Conventional Fire Alarm Control Panel
8830139 - REV E • 9/19 page 1 OF 5
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
Features
• 6 programmable Initiating Device Circuits
• System is expandable to 192 input circuits using the IDC-6
expansion module
• 5.0 amp power Supply
• 4 Notification Circuit rated at 3.0 Amps
• Strobe Synchronization for gentex, aMSeCO, System Sensor
and Cooper/Wheelock
• One programmable auxiliary output rated at 1.0 a
• 4 x 20 LCD display with system LeDs for clear system status
• P-Link RS-485 bus supports 31 system accessories
• Built-in ethernet Connection with listed Ip Communicator
• Ability to E-mail system status, reports and system configuration
• Service Reminder e-mails
Dimensions 18 1/2” H x 14 1/4 W x 4 3/4” D
enclosure 18 gauge cold rolled steel with removable locked
door with Lexan viewing window
aC Mains 5.0 amp @ 120 VaC 60 Hz
2.0 amp @ 240 VaC 50 Hz
Battery 70 ma Standby
235 mA Alarm
Temperature
and Humidity
Range
32° to 120° (0°C to 49°C) with a maximum
humidity of 93% non-condensing.
Standards NFpa 70, 72
Description
The pFC-4064 Conventional Fire panel is a compact, expandable panel
designed to monitor all facets of a fire alarm system and communicate
the status to a monitoring station. The pFC-4064 panel is a listed and
approved microprocessor based conventional fire panel and complies
with UL-864, NFpa-70, and NFpa-72. The panel is provided with
six (6) inputs and four (4) 24VDC, 3.0 Amp Notification Appliance
Circuits (NAC) with strobe synchronization. The 5.0 Amp power
supply provides ample power to meet any jurisdictions requirements
and will charge up to two (2) 55 amp/hour batteries. In addition, the
panel has the potter p-Link for connection to system accessories.
The panel also has a 1.0 amp auxiliary power output for controlling
ancillary fire alarm functions.
The control panel is in a metal cabinet with a key lock and lexan
window for viewing the system status. The printed circuit assembly is
mounted for quick removal and installation to allow the cabinet to be
installed with minimal effort. The cabinet houses up to two (2) 7 AH or
two (2) 12 AH batteries.
The display is an eighty (80) character LCD with system status LEDs.
The system status is clearly displayed and the panel includes a history
buffer for past events. The key pad allows navigation into the system
menu, limited programming and system control. The condition and
events on the panel are clearly displayed to allow the user and installer
to determine the system status.
The panel will support up to thirty-one (31) system accessories.
Technical Specifications
LISTED
8830139 - REV E • 9/19 page 2 OF 5
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
PFC-4064
Conventional Fire Alarm Control Panel
2-Wire Smoke Detector Compatibility
Detector Model Identifier Base Model Identifier
SYSTEM SENSOR (Brk) (Max. No. Of Detectors Per Zone Is 20)
1400 a N/a N/a
2400 a N/a N/a
2400TH a N/a N/a
2W-B a N/a N/a
2WT-B a N/a N/a
DETECTION SYSTEM (Max. No. Of Detectors Per Zone Is 25)
DS250 a MB2W/MB2WL a
DS250TH a MB2W/MB2WL a
ESL (Max. No. Of Detectors Per Zone Is 25)
611U S10 601U S00
611UD S10 601U S00
611UT S10 601U S00
612U S10 601U S00
612UD S10 601U S00
613U5 S10 601U S00
611UD S10 609U10 S00
612UD S10 609U10 S00
425C S10 N/a N/a
425CT S10 N/a N/a
HOCHIKI (Max. No. Of Detectors Per Zone Is 25)
SLR-24 HD-3 HSC-221R HB-71
HSB-221 HB-54
HSB-221N HB-54
NS6-221
NS4-221
NS6-220 HB-3
SLR-24H HD-3 HSC-221R HB-71
HSB-221 HB-54
HSB-221N HB-54
NS6-221
NS4-221
SIJ-24 HD-3 HSC-221R HB-71
HSB-221 HB-54
HSB-221N HB-54
NS6-221
NS4-221
8830139 - REV E • 9/19 PAgE 3 OF 5
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
PFC-4064
Conventional Fire Alarm Control Panel
Detector Model Identifier Base Model Identifier
FENWAL (Max. No. Of Detectors Per Zone Is 25)
CpD-7051 I51Fe1 2-WIRe Fe51a
pSD-7155 p55Fe1 2WRLT Fe52a
pSD-7156 p56Fe1 2WRB Fe55a
all of the above Fenwal detectors and bases can be used in any combination.
Retrofit Base Adaptor 70-501000-003, Identifier MAFE1 (for series 70-201000 Bases, Models -001, -002, -003, and -005).
Duct Housing with Detector Base DH-51, Identifier DH22FE5 (for CPD-7051 and PSD-7155 detectors only).
POTTER (Max. No. Of Detectors Per Zone Is 25)
CpS-24 HD-3 (HOCHIKI)SB-46 HB-4 (HOCHIKI)
SB-93 HB-3 (HOCHIKI)
pS-24H HD-3 (HOCHIKI)SB-46 HB-71 (HOCHIKI)
HB-54 (HOCHIKI)
IS-24 HD-3 (HOCHIKI)SB-46 HB-71 (HOCHIKI)
HB-54 (HOCHIKI)
NOTE: If using a mix of System Sensor and other smoke detectors, a maximum of 20 detectors shall be permitted.
8830139 - REV E • 9/19 page 4 OF 5
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
PFC-4064
Conventional Fire Alarm Control Panel
User Interface
Ethernet/I.P. Connection
P-Link
The pFC-4064 is shipped standard with an ethernet connection.
This connection is the programming port and may be connected
to a building Wide Area Network (WAN) or Local Area Network
(LAN). Once connected to the Internet, the panel may be selectively
programmed to e-mail alarm conditions, trouble conditions,
supervisory conditions, test, event History and detector status. an
e-mail may be sent to the panel and the panel will e-mail the event
history, detector status, configuration file or server status to an
authorized e-mail account. In addition, reminders may be set to send
an e-mail for service, testing or other conditions.
In addition, the ethernet connection is UL listed as an Ip
communicator. The Ip communicator is listed to report to the UL
listed Sur-gard III Ip receiver. The Ip communicator replaces the
traditional less reliable alarm communicator transmitter that utilized
telephone lines. The Ip communicator is an active method of
connection and communication to the monitoring station.
The pFC-4064 has a proprietary communication protocol that
communicates through a RS-485 connection to field devices. Up
to 31 devices may be connected to a single P-Link connection. The
p-Link includes the communication terminals and regulated 24 VDC
connection for the field devices. The field devices may be any of the
following:
IDC-6 – Initiating device circuit expander, provides an additional six
(6) inputs.
RA-6075R – 2 x 16 LCD annunciator with a key pad in a locked
metal enclosure.
RA-6500R(F) – 4 x 40 LCD annunciator with a key pad in a locked
metal enclosure. Flush mount version available.
LED-16(F) – 16 LeD annunciator with common indicators in a
locked metal enclosure. Flush mount version available.
PSN-1000(E) – 10 amp, remote intelligent power supply with 6
NaCs, 2 Inputs and a p-Link repeater.
CA-4064 – Class a convertor that converts the NaCs and p-Link
connection.
UD-2000 – UL listed, Dual line telephone alarm communicator.
DRV-50 – LeD driver expander, used to connect up to 50 LeDs in a
graphic display .
FCB-1000 – Fire communication bridge, provides remote mounting
of the ethernet connection.
FIB-1000 – Fiber interface module, used to extend p-Link to multi-
mode fiber (2 required).
RLY-5 – Relay module, provides 5 form C relay contacts rated at 3.0
amps 24VDC/125aC.
SPG-1000 – Serial parallel gateway, allows for the connection to a
serial or parallel printer.
The fire alarm control panel has a 4 x 20 LCD display to provide
information to the system status. The keypad has navigation keys
to allow manipulation of the Menu on board the panel. The panel is
shipped standard with the following LeDs:
• aC power - green
• alarm - Red
• earth Fault - amber
• Supervisory - amber
• Silenced - amber
• Trouble - amber
The common buttons include a Silence, Reset, acknowledge, and
Drill. all of the buttons are accessible once the locked door is
opened.
The FIB-1000, FCB-1000 and the SPG-1000 may be installed in the
stacker bracket or ordered with the optional rack mount enclosure.
MC-1000 Multi-Connect allows up to sixty-three panels to share a
single reporting technology.
AE-2 – Two card expansion cabinet.
AE-8 – eight card expansion cabinet.
AE-14 – Fourteen card expansion cabinet.
8830139 - REV E • 9/19 page 5 OF 5
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
PFC-4064
Conventional Fire Alarm Control Panel
BOTTOM
LEFT SIDE
TOP
18
.
6
0
"
18
.
1
0
"
DEPTH
4.63"
3.95"
14.48"
14.78"
RIGHT SIDE
Dimensions
Ordering Information
Model Description Stock No.
pFC-4064 Fire alarm Control panel 3992360
Replacement Board 3992363