Corrections in the following table need to be applied before a permit can be issued
Review Report
Revisions Required
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
1 Free text Cody Jones : Building Open 1 Need new site plan showing building separation or detail of a
fire wall.
1 Callout Stan Crittenden : Fire Open 1 Maximum distance from the fire hydrant is 500 ft..
Would need a second fire hydrant installed.
1 Free text Stan Crittenden : Fire Open 1 New site plan needs to show
dimensions of driveways, and turning radius. 30' min. inside
turning radius and 45' min. outside turn radius.
1 Free text Kyle Baldwin : P&Z Open 1 Need updated site plan showing intended location for current
proposed building with dimensions to property lines and
existing buildings.
# 22-00065
New Commercial Building
Report Date: 02.10.2022
Approval of plans does not constitute approval of variance from code
Page 1 of 1
Powered by TCPDF (www.tcpdf.org)
Need new site plan
showing building
separation or detail of a
fire wall.
Maximum distance from
the fire hydrant is 500 ft..
Would need a second
fire hydrant installed.
New site plan needs to show
dimensions of driveways, and
turning radius. 30' min. inside
turning radius and 45' min.
outside turn radius.
Need updated site plan showing
intended location for current
proposed building with dimensions
to property lines and existing
buildings.