 90286, to internally house addressable SLC control module (CRF-300 or CPYiF- 300) for alarm activation. • Four Class B (Style Y) orfourClass A (StyleZ) (with ZNAC- 4 Module) Notification Appliance Circuits. • 8.0 A full load output (3.0 A maximum per circuit) in NAC expander mode (UL 864). - 6.0 A continuous output in stand-alone mode (UL 1481). • Compatible with coded inputs- signals passed through. • Optional power supervision relay (A77-716B). • In stand-alone mode, output power circuits may be configured as resettable (reset line from FACP required) or non-resettable or a mix of hvo and two_ = Fully regulated and filtered power output (optimal for powering four -wire smoke detectors, annunciators and other system peripherals requiring regulated/filtered power) - Power -limiting technology meets power -limiting require- ments_ • Normally -closed trouble contact. • Fully supervised power supply, battery and Notification California g F State Fire Marshal APPRBVFD 7315-0075:206 LISTED S2424 M EA 2'19-02-E Appliance Circuits. • Selectable earth fault detection. • AC trouble report selectable for immediate or 8 hour delay. • Works with virtually any UL 864 fire alarm control which utilizes an industry -standard reverse -polarity notifica- tion circuit (including unfiltered and unregulated bell power) - Requires input trigger voltage of 9.0 - 32 VDC. • Self-contained in compact, lockable cabinet (15" 138.1 cm] H x 14.5" [36.8 cm] W x 2-75" [7.0 cm] D)_ • Includes integral battery charger capable of charging up to '18 AH batteries. Cabinet capable of housing 7-0 AH batteries - Battery charger may be disabled via dip switch for appli- cations requiring larger batteries.. • Fixed, clamp -type terminal blocks accommodate up to 12 AWG (3.1 mm=) wire - This ocu Alarms is a intended t company. � � This document is not intended to be used for installation purposes- We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Fire-Lite Alarms, One Fire-Lite dace, Northford, Connecticut 06472. @I1NEB111%lk � Phone: (800) 627-3473, Toll -Free FA?{: (877) 699-4105. 4 S S t I T Y SYSTEMS GF-52310 - 071DW04 — Page 1 or 2 STANDARDS and CODES The FCPS-24FS8 complies with the following standards: • NFPA 72 National Fire Alarm Code. • UL 864 Standard for Control Units for Fire Alarm Sys- tems (NAC expander ,mode). . UL 1481 Power Supplies for Fire Alarm Systems (stand-alone mode)_ SPECIFICATIONS Primary (AC) Power • 'FCPS-24FS8: 120 VAC 60 Hz, 3.2 A maximum. • Wire size: minimum 14 AWG (2.0 mm-) with 600V insu- lation. Control Input Circuit - Trigger Input Voltage: 9.0 to 32 VDC_ • Trigger Current: 2.0 mA (16 - 32 V). (per input) 1.0 mA (9 - 16 V)- Trouble Contact Rating • 5.0 A at 24 VDC_ Auxiliary Power Output Specific Application Power - 500 mA maximun. Output Circuits • +24 VDC filtered, regulated. • 3.0 A maximum for any one circuit. • 6.0 A maximum total continuous current for all outputs (Stand-alone mode). • 8.0 A maximum total short-term current. for all outputs (NAC Expander mode). Secondary Power (Battery) Charging Circuit • Supports lead -acid batteries only. • Float Charge Voltage: 27.6VDC. • Maximum Charge Current: 1.5 A. • Maximum Battery Capacity: 18 AH. ORDISUNG INFORMATION FCPS-24FS8 Remote charger power supply (120 VAC). Includes main printed circuit board, transformers, red enclosure, and installation instructions. FCPS-2456RB Replacement mother board. PN 90286 FCPS-24FS Module Mounting Kit ZNAC-4 Class A (Style Z) NAC option module. A77-716B 12124 VDC end -of -line relay for monitoring 4-wire smoke detector power_ BAT-1270 Battery, 12 volt, 7.0 AH (two required). APPLICATIONS Example 1 Expand notification appliance pourer an additional 8.0 amps. Use up to 4 Class B (Style Y) outputs or 4 Class A (Style Z) using the ZNAC-4_ In this example, the FACP notification appliance circuits will activate the FCPS-24FS8 when reverse polarity activa- tion: occurs. Trouble conditions on the FCPS-24FSB are sensed by the FACP through the Notification Appliance circuit_ Page 2 of 2 — DF-52310 • 07;'OWD4 Example 2 Use the FCPS-24FS8 to expand auxiliary regulated 24 volt system power up to 6.0 amps- Both non-resettable and resettable power options are available. Resettable outputs are createdby connecting the resettabie output from the FACP to one or both of the FCPS-24FS8 inputs. Example 3 Use addressable control modules to activate the FCPS- 24FS8 versus the FACP Notification Appliance Circuits. This typically allows for mounting: the FCPS-24FSB at greater distances` away from the FACP while expanding system architecture in various applications. In this example, an addressable control module is used. to activate the FCPS-24FS8 and an addressable monitor module is used to sense FCPS-24FS8 trouble conditions. Local auxiliary power output from the FCPS-24FS8 pro- vides power to the addressable control module- 'Fire-Lite's MS-9200 (198-point), MS-9200t1D, or MS-9600 (63&- pointy addressable FACPs have the capability of locating control and monitor modules up to 10,000 feet (3048 m)away. Sync Follower}Genera#or Note: In some installations, it is necessary to synchronize the flash timing of all strobes in the system for ADA compliance. Strobes accomplish this by monitoring very short timing pulses on the NAC power, which are created by a Fire Alarm Control Panel such as the Fire-Lite MS-9600. When installed at the end' of a MS-9600 NAC wire run, this power supply can track (i.e., "follow") the strobe synchronization timing pulses on the existing NAC wire run. This maintains the overall sys- tem flash timing of the additional strobes attached to this power supply. When this power supply is configured (via DIP switch settings) as a "sync follower," this supply's NAC outputs track the strobe synchronization pulses present at this supply's sync input terminal_ The pulses are originated from an upstream FACP or other power supply. When this power supply is configured (via DIP switch settings) as a "sync generator," this supply's sync input terminal are not used. Rather, this power supply is the originator of the strobe synchronization pulses on this power supply's NAG outputs. In "sync generator" mode, the sync type (System Sensor, Wheelock, or Gentex) is selectable via DIP switch settings. �� SYSTEM Selectable Output Notification Devices SpectrAlert' Advance selectable -output horns, strobes, and horn/strobes are rich with features guaranteed to cut installation times and maximize profits. The SpectrAlert Advance series of notification appliances is designed to simplify your installations, with features such as: plug in designs, instant feedback messages to ensure correct installation of individual devices, and eleven field -selectable candela settings for wall and ceiling strobes and horn/strobes. More specifically, when installing Advance products, first attach a universal mounting plate to a four -inch square, four -inch octagon or double -gang junction box.The two -wire mounting plate attaches to a single -gang junction box. Then, connect the notification appliance circuit wiring to the SEMS terminals on the mounting plate. Finally, attach the horn, strobe or horn/strobe to the mounting plate by inserting the product's tabs in the mounting plate's grooves.The device will rotate into position, locking the product's pins into the mounting plate's terminals.The device will temporarily hold in place with a catch until it is secured with a captured mounting screw. SpectrAlert Advance products allow you to choose: 12 or 24 volts At 24 volts, 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177 or 185 candela by way of rear -mounted slide switch and front viewing window Horn tones and volume by way of rotary switch The SpectrAlert Advance series includes outdoor notification appliances. Outdoor strobes and horn/strobes (two wire and four wire) are available for wall or ceiling. Outdoor horns are available for wall only. All System Sensor outdoor products are rated between minus 40 degrees Fahrenheit and 151 degrees Fahrenheit in wet or dry applications. Features Plug-in design Same mounting plate for wall- and ceiling -mount units Shorting spring on mounting plate for continuity check before installation • Captive mounting screw -Tamper resistance capability Field selectable candela settings on wall and ceiling units: 15, 15/75, 30, 75, 95,110, 115, 135, 150, 177, 185 Automatic selection of 12 or 24 volt operation at 15 and 15/75 candela Outdoor wall and ceiling products Outdoor products rated from —40' to 151 °F Minimal intrusion into the back box Horn rated at 88+ dbA at 16 volts Rotary switch for tone selection 3 horn volume settings Electrically compatible with existing SpectrAlert products Agency Listings SIGNALING uL F M MEA 7125-I653:1 d6 (—door r tfobbe,) ) 71s-1653:1970,m LISTED APPROVED approved 7125-1653:1 BB !horn/strobes) / 7725-1653:IA9(h. p ) S4011 1023572 MEM45205-E SpectrAlert Advance Specifications General SpectrAlert Advance horns, strobes and horn/strobes shall mount to a standard 4 x 4 x 1'/2-inch back box, 4-inch octagon back box or double -gang back box. Two -wire products shall also mount to a single -gang 2 x 4 x lh-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync•Circuit' Module accessory, shall be powered from a non -coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync -Circuit Module, 12-volt rated notification appliance circuit outputs shall operate between nine and 17.5 volts; 24-volt rated notification appliance circuit outputs shall operate between 17 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC, or full -wave rectified, unfiltered power supply. Strobes and horn/strobes shall have field -selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135,150, 177, 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary -signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon (lash tube and associated lens/reflector system. Horn/Strobe Combination The horn/strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn/strobe shall be wired as a primary -signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Tz over the strobes entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have three audibility options and an option to switch between a temporal three -pattern and a non -temporal (continuous) pattern.These options are set by a multiple position switch. On four -wire products, the strobe shall be powered independently of the sounder. The horn on horn/strobe models shall operate on a coded or non -coded power supply. Outdoor Products SpectrAlert Advance outdoor horns, strobes and horn/strobes shall be listed for outdoor use by UL and shall operate between minus 40 degrees and 1 S1 degrees Fahrenheit. The products shall be listed for use with a System Sensor outdoor/weatherproof back box with half inch and three -fourths inch conduit entries. Synchronization Module The module shall be a System Sensor Sync -Circuit listed to UL 464 and shall be approved for fire protective service. Ihe module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn/strobe models over a single pair of wires. The module shall mount to a 476 x 06 x A -inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit.The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Standard Operating Temperature 32°F to 120°F (0°C to 49°C) K Series Operating Temperature —407 to 151°F (-40°C to 66°C) Humidity Range 10 to 93% non -condensing (indoor products) Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12DC/FWR or regulated 24DC/FWR' Operating Voltage Range2 8 to 17.5 V (12V nominal) or 16 to 33 V (24 nominal) Input terminal wire gauge 12 to 18 AWG Ceiling mount dimensions (including lens) 6.8"diameter x 2.5" high (173 mm diameter x 64 mm high) Wall mount dimensions (including lens) 5.61 x 4.7 W x 2.5-D (142 mm L x 119 mm W x 64 mm D) Horn dimensions 5.61 x 4.7V x 1.3`D (142 mm L x 119 mm Wx33 mm D) Notes: 1. Full Wave Rectified (FWR) voltage is a non -regulated, time varying power source that is used on some power supply and panel outputs. 2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd. A05 0395-002 UL Current Draw Data UL Max. Horn Current Draw (mA RMS) 8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts Candela DC FWR DC FWR Sound Pattern dB DC FWR DC FWR Standard 15 123 128 66 71 Temporal High 57 55 69 75 Candela Range 15/75 142 148 77 81 Temporal Medium 44 49 58 69 30 NA NA 94 96 Temporal Low 38 44 44 48 75 NA NA 158 153 Non -temporal High 57 56 69 75 95 NA NA 181 176 Non -temporal Medium 42 50 60 69 110 NA NA 202 195 Non -temporal Low 41 44 50 50 115 NA NA 210 205 Coded High 57 55 69 75 High 135 NA NA 228 207 Coded Medium 44 51 56 69 Candela Range 150 NA NA 246 220 Coded Low 40 46 52 50 177 NA NA 281 251 185 NA NA 286 258 UL Max. Current Draw (rnA RMS), 2-wire Horn/Strobe, Standard Candela Range (15-115 cd) 8-17.5 Volts 16-33 Volts DC Input 15 15/75 15 15/75 30 75 45 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non -temporal High 141 152 91 100 116 176 201 221 229 Non -temporal Medium 133 145 75 85 102 163 187 207 216 Non -temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non -temporal High 142 161 103 112 126 181 203 221 229 Non -temporal Medium 134 155 85 95 110 166 189 208 216 Non -temporal Low UL Max. Current Draw 132 (mA RMS), 2-wire 154 Horn/Strobe, High 80 Candela Range 90 105 161 184 202 211 16-33 Volts (135-185 cd) 16-33 Volts DC Input 135 150 177 185 FWR Input 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non -temporal High 255 270 303 309 Non -temporal High 233 248 275 281 Non -temporal Medium 242 259 293 299 Non -temporal Medium 219 232 262 267 Non -temporal Low 238 254 291 295 Non -temporal Low 214 229 256 262 Horn Tones and Sound Output Data Rotary Horn and Horn/Strobe Switch Settings Horn and Horn/Strobe Output (dBA) Setting Repetition Rate dB Level Switch 8-17.5 Volts 16-33 Volts 1 Temporal horn High Position Sound Pattern dB DC FWR DC FWR 2 Temporal horn Medium 1 Temporal High 78 78 84 84 3 Temporal horn Low 2 Temporal Medium 74 74 80 80 4 Normal horn High 3 Temporal Low 71 73 76 76 5 Normal horn Medium 4 Non -temporal High 82 82 88 88 6 Normal horn Low 5 Non -temporal Medium 78 78 85 85 7* Externally coded High 6 Non -temporal Low 75 75 81 81 8* Externally coded Medium 7* Coded High 82 82 88 88 9* Externally coded Low 8* Coded Medium 78 78 85 85 9* Coded Low 75 75 81 81 *Settings 7, 8, and 9 are not available on 2-wire horn/strobe. A05-0395.002 lert Advance Dimensions SpectrAlert Advance Ordering Information faouei Nescription Wall Horn/Strobes P2R*' 2-wire Horn/Strobe, Standard cdt, Red P2RH* 2-wire Horn/Strobe, High cd, Red P2RK* 2-wire Horn/Strobe, Standard cd, Red, Outdoor P2RHK* 2-wire Horn/Strobe, High cd, Red, Outdoor P2W* 2-wire Horn/Strobe, Standard cd, White P2WH* 2-wire Horn/Strobe, High cd, White P4R* 4-wire Horn/Strobe, Standard cd, Red P4RH* 4-wire Horn/Strobe, High cd, Red P4RK 4-wire Horn/Strobe, Standard cd, Red, Outdoor P4RHK 4-wire Horn/Strobe, High cd, Red, Outdoor P4W* 4-wire Horn/Strobe, Standard cd, White P4WH* 4-wire Horn/Strobe, High cd, White Wall Strobes SR*' Strobe, Standard cd, Red SRH*' Strobe, High cd, Red SRK Strobe, Standard cd, Red, Outdoor SRHK Strobe, High cd, Red, Outdoor SN* Strobe, Standard cd, White SWH* Strobe, High cd, White Ceiling Horn/Strobes PC2R* 2-wire Horn/Strobe, Standard cd, Red PC2RH* 2-wire Horn/Strobe, High cd, Red PC2RK 2-wire Horn/Strobe, Standard cd, Red, Outdoor PC2RHK 2-wire Horn/Strobe, High cd, Red, Outdoor 8„ a. Model Description Ceiling Horn/Strobes (contd.) PC2W*' 2-wire Horn/Strobe, Standard cd, White PC2WH*' 2-wire Horn/Strobe, High cd, White PC4R 4-wire Horn/Strobe, Standard cd, Red PC4RH 4-wire Horn/Strobe, High cd, Red PC4RK 4-wire Horn/Strobe, Standard cd, Red, Outdoor PC4RHK 4-wire Horn/Strobe, High cd, Red, Outdoor PC4W 4-wire Horn/Strobe, Standard cd, White PC4WH 4-wire Horn/Strobe, High cd, White Ceiling Strobes SCR* Strobe, Standard cd, Red SCRH* Strobe, High cd, Red SCRK Strobe, Standard cd, Red, Outdoor SCRHK Strobe, High cd, Red, Outdoor SCW*' Strobe, Standard cd, White SCWH*' Strobe, High cd, White Horns HR Horn, Red HRK Horn, Red, Outdoor HW Horn,White Accessories BBS-2 Back Box Skirt, Wall, Red BBSW-2 Back Box Skirt, Wall, White BBSC-2 Back Box Skirt, Ceiling, Red BBSCW-2 Back Box Skirt, Ceiling, White Notes: * Add "-P"to model number for plain housing (no"FIRE"marking on cover), e.g., P2R-P t Add "-SP"to model number for"FUEGO" marking on cover, e.g., P2R-SP *"High cd," refers to strobes that include 135, 150,177, and 185 candela settings."Standard cd," refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. SYSTEM sy��-5-3a,. 3825 Ohio Avenue - St. Charles, IL 60174 P,odua p-fi ,n—n b;eatnchaan9PInith ����-Vis sy—see,,— W SENSOR Phone: 800-SENSOR2•Fax: 630-377-6495 COfe°`;,md�j'f*al; irc'°dwgWelatest wrionofmisdala ee. A05 039S 0o2. 7/06.01659 Part Five Floor Plan Layout