HEAT LOAD - 21-00789 - Rocky Mountain Power - Mechanic Shop
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Aug-23 09:24:43 Right-Suite® Universal 2022 22.0.04 RSU20783 Page 1 ...lations\T. Webb Const- R.M -Mechanical Shop.rup Calc = MJ8 Front Door faces: S T. Webb Const-Mechanical...Job:Load Short Form 08-20-22Date: Entire House C.MBy: Mechanical ShopPlan:Freedom Heating, Inc P.O Box 51966, Idaho Falls, Id 83405 Phone: 208-589-2396 Fax: 208-522-1320 Email: freedomheatinginc@yahoo.com Project Information T. Webb Const-Mechanical ShopFor: Design Information InfiltrationClgHtg SimplifiedMethod89-6Outside db (°F) Semi-tightConstruction quality7570Inside db (°F) 0Fireplaces1476Design TD (°F) H-Daily range 5030Inside humidity (%) -3135Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Day & Night Make Day & Night Trade Day & Night Trade 13 SEER N SERIES R410A AC Model Cond N4A318AKF10 AHRI ref Coil FXM4X2400AL AHRI ref 0 Efficiency 100 EFF Efficiency 12.0 EER, 14 SEER Heating input kW10.0 Sensible cooling Btuh16356 Heating output Btuh34121 Latent cooling Btuh0 Temperature rise °F47 Total cooling Btuh16356 Actual air flow cfm780 Actual air flow cfm634 Air flow factor cfm/Btuh0.036 Air flow factor cfm/Btuh0.156 Static pressure in H2O0.60 Static pressure in H2O0.60 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Parts Storage 177 2138 166 76 26 Unisex Room 114 759 59 27 9 Storage 587 9186 1199 326 187 Mezzanine 834 8431 1395 300 217 Office 192 1439 1253 51 195 Entire House d 1904 21953 4072 780 634 Other equip loads 4008 738 Equip. @ 0.94 RSM 4522 Latent cooling 0 TOTALS 1904 25962 4522 780 634 2022-Aug-23 09:24:43 Right-Suite® Universal 2022 22.0.04 RSU20783 Page 1 ...lations\T. Webb Const- R.M -Mechanical Shop.rup Calc = MJ8 Front Door faces: S T. Webb Const-Mechanical...Job:Building Analysis 08-20-22Date: Entire House C.MBy: Mechanical ShopPlan:Freedom Heating, Inc P.O Box 51966, Idaho Falls, Id 83405 Phone: 208-589-2396 Fax: 208-522-1320 Email: freedomheatinginc@yahoo.com Project Information T. Webb Const-Mechanical ShopFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-31.535.2Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F) SimplifiedMethod)H(34-Daily range (°F) Semi-tightConstruction quality60-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Other Doors Ceilings Floors Infiltration Ventilation % of loadBtuhBtuh/ft²Component 42.2109484.9Walls 0.820522.8Glazing 7.5193629.6Doors 6.316271.5Ceilings 8.822742.12.1Floors 19.149632.2Infiltration 00Ducts 00Piping 00Humidification 15.44008Ventilation 0Adjustments 100.025962Total Cooling Walls Glazing Doors Ceilings Infiltration Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 21.910520.5Walls 2.09810.8Glazing 9.84717.2Doors 18.78990.8Ceilings 000Floors 10.24920.2Infiltration 00Ducts 15.3738Ventilation 22.01060Internal gains 00Blower 0Adjustments 100.04810Total Latent Cooling Load = 0 Btuh Overall U-value = 0.050 Btuh/ft²-°F WARNING: window to floor area ratio = 0.5% - less than 5%. 2022-Aug-23 09:24:43 Right-Suite® Universal 2022 22.0.04 RSU20783 Page 1 ...lations\T. Webb Const- R.M -Mechanical Shop.rup Calc = MJ8 Front Door faces: S T. Webb Const-Mechanical...Job:Component Constructions 08-20-22Date: Entire House C.MBy: Mechanical ShopPlan:Freedom Heating, Inc P.O Box 51966, Idaho Falls, Id 83405 Phone: 208-589-2396 Fax: 208-522-1320 Email: freedomheatinginc@yahoo.com Project Information T. Webb Const-Mechanical ShopFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-31.535.2Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F) SimplifiedMethod)H(34-Daily range (°F) Semi-tightConstruction quality60-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Frm wall, vnl ext, 3/8" wood shth, r-22 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 24" o.c. stud 3660.4738114.9422.00.065772n 1620.4716894.9422.00.065342e 3500.4736454.9422.00.065738s 1730.4718024.9422.00.065365w 10520.47109484.9422.00.0652216all Partitions (none) Windows 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; foreground = new concrete (0.32); 1 ft overhang (3 ft window ht, 1 ft sep.); 6.67 ft head ht 9810.820522.800.3009n Doors 11D0: Door, wd sc type 1647.2167429.600.39023e 3077.22126229.600.39043s 4717.22193629.600.39065all Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 8990.8416271.5250.00.0201070 Floors 22B-10vpl: Bg floor, light dry soil, on grade depth, r-10 edge ins, vinyl flr fnsh 00227416.010.00.210143 2022-Aug-23 09:24:43 Right-Suite® Universal 2022 22.0.04 RSU20783 Page 1 ...lations\T. Webb Const- R.M -Mechanical Shop.rup Calc = MJ8 Front Door faces: S T. Webb Const-Mechanical...Job:AED Assessment 08-20-22Date: Entire House C.MBy: Mechanical ShopPlan:Freedom Heating, Inc P.O Box 51966, Idaho Falls, Id 83405 Phone: 208-589-2396 Fax: 208-522-1320 Email: freedomheatinginc@yahoo.com Project Information T. Webb Const-Mechanical ShopFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-31.535.2Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F) )H(34-Daily range (°F) 60-Wet bulb (°F) 7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limitGlazing load (Btuh)Hour of Day 0 20 40 60 80 100 120 140 160 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 27.0%. House has adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 0 Btuh Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Aug-23 09:24:43 Right-Suite® Universal 2022 22.0.04 RSU20783 Page 1 ...lations\T. Webb Const- R.M -Mechanical Shop.rup Calc = MJ8 Front Door faces: S T. Webb Const-Mechanical ShopJob:Right-J8® Form J1 08-20-22Date:Entire House C.MBy: Mechanical ShopPlan:Freedom Heating, Inc P.O Box 51966, Idaho Falls, Id 83405 Phone: 208-589-2396 Fax: 208-522-1320 Email: freedomheatinginc@yahoo.com 1 Name of Room Entire House Parts Storage 2 Running Feet of Exposed Wall 268.5 ft 26.8 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.6 ft²3518.7ft 9.0 ft²457.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)ft²1904.4 14.8 x 12.0 ft ft²177.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²2182.4°0 ft²236.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall Frm wall, vnl ext, 3 nFrm wall, vnl ext, 3 n 4.944.94 0.470.47 781 3811 366 133 656 63 .GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 22.8022.80 10.8510.85 9 205 98 0 0 0 .WallWall Frm wall, vnl ext, 3 eFrm wall, vnl ext, 3 e 4.944.94 0.470.47 365 1689 162 108 534 51 .DoorDoor 11D011D0 ee 29.6429.64 7.217.21 23 674 164 0 0 0 11 WallWall Frm wall, vnl ext, 3 sFrm wall, vnl ext, 3 s 4.944.94 0.470.47 781 3645 350 0 0 0 DoorDoor 11D011D0 ss 29.6429.64 7.217.21 43 1262 307 0 0 0 WallWall Frm wall, vnl ext, 3 wFrm wall, vnl ext, 3 w 4.944.94 0.470.47 365 1802 173 0 0 0 CeilCeil 16B-50ad16B-50ad --1.521.52 0.840.84 1070 1627 899 0 0 0 FlorFlor 22B-10vpl22B-10vpl --15.9615.96 0.000.00 1070 2274 0 177 427 0 Infiltration Heating Load (Btuh)0.260.26 4963 522 Effect WAR WAR 12 Sensible Load (Btuh)ACH 1.00 492 0.11 52 0.140.14 Latent Load (Btuh)-684 Internal a Occupants at 230 and 200 Btuh 2 460 400 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 600 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 21953 4072 -284 2138 166 Duct EHLF & ESGF 00 00 0 0 0 0 15 Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 5757 E CfmE Cfm 5757 4008 738 -1026 17 Winter Humidification Load Gal/Day 00 0 18 Piping Load 0 19 Blower Heat 0 20 AED Excursion & Latent Moisture Migration Load 0 0 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 25962 4810 0 2138 166 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Aug-23 09:24:43 Right-Suite® Universal 2022 22.0.04 RSU20783 Page 2 ...lations\T. Webb Const- R.M -Mechanical Shop.rup Calc = MJ8 Front Door faces: S T. Webb Const-Mechanical ShopJob:Right-J8® Form J1 08-20-22Date:Entire House C.MBy: Mechanical ShopPlan:Freedom Heating, Inc P.O Box 51966, Idaho Falls, Id 83405 Phone: 208-589-2396 Fax: 208-522-1320 Email: freedomheatinginc@yahoo.com 1 Name of Room Unisex Room Storage 2 Running Feet of Exposed Wall 9.5 ft 90.3 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²365.6ft 9.0 ft²1206.1ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)9.5 x 12.0 ft ft²114.0 1.0 x 587.4 ft ft²587.4 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²152.0°0 ft²704.4° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall Frm wall, vnl ext, 3 nFrm wall, vnl ext, 3 n 4.944.94 0.470.47 86 422 41 74 367 35 .GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 22.8022.80 10.8510.85 0 0 0 0 0 0 .WallWall Frm wall, vnl ext, 3 eFrm wall, vnl ext, 3 e 4.944.94 0.470.47 0 0 0 97 366 35 .DoorDoor 11D011D0 ee 29.6429.64 7.217.21 0 0 0 23 674 164 11 WallWall Frm wall, vnl ext, 3 sFrm wall, vnl ext, 3 s 4.944.94 0.470.47 0 0 0 437 1946 187 DoorDoor 11D011D0 ss 29.6429.64 7.217.21 0 0 0 43 1262 307 WallWall Frm wall, vnl ext, 3 wFrm wall, vnl ext, 3 w 4.944.94 0.470.47 0 0 0 205 1011 97 CeilCeil 16B-50ad16B-50ad --1.521.52 0.840.84 0 0 0 236 359 199 FlorFlor 22B-10vpl22B-10vpl --15.9615.96 0.000.00 114 152 0 587 1440 0 Infiltration Heating Load (Btuh)0.260.26 185 1760 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0.04 18 0.35 175 0.140.14 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 759 59 9186 1199 Duct EHLF & ESGF 00 00 0 0 0 0 15 Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 5757 E CfmE Cfm 5757 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 0 0 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 759 59 9186 1199 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Aug-23 09:24:43 Right-Suite® Universal 2022 22.0.04 RSU20783 Page 3 ...lations\T. Webb Const- R.M -Mechanical Shop.rup Calc = MJ8 Front Door faces: S T. Webb Const-Mechanical ShopJob:Right-J8® Form J1 08-20-22Date:Entire House C.MBy: Mechanical ShopPlan:Freedom Heating, Inc P.O Box 51966, Idaho Falls, Id 83405 Phone: 208-589-2396 Fax: 208-522-1320 Email: freedomheatinginc@yahoo.com 1 Name of Room Mezzanine Office 2 Running Feet of Exposed Wall 126.0 ft 16.0 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 ft²1008.0ft 9.0 ft²473.6ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)1.0 x 834.0 ft ft²834.0 16.0 x 12.0 ft ft²192.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²834.0°0 ft²256.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall Frm wall, vnl ext, 3 nFrm wall, vnl ext, 3 n 4.944.94 0.470.47 344 1699 163 144 667 64 .GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 22.8022.80 10.8510.85 0 0 0 9 205 98 .WallWall Frm wall, vnl ext, 3 eFrm wall, vnl ext, 3 e 4.944.94 0.470.47 160 790 76 0 0 0 .DoorDoor 11D011D0 ee 29.6429.64 7.217.21 0 0 0 0 0 0 11 WallWall Frm wall, vnl ext, 3 sFrm wall, vnl ext, 3 s 4.944.94 0.470.47 344 1699 163 0 0 0 DoorDoor 11D011D0 ss 29.6429.64 7.217.21 0 0 0 0 0 0 WallWall Frm wall, vnl ext, 3 wFrm wall, vnl ext, 3 w 4.944.94 0.470.47 160 790 76 0 0 0 CeilCeil 16B-50ad16B-50ad --1.521.52 0.840.84 834 1268 701 0 0 0 FlorFlor 22B-10vpl22B-10vpl --15.9615.96 0.000.00 0 0 0 192 255 0 Infiltration Heating Load (Btuh)0.260.26 2184 312 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0.44 217 0.06 31 0.140.14 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 2 460 400 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 600 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 8431 1395 1439 1253 Duct EHLF & ESGF 00 00 0 0 0 0 15 Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 5757 E CfmE Cfm 5757 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 0 0 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 8431 1395 1439 1253 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Aug-23 09:24:44 Right-Suite® Universal 2022 22.0.04 RSU20783 Page 1 ...lations\T. Webb Const- R.M -Mechanical Shop.rup Calc = MJ8 Front Door faces: S T. Webb Const-Mechanical...Job:J1 Form - Worksheet A 08-20-22Date: Entire House C.MBy: Mechanical ShopPlan:Freedom Heating, Inc P.O Box 51966, Idaho Falls, Id 83405 Phone: 208-589-2396 Fax: 208-522-1320 Email: freedomheatinginc@yahoo.com Supporting Detail Project Name:08-20-22T. Webb Const- R.M -Mechanical Shop Date: Address: Phone:T. Webb Const-Mechanical ShopJob ID: Worksheet A Location and Design Conditions Weather Location: Idaho Falls, ID, US 444741 Latitude =Elevation = Indoor Conditions, Heating: 70 °FDB =%50°F75%30 RH =DB =Indoor Conditions, Cooling:RH = Table 1 Conditions 99% DB = -6 °F Hgr/lb-31°F89 Daily Range =Grains Difference =1% DB = Design Temperature Differences °F14°F76 CTD =HTD = Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Aug-23 09:24:44 Right-Suite® Universal 2022 22.0.04 RSU20783 Page 1 ...lations\T. Webb Const- R.M -Mechanical Shop.rup Calc = MJ8 Front Door faces: S T. Webb Const-Mechanical...Job:Project Summary 08-20-22Date:Entire House C.MBy: Mechanical ShopPlan:Freedom Heating, Inc P.O Box 51966, Idaho Falls, Id 83405 Phone: 208-589-2396 Fax: 208-522-1320 Email: freedomheatinginc@yahoo.com Project Information T. Webb Const-Mechanical ShopFor: INFORMATION CONTAIN WITHIN THE REPORT IS PER THE RESCHECK COMPLIANCE CERTIFICATE. IF ANY OF THESE VALUES SHOULD CHANGE, THIS REPORT WILL BE NULL AND VOID. Notes: Design Information Idaho Falls, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-6 Outside db °F89 Inside db °F70 Inside db °F75 Design TD °F76 Design TD °F14 Daily range H Relative humidity %50 Moisture difference gr/lb-31 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh21953 Structure Btuh4072 Ducts Btuh0 Ducts Btuh0 Central vent (57 cfm) 4008 Btuh Central vent (57 cfm) Btuh738 Outside air Outside air Humidification Btuh0 Blower Btuh0 Piping Btuh0 Equipment load Btuh25962 Use manufacturer's data n Rate/swing multiplier 0.94 Infiltration Equipment sensible load Btuh4522 Method Latent Cooling Equipment Load SizingSimplified Construction quality Semi-tight 0Fireplaces Structure Btuh-284 Ducts Btuh0 Central vent (57 cfm) Btuh-1026 CoolingHeating Outside air 19041904Area (ft²)Equipment latent load Btuh0 1630516305Volume (ft³) Air changes/hour 0.140.26 Equipment Total Load (Sen+Lat)Btuh4522 Equiv. AVF (cfm) 3871 Req. total capacity at 1.00 SHR ton0.4 Heating Equipment Summary Cooling Equipment Summary Make Day & Night Make Day & Night Trade Day & Night Trade 13 SEER N SERIES R410A AC Model Cond N4A318AKF10 AHRI ref Coil FXM4X2400AL AHRI ref 0 Efficiency 100 EFF Efficiency 12.0 EER, 14 SEER Heating input kW10.0 Sensible cooling Btuh16356 Heating output Btuh34121 Latent cooling Btuh0 Temperature rise °F47 Total cooling Btuh16356 Actual air flow cfm780 Actual air flow cfm634 Air flow factor cfm/Btuh0.036 Air flow factor cfm/Btuh0.156 Static pressure in H2O0.60 Static pressure in H2O0.60 Space thermostat Load sensible heat ratio 1.00 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Aug-23 09:24:44 Right-Suite® Universal 2022 22.0.04 RSU20783 Page 1 ...lations\T. Webb Const- R.M -Mechanical Shop.rup Calc = MJ8 Front Door faces: S T. Webb Const-Mechanical ShopJob:Right-J® Worksheet 08-20-22Date:Entire House C.MBy: Mechanical ShopPlan:Freedom Heating, Inc P.O Box 51966, Idaho Falls, Id 83405 Phone: 208-589-2396 Fax: 208-522-1320 Email: freedomheatinginc@yahoo.com 1 Room name Entire House Parts Storage 2 Exposed wall 268.5 ft 26.8 ft 3 Room height 8.6 dft 9.0 heat/coolft 4 Room dimensions ft12.0x14.8 5 Room area 1904.4 ft²177.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 781 772 3811 366 133 133 656 63 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 22.8022.80 10.8510.85 9 0 205 98 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 365 342 1689 162 108 108 534 51 .DD 11D011D0 0.3900.390 ee 29.6429.64 7.217.21 23 23 674 164 0 0 0 0 11 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 781 738 3645 350 0 0 0 0 DD 11D011D0 0.3900.390 ss 29.6429.64 7.217.21 43 43 1262 307 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 365 365 1802 173 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 1070 1070 1627 899 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --15.9615.96 0.000.00 1070 143 2274 0 177 27 427 0 6 c) AED excursion 0 0 Envelope loss/gain 16991 2520 1616 114 12 a) Infiltration 4963 492 522 52 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 2 460 0 0 Appliances/other 600 0 Subtotal (lines 6 to 13)21953 4072 2138 166 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 21953 4072 2138 166 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 21953 4072 2138 166 Air required (cfm)Air required (cfm)780 634 76 26 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Aug-23 09:24:44 Right-Suite® Universal 2022 22.0.04 RSU20783 Page 2 ...lations\T. Webb Const- R.M -Mechanical Shop.rup Calc = MJ8 Front Door faces: S T. Webb Const-Mechanical ShopJob:Right-J® Worksheet 08-20-22Date:Entire House C.MBy: Mechanical ShopPlan:Freedom Heating, Inc P.O Box 51966, Idaho Falls, Id 83405 Phone: 208-589-2396 Fax: 208-522-1320 Email: freedomheatinginc@yahoo.com 1 Room name Unisex Room Storage 2 Exposed wall 9.5 ft 90.3 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft12.0x9.5 ft587.4x1.0 5 Room area 114.0 ft²587.4 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 86 86 422 41 74 74 367 35 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 22.8022.80 10.8510.85 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 0 0 0 0 97 74 366 35 .DD 11D011D0 0.3900.390 ee 29.6429.64 7.217.21 0 0 0 0 23 23 674 164 11 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 0 0 0 0 437 394 1946 187 DD 11D011D0 0.3900.390 ss 29.6429.64 7.217.21 0 0 0 0 43 43 1262 307 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 0 0 0 0 205 205 1011 97 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 0 0 0 0 236 236 359 199 FF 22B-10vpl22B-10vpl 0.2100.210 --15.9615.96 0.000.00 114 10 152 0 587 90 1440 0 6 c) AED excursion 0 0 Envelope loss/gain 574 41 7426 1024 12 a) Infiltration 185 18 1760 175 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)759 59 9186 1199 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 759 59 9186 1199 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 759 59 9186 1199 Air required (cfm)Air required (cfm)27 9 326 187 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Aug-23 09:24:44 Right-Suite® Universal 2022 22.0.04 RSU20783 Page 3 ...lations\T. Webb Const- R.M -Mechanical Shop.rup Calc = MJ8 Front Door faces: S T. Webb Const-Mechanical ShopJob:Right-J® Worksheet 08-20-22Date:Entire House C.MBy: Mechanical ShopPlan:Freedom Heating, Inc P.O Box 51966, Idaho Falls, Id 83405 Phone: 208-589-2396 Fax: 208-522-1320 Email: freedomheatinginc@yahoo.com 1 Room name Mezzanine Office 2 Exposed wall 126.0 ft 16.0 ft 3 Room height 8.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft834.0x1.0 ft12.0x16.0 5 Room area 834.0 ft²192.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 344 344 1699 163 144 135 667 64 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 22.8022.80 10.8510.85 0 0 0 0 9 0 205 98 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 160 160 790 76 0 0 0 0 .DD 11D011D0 0.3900.390 ee 29.6429.64 7.217.21 0 0 0 0 0 0 0 0 11 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 344 344 1699 163 0 0 0 0 DD 11D011D0 0.3900.390 ss 29.6429.64 7.217.21 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 160 160 790 76 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 834 834 1268 701 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --15.9615.96 0.000.00 0 0 0 0 192 16 255 0 6 c) AED excursion 0 0 Envelope loss/gain 6247 1179 1127 162 12 a) Infiltration 2184 217 312 31 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 2 460 Appliances/other 0 600 Subtotal (lines 6 to 13)8431 1395 1439 1253 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 8431 1395 1439 1253 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 8431 1395 1439 1253 Air required (cfm)Air required (cfm)300 217 51 195 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Aug-23 09:24:44 Right-Suite® Universal 2022 22.0.04 RSU20783 Page 1 ...lations\T. Webb Const- R.M -Mechanical Shop.rup Calc = MJ8 Front Door faces: S T. Webb Const-Mechanical...Job:Loads for Multiple Orientations 08-20-22Date: Entire House C.MBy: Mechanical ShopPlan:Freedom Heating, Inc P.O Box 51966, Idaho Falls, Id 83405 Phone: 208-589-2396 Fax: 208-522-1320 Email: freedomheatinginc@yahoo.com Project Information T. Webb Const-Mechanical ShopFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-31.535.2Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F) )H(34-Daily range (°F) 60-Wet bulb (°F) 7.515.0Wind speed (mph) Front Door North Northeast East Southeast South Southwest West Northwest Sensible Load (Btuh) 4681 4892 4974 4812 4522 4730 4854 4859 Latent Load (Btuh) 0 0 0 0 0 0 0 0 Total Load (Btuh) 4681 4892 4974 4812 4522 4730 4854 4859 Heating AVF (cfm) 780 780 780 780 780 780 780 780 Cooling AVF (cfm) 634 634 634 634 634 634 634 634 Building Orientation Cooling Load Total Cooling Load (Btuh)Direction Front Door faces 0 1000 2000 3000 4000 5000 N NE E SE S SW W NW Front Door faces SouthCurrent Orientation: Front Door faces EastHighest Cooling Load: 2022-Aug-23 09:24:45 Right-Suite® Universal 2022 22.0.04 RSU20783 Page 1 ...lations\T. Webb Const- R.M -Mechanical Shop.rup Calc = MJ8 Front Door faces: S T. Webb Const-Mechanical...Job:Static Pressure and Friction Rate 08-20-22Date: Entire House C.MBy: Mechanical ShopPlan:Freedom Heating, Inc P.O Box 51966, Idaho Falls, Id 83405 Phone: 208-589-2396 Fax: 208-522-1320 Email: freedomheatinginc@yahoo.com Project Information T. Webb Const-Mechanical ShopFor: Available Static Pressure CoolingHeating (in H2O)(in H2O) 0.600.60External static pressure Pressure losses 00Coil 00Heat exchanger 0.030.03Supply diffusers 0.030.03Return grilles 00Filter 00Humidifier 0.030.03Balancing damper 00Other device 0.510.51Available static pressure Total Effective Length ReturnSupply (ft)(ft) 818Measured length of run-out 2935Measured length of trunk 310190Equivalent length of fittings 347243Total length 590Total effective length Friction Rate CoolingHeating (in/100ft)(in/100ft) OK0.086OK0.086Supply Ducts OK0.086OK0.086Return Ducts Fitting Equivalent Length Details 4AD=60, 2A2=55, 12H1=20, 12H1=20, 1C=35: TotalEL=190Supply 6M=20, 6B6=110, 10A=75, 12H1=20, 12H1=20, 5A=40, 6BB=25: TotalEL=310Return 2022-Aug-23 09:24:45 Right-Suite® Universal 2022 22.0.04 RSU20783 Page 1 ...lations\T. Webb Const- R.M -Mechanical Shop.rup Calc = MJ8 Front Door faces: S T. Webb Const-Mechanical...Job:Duct System Summary 08-20-22Date: Entire House C.MBy: Mechanical ShopPlan:Freedom Heating, Inc P.O Box 51966, Idaho Falls, Id 83405 Phone: 208-589-2396 Fax: 208-522-1320 Email: freedomheatinginc@yahoo.com Project Information T. Webb Const-Mechanical ShopFor: CoolingHeating External static pressure in H2O0.60in H2O0.60 Pressure losses in H2O0.09in H2O0.09 Available static pressure in H2O0.51in H2O0.51 Supply / return available pressure 0.210 / 0.300 in H2O in H2O0.210 / 0.300 Lowest friction rate in/100ft0.086in/100ft0.086 Actual air flow cfm634cfm780 Total effective length (TEL)ft590 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st1B180.054.5ShMt0x08.00.0901091504216hMezzanine-A 00ShMt0x000109150698hMezzanine-B st1A160.037.0ShMt0x08.00.107195511253cOffice-A st1B190.053.0ShMt0x06.00.08626762138hParts Storage-A st1140.06.8ShMt0x06.00.143621093062hStorage st1A150.024.3ShMt0x06.00.121621093062hStorage-A st1B170.040.8ShMt0x06.00.100621093062hStorage-B st1130.024.5ShMt0x06.00.136927759hUnisex Room-A Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st1B Peak AVF 335 197 0.086 602 9.4 10x8 ShtMetl st1A st1A Peak AVF 494 454 0.086 556 10.9 16x8 ShtMetl st1 st1 Peak AVF 630 525 0.086 567 12.9 20x8 ShtMetl 2022-Aug-23 09:24:45 Right-Suite® Universal 2022 22.0.04 RSU20783 Page 2 ...lations\T. Webb Const- R.M -Mechanical Shop.rup Calc = MJ8 Front Door faces: S Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb2 0x 3000 217 74.8 0.401 858 8.0 x0 0 ShMt rb1 0x 3530 196 128.3 0.234 559 7.9 2-3.25x14 2-10x18 SJSp rt1 rb4 0x 760 26 346.8 0.086 240 5.4 3.25x14 10x9 SJSp rt1B rb3 0x 510 195 205.3 0.146 617 6.9 3.25x14 10x9 SJSp rt1A Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1B Peak AVF 76 26 0.086 137 5.4 10x8 ShtMetl rt1A rt1A Peak AVF 127 221 0.086 199 8.1 20x8 ShtMetl rt1 rt1 Peak AVF 480 417 0.086 360 10.8 24x8 ShtMetl Job #: T. Webb Const-Mechanical Shop Performed by C.M for: T. Webb Const-Mechanical Shop Freedom Heating, Inc P.O Box 51966 Idaho Falls, Id 83405 Phone: 208-589-2396 Fax: 208-522-1320 freedomheatinginc@yahoo.com Scale: 1 : 189 Page 1 Right-Suite® Universal 2022 22.0.04 RSU20783 2022-Aug-23 09:24:58 ... Const- R.M -Mechanical Shop.rup N Main Lvl Parts StorageOfficeUnisex Room Storage 18'-0" 76 cfm 195 cfm 76 cfm 27 cfm 109 cfm 109 cfm109 cfm 6 " 6 " 6 " 8 "6 " 20 x 8 6 " 353 cfm 14x3.25 24 x 8 2-14x3.25 8 " 16 x 8 10 x 8 8 " 20 x 8 195 cfm 14x3.25 10 x 8 Job #: T. Webb Const-Mechanical Shop Performed by C.M for: T. Webb Const-Mechanical Shop Freedom Heating, Inc P.O Box 51966 Idaho Falls, Id 83405 Phone: 208-589-2396 Fax: 208-522-1320 freedomheatinginc@yahoo.com Scale: 1 : 189 Page 2 Right-Suite® Universal 2022 22.0.04 RSU20783 2022-Aug-23 09:24:59 ... Const- R.M -Mechanical Shop.rup N Upper Lvl Mezzanine 18'-0" 150 cfm 150 cfm 300 cfm