Loading...
HomeMy WebLinkAboutAPPROVED ELECTRICAL LAYOUT - 21-00715 - 336 Salem Ave - Solar PanelsAuthor Name Author Email Author Phone No.: Alex Owens Alex.Owens@rexburg.org 208-372-2330 Description : 336 Salem Ave - Solar Panels Address : 336 Salem Ave Record Type : Solar Panels Document Filename : MartinOneLineDrawing.pdf Comment Author Contact Information: Corrections in the following table need to be applied before a permit can be issued Review Report Approved # 21-00715 Page Reference Annotation Type Author : Department Status Page Review Comments Applicant Response Comments Pg 1 Callout Alex Owens : Electrical Open 1 Wire size not specified. Must be in accordance with NEC 690. Wire type must be wet location rated (example: THWN). Must fasten conduit according to NEC 356 or 350. Pg 1 Callout Alex Owens : Electrical Open 1 If connecting on line side of service, please ensure grounding electrode is bonded to neutral. If on load side, please ensure buss or wire is in accordance with 705.12B Pg 1 Free text Alex Owens : Electrical Open 1 All wiring must be in accordance with 2017 NEC requirements Pg 1 Free text Alex Owens : Electrical Open 1 Please see attached label schedule as example of what is needed. Pg 1 Stamp Alex Owens : Electrical Open 1 Approved - Electrical Inspector Solar Panels Approval of plans does not constitute approval of variance from code Powered by TCPDF (www.tcpdf.org) 3 feet Square D Fronius APsmart REC D221NRB Primo 3.8-1 208/240 Transmitter-PLC REC365AA 3R NEMA Enclosure 3.8kW AC RSD-S-PLC 365 WDC ea 30 Amps 240 VAC QTY: 1 QTY: 1 QTY: 10 Engraved Label: Parallel Generation on Site Engraved Label: Manual Disconnect for Parallel Generation RSD-S-PLC QTY: 10 One-line Drawing:336 SALEM AVENUE, REXBURG, ID, 83440 Grid-Tied PV System Utility Meter Main Service Panel (Connected to Utility Meter) Lockable AC Disconnect Switch Grid Tied Inverter With Built-in DC Disconnect Solar Array (1 String) w/ Rapid Shutdown Receivers Rapid Shutdown System Transmitter Wire size not specified. Must be in accordance with NEC 690. Wire type must be wet location rated (example: THWN). Must fasten conduit according to NEC 356 or 350. If connecting on line side of service, please ensure grounding electrode is bonded to neutral. If on load side, please ensure buss or wire is in accordance with 705.12B All wiring must be in accordance with 2017 NEC requirements Please see attached label schedule as example of what is needed.