HomeMy WebLinkAboutPLANS - 22-00730 - 7N Apartments - Bldg 4 - Fire Alarm7TH NORTH APARTMENTS 7TH NORTH & STONEBRIDGE ST REXBURG, ID 83440 GENERAL NOTES: 1.THESE DRAWINGS ARE DIAGRAMMATIC. REFER TO THE ARCHITECTURAL DRAWINGS FOR EXACT DIMENSIONS. 2.INSTALLATION SHALL COMPLY WITH 2017 NEC, 2016 NFPA 72, 2018 IBC/IFC AND ALL OTHER APPLICABLE CODES AS REQUIRED BY THE LOCAL AUTHORITY HAVING JURISDICTION. 3.WIRING DEPICTED ON THESE PLANS IS SCHEMATIC - ACTUAL WIRE LOCATIONS MAY DIFFER FROM THESE PLANS. WIRING SHALL BE PERFORMED AS ACTUAL BUILDING CONSTRUCTION CONDITIONS ALLOW AND TO MINIMIZE PENETRATIONS THROUGH AREA SEPARATION WALLS AND FIRE WALLS. THE USE OF A RACEWAY IS PERMITTED AS LONG AS NO 110V OR HIGHER VOLTAGE CABLES ARE IN THE SAME RACEWAY. 4.FIRE RATINGS SHALL BE MAINTAINED FOR ALL PENETRATIONS THROUGH FIRE-RATED CONSTRUCTION. 5.POWER FOR ALL FIRE ALARM PANELS AND FIRE ALARM POWER SUPPLIES MUST BE PROVIDED BY A DEDICATED AC BRANCH CIRCUIT. 6.POWER-LIMITED AND NONPOWER-LIMITED CIRCUIT WIRING MUST REMAIN SEPARATED IN CABINET. ALL POWER-LIMITED CIRCUIT WIRING MUST REMAIN AT LEAST 0.25" AWAY FROM ANY NONPOWER-LIMITED CIRCUIT WIRING. FURTHERMORE, ALL POWER-LIMITED AND NONPOWER-LIMITED CIRCUIT WIRING MUST ENTER AND EXIT THE CABINET THROUGH DIFFERENT KNOCK OUTS AND/OR SEPARATE CONDUITS. 7.WHEN UTILIZING SHIELDED CABLE TIE SHIELDS THROUGH AND INSULATE AT EACH JUNCTION BOX. INSULATE AND TAPE BACK AT END. 8.ALL FIRE ALARM CABLING SHALL BE ACCEPTABLE TO THE FIRE ALARM EQUIPMENT MANUFACTURER FOR THE INTENDED PURPOSE. 9.SMOKE DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER CONSTRUCTION CLEAN-UP IS COMPLETED AND FINAL. 10.LOCATE SMOKE DETECTORS A MINIMUM OF THREE (3) FEET FROM MECHANICAL DIFFUSERS. WALL-MOUNTED SMOKE DETECTORS SHALL BE LOCATED A MINIMUM OF 4" AND A MAXIMUM OF 12" FROM CEILING. CEILING-MOUNTED SMOKE DETECTORS SHALL BE MOUNTED ON CEILINGS AND NOT ON THE BOTTOMS OF BEAMS OR JOISTS. 11.PROVIDE SYNCHRONIZATION OF ALL VISUAL NOTIFICATION APPLIANCE CIRCUITS. PROVIDE ALL REQUIRED SYNC MODULES. PROVIDE A MULTI-SYNC MODE SLAVE CONNECTION BETWEEN ALL SYNC MODULES. 12.VERIFY ALL FIELD SELECTABLE AUDIBILITY SETTINGS OF NOTIFICATION APPLIANCES WITH FIRE ALARM CONTRACTOR. 13.UPON COMPLETION OF THE FIRE ALARM SYSTEM INSTALLATION AND PROGRAMMING, THE INSTALLING CONTRACTOR SHALL PERFORM FINAL TESTING OF THE ENTIRE SYSTEM, PER ALL APPLICABLE CODES, AND SHALL COORDINATE AND PERFORM A FINAL FIRE ALARM SYSTEM INSPECTION. 14.PROVIDE OFF-SITE MONITORING AS REQUIRED BY THE INTERNATIONAL FIRE CODE, SECTION 907.15 AND THE LOCAL AUTHORITY HAVING JURISDICTION. 15.INSTALLING CONTRACTOR SHALL, PHYSICALLY, LABEL ALL INITIATING DEVICES AND NOTIFICATION APPLIANCE CIRCUIT END OF LINE (WHEN WIRING CLASS "B"). THESE LABELS SHALL BE IN PLACE PRIOR TO START-UP AND TESTING. 0 6'12' OCCUPANCY GROUP(S): R2 TYPE OF CONSTRUCTION: V B FIRE SPRINKLER: FULLY SPRINKLED SF AREA OF WORK: 4.240 SF. CEILING HEIGHT: 9' EOL HORN/STROBES, STROBES, HORNS (FPL, FPLR OR FPLP (1)#14/2 RED CABLE REQUIRED) SLC / ADDRESSABLE LOOPS (FPL, FPLR OR FPLP (1)#18/4 RED CABLE REQUIRED) ANNUNCIATOR (FPL, FPLR OR FPLP (2) #18/4 RED CABLES) SCALE: MAIN FLOOR FIRE ALARM PLAN 3/16" = 1'-0"1 FACP ZONE-1 #18/4 AWG P KITCHEN NICET CERTIFIED Robert W. Ryan Lead Installer NICET IV Cert 108137 PROJECT MANAGER: Ritch Way Cell: (208) 520.2665 Office: (208) 524-4282 DINING FAMILY ROOM UNIT A BED 3BED 2 BED 1 CLOSET BATH 1 BATH 2 COVERED ENTRY ROOM LAUNDRY KITCHEN DINING FAMILY ROOM UNIT B BED 3 BED 2 BED 1 CLOSET BATH 1 BATH 2 LAUNDRY KITCHENDINING FAMILY ROOM UNIT C BED 3BED 2 BED 1 CLOSET BATH 1 BATH 2 LAUNDRY KITCHEN DINING FAMILY ROOM UNIT D BED 3 BED 2 BED 1 CLOSET BATH 1 BATH 2 LAUNDRY COVERED ENTRY SCALE: UPPER FLOOR FIRE ALARM PLAN 3/16" = 1'-0"2 SCALE: ENLARGED RISER ROOM N.T.S.3 ZONE-3 EOL ZONE-2 #18/4 AWG EOL EOL ZONE-4 EOL #18/4 AWG LF110 LF110 LF 110 LF110 LF110 LF110 LF 110 LF110 WP 75 RISER NAC-1 #14/2 AWG EOL LF110 LF110 LF 110 LF110 LF110 LF110 LF 110 LF110 NAC-2 #14/2 AWG 7T H N O R T H A P A R T M E N T S DA T E No . RE M A R K S RE V I S I O N S DATE REVISION CHECKED DRAWN 09/27/2022 7T H N O R T H & S T O N E B R I D G E S T Al a r m PE A K A L A R M 24 0 S . H O L M E S , I D A H O F A L L S I D 8 3 4 0 1 Ph . ( 2 0 8 ) 5 2 4 - 4 2 8 2 E X T 0 RW STAMP NICET R RE X B U R G , I D 8 3 4 4 0 ROS FA-01 FI R E A L A R M P L A N 0 RE L E A S E E G R E S S M A G L O C K S / U N L O C K E X I T S TR A N S M I T T R O U B L E S I G N A L TR A N S M I T S U P E R V I S O R Y S I G N A L TR A N S M I T A L A R M S I G N A L AC T I V A T E A U D I B L E T R O U B L E I N D I C A T O R AC T I V A T E T R O U B L E I N D I C A T O R AC T I V A T E A U D I B L E S U P E R V I S O R Y S I G N A L AC T I V A T E S U P E R V I S O R Y I N D I C A T O R AC T I V A T E A U D I B L E A L A R M FI R E A L A R M O U T P U T AC T I V A T E A L A R M I N D I C A T O R NAC SHORT CIRCUIT LOSS OF AC TO BUILDING GROUND FAULT OPEN CIRCUIT FIRE ALARM LOW BATTERY FIRE ALARM AC POWER FAIL VALVE TAMPER SWITCHES WATERFLOW SWITCHES FIRE ALARM INPUT PULL STATIONS SMOKE DETECTORS MATRIX OPERATIONS HEAT DETECTORS RE L E A S E M A G N E T I C A L L Y H E L D S M O K E D O O R S SYMBOL DESCRIPTION MOUNTING FIRE ALARM CONTROL PANEL WALL-TOP @ 66" FIRE ALARM POWER SUPPLY FIELD VERIFY REMOTE ANNUNCIATOR WALL-TOP @ 66" FIRE/SMOKE DAMPER BY OTHERS SMOKE DETECTOR CEILING DUCT SMOKE DETECTOR IN DUCT HEAT DETECTOR CEILING HORN / STROBE WALL 80"-96"STROBE WALL 80"-96" MANUAL PULL STATION WALL @ 48" WATER FLOW SWITCH BY OTHERS VALVE TAMPER SWITCH BY OTHERS MONITOR MODULE FIELD VERIFY CONTROL MODULE FIELD VERIFY MAGNETIC DOOR HOLDER FIELD VERIFY FIRE ALARM SYMBOL LEGEND HORN / STROBE CEILING STROBE CEILING TWSP TWISTED SHIELDED PAIR ABBREVIATION DESCRIPTION TWP TWISTED PAIR EOL END OF LINE RESISTOR AWG AMERICAN WIRE GAUGE EOLR END OF LINE RELAY FACP ANN FSD DD COMBINED SMOKE DETECTOR CEILINGCO P CM MM FAPS WP WEATHER PROOF R RESIDENTIAL (110V) LF LOW FREQUENCY FACP Battery Calculation PROJECT NAME: Required Standby Time:24 Hours Required Alarm Time:5 Minutes Regulated Load in STANDBY Device Type Number of Devices Current (Amps) Total Current (Amps) MAIN BOARD 1 X 0.07000 =0.07000 CLASS B ZONES TOTAL STANDBY LOAD 0.13000 Regulated Load in ALARM Device Type Number of Devices Current (Amps) Total Current (Amps) MAIN BOARD 1 X 0.23500 =0.23500 NAC-1 1 X 1.92400 =1.92400 TOTAL ALARM LOAD 4.16300 Battery Requirements Standby Load Required Standby Time in Hours Current (Amps)0.13000 X 24.00000 =3.12000 Alarm Load Required Alarm Time in Hours Current (Amps)4.16300 X 0.08333 =0.34692 Total Ampere Hours (before derating factor)3.46692 Derating Factor X 1.2 TOTAL AMPERE HOURS REQUIRED =4.16030 BATTERIES TO BE PROVIDED (2 - 12v)7 AH Notification Circuit Voltage Drop Calculation Project Name Circuit Number NAC-1 Wire Gauge Resistance Per 1000Nominal System Voltage 20.4 Volts Minimum Device Voltage 16 Volts 14 6.14 Distance from source to 1st device 8 14 6.14 Max Output Current 3.0 Amps Total Circuit Current 1.924 Amps Circuit is Within Limits Distance Device Current Previous Device Voltage at Device Drop from Source Percent Drop Device 1 0.140 20.31 0.09 0% 19.89 0.51 3% 19.72 0.68 3% 19.57 0.83 4% 19.43 0.97 5% 19.40 1.00 5% 19.32 1.08 5% END 19.27 1.13 6% Totals 1.924 163 NICET CERTIFIED Robert W. Ryan Lead Installer NICET IV Cert 108137 PROJECT MANAGER: Ritch Way Cell: (208) 520.2665 Office: (208) 524-4282 X 1.78400 =1.78400 CLASS B ZONES 1 4 X 0.00500 =0.02000 4 X 0.04000 =0.16000 SCALE: RISER DIAGRAM NONE1 120 VAC (DEDICATED CKT.) PFC - 4064 FACP #18/4 AWG ZONE-1 ZONE-2 ZONE-3 EOL P PULL STATION ENTRY EOL FACP TAMPER SWITCH CELLCOMM SU P E R V I S O R Y TR O U B L E AL A R M #18/4 AWG EOL ZONE-4 #18/4 AWG #18/4 AWG FLOW SWITCH EOL BATTERY BATTERY + - BA T T E R Y (INDICATING CKTS.) #14/2 AWG (STYLE Y) LF110 LF110 LF110 LF110 #14/2 AWG (STYLE Y) EOL WP75 NAC-1 NAC-2 LF110 LF110 LF110 LF110 LF110 LF110 LF110 LF110 LF110 LF110 LF110 LF110 EOL NAC-2 Device 2 Device 3 Device 4 Device 5 Device 6 Device 7 Device 8 Device 9 09/27/2022 7TH NORTH APARTMENTS 09/27/2022 7TH NORTH APARTMENTS 0.223 0.223 0.223 0.223 0.223 0.223 0.223 0.223 38 18 18 20 5 20 18 18 19.25 1.15 6% 19.25 1.15 6% Notification Circuit Voltage Drop Calculation Project Name Circuit Number NAC-2 Wire Gauge Resistance Per 1000Nominal System Voltage 20.4 Volts Minimum Device Voltage 16 Volts 14 6.14 Distance from source to 1st device 38 14 6.14 Max Output Current 3.0 Amps Total Circuit Current 1.784 Amps Circuit is Within Limits Distance Device Current Previous Device Voltage at Device Drop from Source Percent Drop Device 1 0.223 19.98 0.42 2% 19.81 0.59 3% 19.66 0.74 3% 19.53 0.87 4% 19.50 0.90 5% 19.42 0.98 5% 19.37 1.03 5% END 19.34 1.06 5% Totals 1.784 155 Device 2 Device 3 Device 4 Device 5 Device 6 Device 7 Device 8 09/27/2022 7TH NORTH APARTMENTS 0.223 0.223 0.223 0.223 0.223 0.223 0.223 18 18 20 5 20 18 19.34 1.06 5% 19.34 1.06 5% END 18 COMMUNICATOR 1 X 0.04000 =0.04000 COMMUNICATOR 1 X 0.06000 =0.06000 7T H N O R T H A P A R T M E N T S DA T E No . RE M A R K S RE V I S I O N S DATE REVISION CHECKED DRAWN 09/27/2022 7T H N O R T H & S T O N E B R I D G E S T Al a r m PE A K A L A R M 24 0 S . H O L M E S , I D A H O F A L L S I D 8 3 4 0 1 Ph . ( 2 0 8 ) 5 2 4 - 4 2 8 2 E X T 0 RW STAMP NICET R RE X B U R G , I D 8 3 4 4 0 ROS FA-02 RI S E R D I A G R A M & B A T T E R Y C A L C S 0