Corrections in the following table need to be applied before a permit can be issued
Review Report
Approved
# 21-00715
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
Pg 1 Callout Alex Owens : Electrical Open 1 Wire size not specified. Must be in accordance with NEC 690.
Wire type must be wet location rated (example: THWN). Must
fasten conduit according to NEC 356 or 350.
Pg 1 Callout Alex Owens : Electrical Open 1 If connecting on line side of service, please ensure grounding
electrode is bonded to neutral. If on load side, please ensure
buss or wire is in accordance with 705.12B
Pg 1 Free text Alex Owens : Electrical Open 1 All wiring must be in accordance with 2017 NEC requirements
Pg 1 Free text Alex Owens : Electrical Open 1 Please see attached label schedule as example of what is
needed.
Pg 1 Stamp Alex Owens : Electrical Open 1 Approved - Electrical Inspector
Solar Panels
Approval of plans does not constitute approval of variance from code
Powered by TCPDF (www.tcpdf.org)
3 feet
Square D Fronius APsmart REC
D221NRB Primo 3.8-1 208/240 Transmitter-PLC REC365AA
3R NEMA Enclosure 3.8kW AC RSD-S-PLC 365 WDC ea
30 Amps 240 VAC QTY: 1 QTY: 1 QTY: 10
Engraved Label:
Parallel Generation
on Site
Engraved Label:
Manual Disconnect
for Parallel
Generation
RSD-S-PLC
QTY: 10
One-line Drawing:336 SALEM AVENUE, REXBURG, ID, 83440 Grid-Tied PV System
Utility Meter
Main Service Panel
(Connected to Utility
Meter)
Lockable AC
Disconnect Switch
Grid Tied Inverter
With Built-in DC
Disconnect
Solar Array (1 String)
w/ Rapid Shutdown
Receivers
Rapid Shutdown
System Transmitter
Wire size not specified. Must
be in accordance with NEC
690. Wire type must be wet
location rated (example:
THWN). Must fasten conduit
according to NEC 356 or
350.
If connecting on line side of
service, please ensure
grounding electrode is
bonded to neutral. If on load
side, please ensure buss or
wire is in accordance with
705.12B
All wiring must be in
accordance with 2017 NEC
requirements
Please see attached label schedule
as example of what is needed.