In Place Density of Soils ASTM D2922 & D3017
Project Number:
22-204B
Contractor:
Edstrom Construction
Project Name:
Evo Automation
Instrument ID
76561
Daily Standardization:
Client:
Edstrom Construction
Date:
02/10/2022
MS:
772
DS:
2802
Time Start:
10:00 AM
Time End:
12:30 PM
Details
Test
#:
Location:Elevation: Depth:Wet:Dry:% M:Proctor #:%
Proctor:
Pass Fail
1 Southeast corner of
building pad
Approximately
2' above
water table
10 133.5 129.7 2.9 132.6
Material
Type
Native
Material
98
2 Southwest corner of
building pad
Approximately
2' above
water table
10 130.7 126.5 3.4 132.6
Material
Type
Native
Material
95
3 South wall of
building pad
Approximately
2' above
water table
10 134.1 130.4 2.8 132.6
Material
Type
Native
Material
98
4 South wall of
building pad
Approximately
2' above
water table
10 133.4 128.8 3.6 132.6
Material
Type
Native
Material
97
5 West wall of building
pad
Approximately
2' above
water table
10 130.1 125.9 3.3 132.6
Material
Type
Native
Material
95
File Name:
22-204BD02102022BB
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
b8bc23e67404a7c5-1644513181409 2
Observations/Remarks:
Checking densities on native materials in building pad
Ambient temperature was 24 degrees
Tested By:
Ben E. Ball
Signature:
Reviewed By:
E. Vail
Signature:
Date:
02/15/2022
Inspection Images:
File Name:
22-204BD02102022BB
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
b8bc23e67404a7c5-1644513181409 3