Corrections in the following table need to be applied before a permit can be issued
Review Report
Approved
# 22-00472
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
Pg 1 Stamp Larry Beesley : Building Open 1 Approved - Building Inspector
Solar Panels
Approval of plans does not constitute approval of variance from code
Powered by TCPDF (www.tcpdf.org)
RE:CERTIFICATION LETTER
Project Address: JACK ZOLLINGER RESIDENCE
152 N CENTER
REXBURG, ID 83440
Design Criteria:
- Applicable Codes = 2018 IEBC/IBC, 2018 IRC, ASCE 7-16 and 2018 NDS
- Risk Category = II
- Wind Speed = 115 mph, Exposure Category B, Partially/Fully Enclosed Method
- Ground Snow Load = 50 psf
- Roof 1: 2 x 6 @ 24" OC, Roof DL = 7 psf, Roof LL/SL = 39 psf (Non-PV), Roof LL/SL = 33.4 psf (PV)
To Whom It May Concern,
Sincerely,
August 11, 2022
Based on this evaluation, I certify that the alteration to the existing structure by installation of the PV system meets the prescriptive
compliance requirements of the applicable existing building and/or new building provisions adopted/referenced above.
Additionally, the PV module assembly including attachment hardware has been reviewed to be in accordance with the manufacturer’s
specifications and to meet and/or exceed the requirements set forth by the referenced codes.
A structural evaluation of loading was conducted for the above address based on the design criteria listed above.
Existing roof structural framing has been reviewed for additional loading due to installation of PV Solar System on the roof. The structural
review applies to the sections of roof that is directly supporting the solar PV system.
Barun Corp | Design and Engineering | 610.202.4506 | chrisk@barun-corp.com | www.barun-corp.com 1/4
By Yuri at 12:21:09 AM, 8/12/2022
Yurianto
Yurianto
Digitally signed by
Yurianto Yurianto
DN: cn=Yurianto Yurianto
c=US o=Unaffiliated
ou=A01410D00000176B0
7CBF250000A7A2
Reason: I am the author
of this document
Location:
Date: 2022-08-12
00:21-05:00
Roof 1 18°OK IEBC IMPACT CHECK
MOUNTING PLANE
Limits of Scope of Work and Liability:
The existing structure has been reviewed based on the assumption that it has been originally designed and constructed per
appropriate codes.The structural analysis of the subject property is based on the provided site survey data.The calculations
produced for this structure's assessment are only for the roof framing supporting the proposed PV installation referenced in the
stamped planset and were made according to generally recognized structural analysis standards and procedures.All PV modules,
racking and attachment components shall be designed and installed per manufacturer’s approved guidelines and specifications.
These plans are not stamped for water leakage or existing damage to the structural component that was not accessed during the
site survey.Prior to commencement of work,the PV system installer should verify that the existing roof and connections are in
suitable condition and inspect framing noted on the certification letter and inform the Engineer of Record of any discrepancies
prior to installation.The installer should also check for any damages such as water damage,cracked framing,etc.and inform the
Engineer of Record of existing deficiencies which are unknown and/or were not observable during the time of survey and have
not been included in this scope of work.Any change in the scope of the work shall not be accepted unless such change,addition,
or deletion is approved in advance and in writing by the Engineer of Record.
STANDOFF HARDWARE EVALUATION FOR WIND UPLIFT
UPLIFT DCR
RESULTS SUMMARYBARUN CORP
JACK ZOLLINGER RESIDENCE, 152 N CENTER, REXBURG, ID 83440
RESULTMOUNTING PLANE ROOF PITCH
(deg.)GOVERNING ANALYSIS
MOUNTING PLANE STRUCTURAL EVALUATION
Barun Corp | Design and Engineering | 610.202.4506 | chrisk@barun-corp.com | www.barun-corp.com 2/4
PV Module Weight =2.50 psf
Hardware Assembly Weight =0.50 psf
PV-DL =3.00 psf
Existing Roofing Material Weight 1 Layer(s)=2.50 psf
Underlayment Weight =0.50 psf
Plywood/OSB Sheathing Weight =1.50 psf
Framing Weight =1.15 psf
No Vaulted Ceiling =0.00 psf
Miscellaneous =1.50 psf
Total Roof Dead Load R-DL =7.10 psf
Roof Live Load Lo =20.00 psf
Member Tributary Area At < 200 ft2
Roof 1 Pitch 18° or 4/12
Tributary Area Reduction Factor R1 =1.00
Roof Slope Reduction Factor R2 =1.00
Reduced Roof Live Load, Lr = Lo (R1) (R2)Lr =20.00 psf
Ground Snow Load pg =50.00 psf
Effective Roof Slope 18°
Snow Importance Factor Is =1.00
Snow Exposure Factor Ce =1.00
Snow Thermal Factor Ct =1.10
Minimum Flat Roof Snow Load pf-min =20.00 psf
Flat Roof Snow Load pf =38.50 psf
Roof Slope Factor Cs-roof =1.00
Sloped Roof Snow Load on Roof ps-roof =38.50 psf
Roof Slope Factor Cs-pv =0.87
Sloped Roof Snow Load on PV Panel ps-pv =33.40 psf
Total PV System Dead Load
2 x 6 @ 24 in. O.C.
Composite Shingle Roof
BARUN CORP Roof 1
LOAD CALCULATION
JACK ZOLLINGER RESIDENCE, 152 N CENTER, REXBURG, ID 83440
PV SYSTEM DEAD LOAD (PV-DL)
ROOF DEAD LOAD (R-DL)
SLOPED ROOF SNOW LOAD ON PV PANEL (Unobstructed Slippery Surfaces)
REDUCED ROOF LIVE LOAD (Lr)
SNOW LOAD
SLOPED ROOF SNOW LOAD ON ROOF (Non-Slippery Surfaces)
Barun Corp | Design and Engineering | 610.202.4506 | chrisk@barun-corp.com | www.barun-corp.com 3/4
EXISTING
7.10 psf
20.00 psf
38.50 psf
EXISTING
21.68 psf
39.65 psf
39.65 psf
-4.61%OK
2018
Roof Snow Load (SL) =33.40
(DL + SL)/Cd =37.83
Maximum Gravity Load =37.83
BARUN CORP IEBC IMPACT CHECK
Roof 1
JACK ZOLLINGER RESIDENCE, 152 N CENTER, REXBURG, ID 83440
Roof Live Load (Lr) =0.00
WITH PV PANEL
WITH PV PANEL
Roof Dead Load (DL) =10.10
The requirements of section 806.2 of 2018 IEBC are met and the structure is permitted to remain unaltered.
IEBC Provision :
Load Increase (%) =
(DL + Lr)/Cd =11.22
Barun Corp | Design and Engineering | 610.202.4506 | chrisk@barun-corp.com | www.barun-corp.com 4/4