Description : Madison Memorial Hospital - MRI Zone Remodel
Address : 450 E Main St
Record Type : Commercial - Remodel
Document Filename : MMH MRI Renovations - BID SET 10.28.21.pdf
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report
Approved
# 21-00880
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
G100 Stamp Cody Jones : Building Open 1 Approved - Building Inspector
A100 Free text Cody Jones : Building Open 2 All construction and materials need to comply with IBC 2018.
Exit lighting and Emergency lighting to be installed.
Ceiling to be installed to manufactures specifications.
G100 Stamp Alex Owens : Electrical Open 1 Approved - Electrical Inspector
E000 Callout Alex Owens : Electrical Open 3 All wiring must meet 2017 NEC requirements
E000 Stamp Alex Owens : Electrical Open 3 Approved - Electrical Inspector
E100 Stamp Alex Owens : Electrical Open 4 Approved - Electrical Inspector
G100 Stamp Kyle Baldwin : P&Z Open 1 Approved - Planning and Zoning
A100 Stamp Kyle Baldwin : P&Z Open 2 Approved - Planning and Zoning
E000 Stamp Kyle Baldwin : P&Z Open 3 Approved - Planning and Zoning
E100 Stamp Kyle Baldwin : P&Z Open 4 Approved - Planning and Zoning
Commercial - Remodel
Approval of plans does not constitute approval of variance from code
Powered by TCPDF (www.tcpdf.org)
GSPublisherVersion 1169.55.55.100
TITLE SHEET
G100
B. LEDFORD
SHEET TITLE:
JOBNUMBER:
REVISION DATE
RE
X
B
U
R
G
,
ID
PR
O
J
E
C
T
:
CONTRACTOR SHALL VERIFY
ALL DIMENSIONS & CONDITIONS
SHOWN OR IMPLIED
21553-21B
OCTOBER 2021
M
y
e
r
s
92
7
Ma
i
n
St
r
e
e
t
,
Su
i
t
e
30
0
■
Ev
a
n
s
t
o
n
,
Wy
o
m
i
n
g
82
9
3
0
■
Te
l
.
(30
7
)
78
9
-
09
3
4
12
2
So
u
t
h
Ma
i
n
St
r
e
e
t
■
Po
c
a
t
e
l
l
o
,
Id
a
h
o
83
2
0
4
■
Te
l
.
(20
8
)
23
2
-
37
4
1
■
Fa
x
(20
8
)
23
2
-
37
8
2
AI
A
NC
A
R
B
AS
I
D
DRAWNBY:
PROJECTDATE:
SHEET
MR
I
ZO
N
E
S
DRAWING SCALE APPLIES TO22" X 34" SHEET SIZE
■ Ar
c
h
i
t
e
c
t
u
r
e
A
n
d
e
r
s
o
n
■ In
t
e
r
i
o
r
De
s
i
g
n
■ Hi
s
t
o
r
i
c
Pr
e
s
e
r
v
a
t
i
o
n
MA
D
I
S
O
N
ME
M
O
R
I
A
L
HO
S
P
I
T
A
L
MRI ZONES
CONSULTANTSABBREVIATIONS
ELECTRICAL ENGINEER
MUSGROVE ENGINEERING
645 W. 25TH ST.
IDAHO FALLS, ID 83402
PHONE: (208) 523-2862
FAX: (208) 523-2864
CONCRETE BLOCK
STRUCTURAL WOOD
DEMO
RIGID INSULATION
BRICK VENEER
GRAVEL
SYMBOLS
METAL STUDS
CONCRETE
GYP. WALL BD.
WOOD STUDS
EARTH
DRAWING NUMBER
TITLE
DETAIL NUMBER
DETAIL SYMBOL
SECTION LETTER
BUILDING SECTION
SHEET NUMBER
ELEVATION
WINDOW MARKER
ROOM NUMBER
DOOR NUMBER
DETAIL NUMBER
DETAIL CUT
SHEET NUMBER
WALL ELEVATION
ELEVATION NUMBER
BATT INSULATION
SHEET NUMBER
SHEET NUMBER
SECTION NUMBER
WALL SECTION
SHEET NUMBER
FILL EARTH
EXISTING
METAL
3/4" = 1'-0"
J
A300
SHEET NUMBER
ELEVATION NUMBER
BUILDING ELEVATION
SHEET NUMBER
DRAWING INDEX
SHEET NUMBER SHEET TITLE
G100 COVER SHEET
A100 ARCHITECTURAL DRAWINGS
E000 ELECTRICAL COVER SHEET
E100 POWER PLAN
VICINITY MAP
CODE REVIEW
RENOVATION IS LIMITED IN SCOPE AND DOES NOT AFFECT USE OR CONSTRUCTION
TYPE. THE COMMENTS BELOW ARE INTENDED TO ADDRESS POTENTIAL QUESTIONS
THAT MAY ARISE IN REVIEW.
1. RENOVATION ADDS NO AREA TO EXISTING BUILDING.
2. RENOVATION CLOSES OFF AN EXISTING HALLWAY BUT THE DEAD-END HALLWAY
CREATED IS ONLY 15' LONG.
3. THE HALLWAY THAT IS BEING CLOSED IS NOT A REQUIRED SECOND PATH OF
EGRESS FOR ANY AREA OF THE HOSPITAL.
4. NEW WALLS BEING ADDED ARE NOT FIRE OR SMOKE PARTITIONS. NO EXISTING
FIRE OR SMOKE PARTITIONS ARE AFFECTED.
5. EXISTING FIRE SPRINKLER HEADS WILL NOT BE AFFECTED AND WILL CONTINUE TO
PROVIDE COVERAGE TO ALL AREAS IN THE RENOVATION.
ARCH ARCHITECTURAL
CLG. CEILING
ELEC. ELECTRICAL
EQ. EQUAL
EXIST. EXISTING
GYP. BRD. GYPSUM BOARD
HM HOLLOW METAL
HORIZ HORIZONTAL
MECH. MECHANICAL
O.C. ON CENTER
TYP. TYPICAL
VERT VERTICAL
WD WOOD
PROJECT LOCATION
450 E MAIN ST, REXBURG, ID 83440
155
W03
4
A501
A300
A202
5/A300
2/SD102
#DrgID
#DrgID
#DrgID
#DrgID #DrgID
#LayID
WALL TYPE3
PLYWOOD
WOOD BLOCKING
PROJECT SITE
B
B
ROOM NAME
146
43 sq ft
OVERALL MAIN LEVEL PLAN
1/32" = 1'-0"
PROJECT LOCATION
GSPublisherVersion 1169.55.55.100
ARCH.DRAWINGS
A100
B. LEDFORD
SHEET TITLE:
JOBNUMBER:
REVISION DATE
RE
X
B
U
R
G
,
ID
PR
O
J
E
C
T
:
CONTRACTOR SHALL VERIFY
ALL DIMENSIONS & CONDITIONS
SHOWN OR IMPLIED
21553-21B
OCTOBER 2021
M
y
e
r
s
92
7
Ma
i
n
St
r
e
e
t
,
Su
i
t
e
30
0
■
Ev
a
n
s
t
o
n
,
Wy
o
m
i
n
g
82
9
3
0
■
Te
l
.
(30
7
)
78
9
-
09
3
4
12
2
So
u
t
h
Ma
i
n
St
r
e
e
t
■
Po
c
a
t
e
l
l
o
,
Id
a
h
o
83
2
0
4
■
Te
l
.
(20
8
)
23
2
-
37
4
1
■
Fa
x
(20
8
)
23
2
-
37
8
2
AI
A
NC
A
R
B
AS
I
D
DRAWNBY:
PROJECTDATE:
SHEET
MR
I
ZO
N
E
S
DRAWING SCALE APPLIES TO22" X 34" SHEET SIZE
■ Ar
c
h
i
t
e
c
t
u
r
e
A
n
d
e
r
s
o
n
■ In
t
e
r
i
o
r
De
s
i
g
n
■ Hi
s
t
o
r
i
c
Pr
e
s
e
r
v
a
t
i
o
n
MA
D
I
S
O
N
ME
M
O
R
I
A
L
HO
S
P
I
T
A
L
MRI (ZONE 4)
---
A:469 sq ft
MRI/CT CONTROL
---
A:309 sq ft
CT
---
A:386 sq ft
PAT. RR.
---
A:39 sq ft
XRAY 2
---
A:324 sq ft
XRAY 1
---
A:417 sq ft
PAT. RR.
---
A:43 sq ft
JAN.
---
A:35 sq ft
DRESSING RM
---
A:39 sq ft
ZONE 2
100
A:204 sq ft
ZONE 3
101
A:204 sq ft
HALLWAY (ZONE 1)
---
A:853 sq ft
100
101
15
'
-
0
"
ALIGN WALL WITH CORNER
CUT WALL BUMPER BACK 6" FROM
EACH SIDE OF NEW DOOR FRAMES
AND INSTALL NEW END CAPS, TYP.
SINGLE/PAIR PAIR
DOOR
WIDTH 7'-7"
HEIGHT 7'-0"
THK 1 3/4"
MAT FLUSH WOOD
VENEER RED OAK, CLEAR FINISH
FRAME
MAT HOLLOW METAL
THROAT 4 7/8"
GLAZING TYPE 1/4" TEMPERED
HINGES IVES 112HD, CONT. HINGE
KICKPLATE IVES 8400 SERIES
LOCK ASSA ABLOY, M32
LEVER SCHALGE ND SERIES
EXIT DEVICE VON DUPRIN, 98 SERIES
OPERATORS NORTON 6050 689
ADA ACTUATOR NORTON 502
STOPS ROCKWOOD 406 US32D
CARD READER MATCH EXISTING
REQUEST TO EXIT MATCH EXISTING
POWER TRANSFER SECURITRON
POWER SUPPLY SECURITRON
DOOR 100
FUNCTION:
CARD IN. USER PRESENTS CREDENTIAL, MAG LOCK
RELEASES AND OPERATOR OPENS ACTIVE LEAF.
REQUEST TO EXIT IS IN ADA ACTUATOR AND IN EXIT
DEVICE FOR LEFT HAND LEAF.
7'
-
0
"
3'-9 1/2"3'-9 1/2"
8'-0"
1'
-
4
"
8"8"
2'
-
6
"
1'
-
0
"
UNDERCUT DOORS 1"
SINGLE/PAIR PAIR, UNEQUAL LEAVES, AS SHOWN
DOOR
WIDTH 7'-0"
HEIGHT 7'-0"
THK 1 3/4"
MAT FLUSH WOOD
VENEER RED OAK, CLEAR FINISH
FRAME
MAT HOLLOW METAL
THROAT 4 7/8"
GLAZING TYPE 1/4" TEMPERED
HINGES IVES 112HD, CONT. HINGE
KICKPLATE IVES 8400 SERIES
LOCK ASSA ABLOY, M32
LEVER SCHALGE ND SERIES
EXIT DEVICE VON DUPRIN, 98 SERIES
OPERATORS NORTON 6050 689
ADA ACTUATOR NORTON 502
STOPS ROCKWOOD 406 US32D
CARD READER MATCH EXISTING
REQUEST TO EXIT MATCH EXISTING
POWER TRANSFER SECURITRON
POWER SUPPLY SECURITRON
DOOR 101
FUNCTION:
CARD IN. USER PRESENTS CREDENTIAL, MAG LOCK
RELEASES AND OPERATOR OPENS ACTIVE LEAF.
REQUEST TO EXIT IS IN ADA ACTUATOR FOR ACTIVE
LEAF. REQUEST TO EXIT IS IN EXIT DEVICE FOR
INACTIVE LEAF.
1'
-
4
"
3'-0"4'-0"
7'
-
0
"
2'
-
6
"
1'
-
0
"
8"8"
UNDERCUT DOORS 1"
EXIST. MECH. DIFFUSERS
EXIST. LIGHT FIXTURES
EXIST. SPEAKER
EXIST. SPEAKER
EXIST. SPRINKLER HEADS
CUT AND PATCH EXIST.
CLG. GRID TO NEW WALL
CUT AND PATCH EXIST.
CLG. GRID TO NEW WALL
3"
1/2"
2"
5/8" GYP. BRD.
MTL. STUD FRAMING
AT 1'-4" O.C.
5/8" GYP. BRD.
HOLLOW METAL DOOR FRAME
DOOR, SEE DOOR SCHEDULE
3"2"
DOOR, SEE DOOR SCHEDULE
5/8" GYP. BRD.
SEALANT,
BOTH SIDES
5/8" GYP. BRD.
MTL. STUD FRAMING
AT 1'-4" O.C.
HOLLOW METAL DOOR FRAME
MAIN FLOOR PLAN
1/8" = 1'-0"
DOOR 100
3/8" = 1'-0"
DOOR 101
3/8" = 1'-0"
MAIN FLOOR REFLECTED CEILING PLAN
1/8" = 1'-0"
JAMB DETAIL
1 1/2"= 1'-0"
HEAD DETAIL
1 1/2"= 1'-0"
All construction and materials need to comply with IBC 2018.
Exit lighting and Emergency lighting to be installed.
Ceiling to be installed to manufactures specifications.
GSPublisherVersion 1169.55.55.100
E000
E100
B. LEDFORD
SHEET TITLE:
JOBNUMBER:
REVISION DATE
RE
X
B
U
R
G
,
ID
PR
O
J
E
C
T
:
CONTRACTOR SHALL VERIFY
ALL DIMENSIONS & CONDITIONS
SHOWN OR IMPLIED
21553-21B
OCTOBER 2021
M
y
e
r
s
92
7
Ma
i
n
St
r
e
e
t
,
Su
i
t
e
30
0
■
Ev
a
n
s
t
o
n
,
Wy
o
m
i
n
g
82
9
3
0
■
Te
l
.
(30
7
)
78
9
-
09
3
4
12
2
So
u
t
h
Ma
i
n
St
r
e
e
t
■
Po
c
a
t
e
l
l
o
,
Id
a
h
o
83
2
0
4
■
Te
l
.
(20
8
)
23
2
-
37
4
1
■
Fa
x
(20
8
)
23
2
-
37
8
2
AI
A
NC
A
R
B
AS
I
D
DRAWNBY:
PROJECTDATE:
SHEET
MR
I
ZO
N
E
S
DRAWING SCALE APPLIES TO22" X 34" SHEET SIZE
■ Ar
c
h
i
t
e
c
t
u
r
e
A
n
d
e
r
s
o
n
■ In
t
e
r
i
o
r
De
s
i
g
n
■ Hi
s
t
o
r
i
c
Pr
e
s
e
r
v
a
t
i
o
n
MA
D
I
S
O
N
ME
M
O
R
I
A
L
HO
S
P
I
T
A
L
DUAL LEVEL SWITCHING, INSIDE AND OUTSIDE LAMPS OF FIXTURE
TO BE SWITCHED SEPARATELY.
SWITCH, TYPE AS INDICATED. +46"AFF
SINGLE CONVENIENCE OUTLET, +18" AFF UNO
FLOOR MOUNT SINGLE CONVENIENCE OUTLET
DUPLEX CONVENIENCE OUTLET, +18" AFF UNO
FLOOR MOUNT DUPLEX CONVENIENCE OUTLET
EMERGENCY DUPLEX CONVENIENCE OUTLET, +18" AFF UNO
SWITCHED DUPLEX CONVENIENCE OUTLET, +18" AFF UNO
FLOOR MOUNTED SWITCHED DUPLEX CONVENIENCE OUTLET
FOURPLEX CONVENIENCE OUTLET. +18"AFF UNO
FLOOR MOUNT FOURPLEX CONVENIENCE OUTLET
CONNECTION POINT TO EQUIPMENT SPECIFIED, ELECTRICAL
CONTRACTOR TO SUPPLY RACEWAY AND CONDUCTORS AND MAKE
FINAL CONNECTION TO EQUIPMENT UNDER THIS SECTION. UNO
FLOOR MOUNTED CONNECTION POINT, SEE NOTE ABOVE FOR
REQUIREMENTS
JUNCTION BOX
WALL MOUNTED PUSH BUTTON, MOUNT AT SWITCH HEIGHT UNO
WALL MOUNTED PUSH BUTTON, HANDICAPPED MOUNT AT SWITCH
HEIGHT UNO
WALL MOUNTED PUSH BUTTON, MOUNT AT SWITCH HEIGHT UNO
MOTOR STARTER/CONTACTOR, SIZE/POLES NEMA 1 UNO AS INDICATED
COMBINATION STARTER AND DISCONNECT, SIZE/POLES, STARTER SIZE
AS INDICATED, NEMA 1 UNO
MECHANICAL EQUIPMENT CALL OUT
SURFACE MULTI-OUTLET RACEWAY
EQUIPMENT CABINET FLUSH MOUNTED
EQUIPMENT CABINET, SURFACE MOUNTED
PANELBOARD. SEE SCHEDULE FOR TYPE.
TRANSFORMER
POWER POLE - DUAL CHANNEL
THERMOSTAT, +46" AFF PROVIDE CONDUIT, J-BOX, CONDUCTORS AS
REQUIRED TO CONTROL ASSOCIATED UNITS. UNO COORDINATE WITH
DIVISION 15.
NON-FUSED DISCONNECT SIZE/ POLES AS INDICATED, NEMA 1 UNO
FUSED DISCONNECT SWITCH, SIZE/POLES, FUSE SIZES AS INDICATED,
NEMA 1 UNO
KITCHEN EQUIPMENT CALLOUT
FLOOR MOUNTED JUNCTION BOX
#
#
#
#
#
2 DOUBLE POLE
3 3-WAY
4 4-WAY
K KEYED
P PILOT LIGHT
D DIMMER
HP HORSEPOWER RATED
TO THERMAL OVERLOAD
LV LOW VOLTAGE
OS OCCUPANCY SENSOR
OR LOW VOLTAGE, MOMENTARY OVERRIDE
VS VACANCY SENSOR
a SUPERSCRIPT INDICATES LIGHTS
TO BE SWITCHED TOGETHER
SX
X
J
J
HC
F
T
X-X
S S
SOS
2 DUAL LEVEL SWITCHING WITH OCCUPANCY SENSOR, INSIDE AND
OUTSIDE LAMPS OF FIXTURE TO BE SWITCHED SEPARATELY.
DEVICES
A AMPERES
AC 6" ABOVE BACKSPLASH
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AF AMP FRAME
AIC AMPS INTERRUPTING CAPACITY
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
BD BOTTOM OF DECK
BS BOTTOM OF STRUCTURE
C CEILING MOUNTED
C CONDUIT
CB CIRCUIT BREAKER
CF COMPACT FLUORESCENT
CKT CIRCUIT
CO CONDUIT ONLY, PROVIDE PULL-LINE
CT CURRENT TRANSFORMER
CTL CONTROL
DC DIRECT CURRENT
(D)DEMOLITION
DEMO DEMOLITION
DET DETAIL
DTT DOUBLE TWIN TUBE
E EMERGENCY
(E)EXISTING
EC ELECTRICAL CONTRACTOR
EL EMERGENCY LIGHT
F FUSE
(F)FUTURE
FACP FIRE ALARM CONTROL PANEL
G/GND GROUND
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFI GROUND FAULT INTERRUPTER
HH HAND HOLE
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTO
HPS HIGH PRESSURE SODIUM
HVAC HEATING, VENTILATION, & AIR CONDITIONING
IG ISOLATED GROUND
IPCO IDAHO POWER COMPANY
J-BOX JUNCTION BOX
KA KILOAMP
KVA KILO VOLT-AMP
KW KILOWATT
KWH KILOWATT HOUR
LCP LIGHTING CONTROL PANEL
MB MAIN BREAKER
MBR MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MLO MAIN LUGS ONLY
MMC MODULAR METERING CENTER
MH METAL HALIDE
MSB MAIN SWITCH BOARD
MTG MOUNTING
N NEUTRAL
(N)NEW
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OH OVERHEAD
OS OCCUPANCY SENSOR
P POLES
PC PHOTO-CONTROL
PVC POLYVINYL CHLORIDE
PWR POWER
RE:REFERENCE
REC RECEPTACLE
(R)RELOCATED
SF SQUARE FEET
TBD TO BE DETERMINED
TDR TIME DELAY RELAY
TK TOE KICK
TSP TWISTED SHIELDED PAIR
TRT TRIPLE TUBE
TTB TELEPHONE TERMINAL BOARD
(TYP.)TYPICAL
UC UNDERCABINET
UG UNDERGROUND
U.N.O.UNLESS NOTED OTHERWISE
V VOLT
VA VOLT-AMPERE
W WATT
WG WIRE GUARD
WP WEATHER PROOF/NEMA 3R
ELECTRICAL ABBREVIATIONS
PROVIDED/
PROVIDE BY
INSTALLED/
INSTALL
PROVIDE AND INSTALL / PROVIDED AND
INSTALLED BY / PROVIDE AND INSTALL
NOTE:
THIS IS A STANDARD LIST OF COMMONLY USED
ELECTRICAL ABBREVIATIONS. SOME OF THE
ABBREVIATIONS SHOWN ABOVE MAY NOT BE
USED IN THIS DRAWING PACKAGE.
NOTE:
THIS IS A STANDARD LIST OF COMMONLY USED ELECTRICAL SYMBOLS. SOME
OF THE SYMBOLS SHOWN MAY NOT HAVE BEEN USED IN THIS DRAWING
PACKAGE.
EXISTING
CONDUIT DOWN CONDUIT UP
6
NEUTRAL CONDUCTORS
GROUNDING CONDUCTOR
SIZE
QUANTITY
1"-4#10,1#10G
PANEL HOMERUN. (3/4"-2#12,1#12G CONDUCTORS UNO)
RACEWAY
A-2,4,6
PANEL NAME
CIRCUIT #
EM
NOTE:
J
J J J
J J
CIRCUITING SYMBOLS
CURRENT CARRYING
CONDUCTORS
T
ELECTRICAL SPECIFICATIONS
- BLACK
- RED
- BLUE
- WHITE
- GREEN
PHASE A
PHASE B
PHASE C
NEUTRAL
GROUND
- BROWN
- ORANGE
- YELLOW
- GRAY
- GREEN
PHASE A
PHASE B
PHASE C
NEUTRAL
GROUND
208Y/120 VOLT SYSTEM 480Y/277 VOLT SYSTEM
A.ALL WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE
LOCALLY ADOPTED ELECTRICAL CODE, ALL LOCAL CODES, AND TO THE FULL
ACCEPTANCE OF THE AUTHORITY HAVING JURISDICTION.
B.OBTAIN ALL PERMITS, COORDINATE, FURNISH, INSTALL, CONNECT AND TEST
ALL ELECTRICAL EQUIPMENT REQUIRED FOR ALL THE SYSTEMS INSTALLED
UNDER THIS CONTRACT TO INSURE COMPLETE AND FULLY OPERATIONAL
SYSTEMS.
C.CONTRACTOR SHALL MAINTAIN A COMPLETE SET OF AS-BUILT DRAWINGS.
AS-BUILT SET OF DRAWINGS SHALL BE UPDATED DAILY AND SHALL DOCUMENT
THE ACTUAL INSTALLED CONDITION OF THE ENTIRE ELECTRICAL
INSTALLATION. AS-BUILT SET OF DRAWINGS SHALL BE AVAILABLE AT ALL
TIMES ON THE SITE FOR INSPECTION BY CODE OFFICIALS, OWNER, ARCHITECT,
AND ENGINEER.
D.PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION.
E.DESIGN IS BASED ON BEST AVAILABLE INFORMATION. CONTRACTOR SHALL
FIELD VERIFY EXISTING CONDITIONS TO DETERMINE STATUS OF ACTUAL
CONDITIONS AS THEY RELATE TO THE SCOPE OF WORK AS SHOWN ON THESE
PLANS.
F.COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.
G.COORDINATE EXACT LOCATION AND MOUNTING HEIGHTS OF ALL ELECTRICAL
EQUIPMENT AND DEVICES WITH THE ARCHITECTURAL ELEVATIONS AND
DETAILS PRIOR TO ROUGH-IN.
H.DEMOLITION WORK IS A PART OF THIS PROJECT. SEE DRAWINGS FOR
EXISTING ELECTRICAL DEVICES TO BE REMOVED. REMOVE ASSOCIATED
BOXES, RACEWAYS AND CONDUCTORS BACK TO SOURCE, AND MAKE SAFE.
I.ALL MATERIALS AND EQUIPMENT FURNISHED TO THE PROJECT SHALL BE NEW
AND SHALL BEAR THE LISTING LABEL OF A NATIONALLY RECOGNIZED TESTING
LAB AS DEFINED BY OSHA.
J.ALL ELECTRICAL DEVICES AND TERMINALS SHALL BE RATED 75°C MINIMUM.
K.ALL CONDUCTORS SHALL BE STRANDED COPPER, 600 VOLT RATED.
INSULATION TYPE SHALL BE THHN/THWN, FULLY COLOR CODED WITH GAUGE,
TYPE AND MANUFACTURER MARKED EVERY 24" ALONG. CONDUCTOR COLOR
CODE SHALL BE AS FOLLOWS:
L.MINIMUM SIZE WIRE FOR POWER AND LIGHTING CIRCUITS SHALL BE #12 AWG.
ALL POWER AND LIGHTING CONDUCTORS SHALL BE ROUTED IN 3/4" CONDUIT
MINIMUM.
M.EMT OR MC TYPE CABLE IS ALLOWED WHEN CONCEALED IN INTERIOR SPACES.
MC TYPE CABLE IS NOT ALLOWED FOR HOMERUNS.
N.MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S
REQUIREMENTS.
O.ALL EQUIPMENT, SWITCHING DEVICES AND PANELS SHALL BE MOUNTED SO AS
TO BE ACCESSIBLE AND SHALL BE MOUNTED PLUMB AND SQUARE WITH
WALLS.
P.DEVICES AND RACEWAYS PENETRATING FIRE RATED WALLS AND FLOORS
SHALL BE SEALED WITH FIRE RESISTIVE MATERIAL, COMPATIBLE WITH
CONSTRUCTION PENETRATED, TO MAINTAIN RATING OF THE WALL. SEALANT
SYSTEM SHALL BE A U.L. APPROVED SYSTEM AND INSTALLED PER
MANUFACTURER'S INSTRUCTIONS.
Q.FURNISH AND INSTALL PULL CORD IN ALL EMPTY CONDUITS.
R.ALL JUNCTION BOX COVERS WITH POWER WIRING SHALL HAVE THE PANEL AND
CIRCUIT LABELED ON THE OUTSIDE SURFACE. ALL LABELS FOR EXPOSED
JUNCTION BOXES IN "FINISHED AREAS" SHALL BE LABELED UTILIZING SELF
ADHESIVE LABELS PRODUCED BY A MECHANICAL LABELING MACHINE. LABELS
FOR JUNCTION BOX COVERS IN CONCEALED LOCATIONS SHALL CONSIST OF
THE INFORMATION BEING NEATLY HANDWRITTEN ON THE OUTSIDE SURFACE
OF THE COVER WITH A PERMANENT STYLE MARKER.
S.CLEARLY LABEL ALL ACCESSIBLE CONDUIT STUBS WITH SYSTEM NAME AND
LOCATION (ROOM NUMBER) WHERE THE OTHER END OF THE CONDUIT
TERMINATES. USE INDELIBLE INK. THE LABELS SHALL BE LOCATED ON THE
CONDUIT IN A POSITION THAT CAN BE EASILY READ.
T.ALL 1 POLE BREAKER CIRCUITS SHALL HAVE AN INDEPENDENT NEUTRAL
CONDUCTOR. NO EDISON STYLE SHARED NEUTRAL CONDUCTORS ARE
ALLOWED.
U.ALL CONDUCTORS IN ELECTRICAL PANELS, CABINETS AND EQUIPMENT SHALL
BE NEATLY TRAINED AND LACED.
V.THE CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES
FOR ALL PANELS. DIRECTORIES SHALL BE TYPED.
W.PROVIDE ELECTRICAL SUBMITTALS FOR EQUIPMENT SHOWN AS REQUIRED BY
DIVISION 1 SPECIFICATIONS.
X.ELECTRICAL CONTRACTOR SHALL OBTAIN THE AVAILABLE FAULT CURRENT
VALUE FROM THE LOCAL UTILITY OR THE ONE-LINE DIAGRAM AND LABEL THE
MAIN BREAKER WITH THAT VALUE.
Y.SWITCH AND RECEPTACLE LABELING: IDENTIFY PANELBOARD AND CIRCUIT
NUMBER FROM WHICH DEVICES ARE SERVED. USE MACHINE PRINTED LABEL
AND 1/8" TEXT. INSTALL ON THE OUTSIDE OF THE FACEPLATE FOR
RECEPTACLES AND INSIDE THE FACEPLATE FOR SWITCHES.
OCCUPANCY SENSOR WITH MANUAL DIMMING, SET FOR 50%
AUTOMATIC ON, AUTOMATIC OFF, WITH MANUAL DIMMING.SOS
D
DESIGNATES CIRCUIT ON
EMERGENCY SOURCE
UNMARKED CIRCUIT IS CONCEALED IN
CEILING OR WALL. MAINTAIN
CONDUIT AND CONDUCTOR SIZE
THROUGHOUT ENTIRE CIRCUIT.
BEGINNING OF INDIVIDUAL
CIRCUIT(S), CIRCUIT NUMBER(S)
INDICATED.
EDISON STYLE SHARED NEUTRAL CONDUCTORS ARE NOT ALLOWED.
EACH 1 POLE BREAKER SHALL BE FURNISHED WITH AN INDIVIDUAL
DEDICATED NEUTRAL CONDUCTOR.
CONDUIT, STUBBED, CAPPED AND MARKED
WITH PULL CORD AS SPECIFIED
CONCEALED IN
FLOOR OR
UNDERGROUND
ELECTRICAL GENERAL NOTES
A.THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC IN NATURE; THEREFORE,
THE ELECTRICAL CONTRACTOR SHALL COORDINATE ALL ELECTRICAL
EQUIPMENT AND DEVICE LOCATIONS WITH ARCHITECTURAL, MECHANICAL,
AND PLUMBING DIVISIONS PRIOR TO ROUGH-IN. REFER TO AND COORDINATE
WITH ARCHITECTURAL, MECHANICAL, AND PLUMBING DRAWINGS FOR
ADDITIONAL WORK THAT IS REQUIRED BY THE ELECTRICAL CONTRACTOR.
B.ALL CONDUIT AND JUNCTION BOXES ARE TO BE CONCEALED UNLESS LOCATED
WITHIN DEDICATED ELECTRICAL OR MECHANICAL ROOMS. USE OF SURFACE
MOUNTED RACEWAYS IN ALL OTHER SPACES MUST BE APPROVED BY THE
ARCHITECT FOR EACH LOCATION. WHERE SURFACE RACEWAYS ARE
APPROVED, UTILIZE WIREMOLD, OR APPROVED EQUAL, SURFACE MOUNTED
RACEWAYS PAINTED TO MATCH SURROUNDING WALLS.
C.REFER TO ARCHITECTURAL ELEVATIONS FOR OUTLET HEIGHTS WHERE THE
SPECIFIC OUTLET HEIGHT IS NOT INDICATED. REFER TO THE ELECTRICAL
LEGEND FOR THE DEFAULT OUTLET HEIGHT WHEN NOT INDICATED ON
ELEVATIONS OR ON AT THE DEVICES.
D.PROVIDE PULL-LINE IN ALL EMPTY CONDUITS.
E.TERMINATE ALL LOW-VOLTAGE CONDUITS WITH INSULATED THROAT BUSHING.
F.MECHANICAL EQUIPMENT INDICATED IS SHOWN IN AN APPROXIMATE
LOCATION. COORDINATE EXACT LOCATION WITH MECHANICAL CONTRACTOR
PRIOR TO ROUGH-IN.
USB DUPLEX CONVENIENCE OUTLET, +18" AFF UNO
USB FOURPLEX CONVENIENCE OUTLET, +18" AFF UNO
SHEET TITLE:
CHECKED
BY:
JOB
NUMBER:
REVISION DATE
RE
X
B
U
R
G
,
I
D
PR
O
J
E
C
T
:
CONTRACTOR SHALL VERIFY
ALL DIMENSIONS & CONDITIONS
SHOWN OR IMPLIED
M
y
e
r
s
92
7
M
a
i
n
S
t
r
e
e
t
,
S
u
i
t
e
3
0
0
■
E
v
a
n
s
t
o
n
,
W
y
o
m
i
n
g
8
2
9
3
0
■
T
e
l
.
(
3
0
7
)
7
8
9
-
0
9
3
4
12
2
S
o
u
t
h
M
a
i
n
S
t
r
e
e
t
■
P
o
c
a
t
e
l
l
o
,
I
d
a
h
o
8
3
2
0
4
■
T
e
l
.
(
2
0
8
)
2
3
2
-
3
7
4
1
■
F
a
x
(
2
0
8
)
2
3
2
-
3
7
8
2
AI
A
N
C
A
R
B
A
S
I
D
DRAWN
BY:
PROJECT
DATE:
SHEET
MR
I
Z
O
N
E
S
DRAWING SCALE APPLIES TO
22" X 34" SHEET SIZE
■ Ar
c
h
i
t
e
c
t
u
r
e
A
n
d
e
r
s
o
n
■ I
n
t
e
r
i
o
r
D
e
s
i
g
n
■ Hi
s
t
o
r
i
c
P
r
e
s
e
r
v
a
t
i
o
n
MA
D
I
S
O
N
M
E
M
O
R
I
A
L
HO
S
P
I
T
A
L
PROJECT NO.21-468
ELECTRICAL
COVER
SHEET
E000
10/27/2021
All wiring must meet 2017
NEC requirements
GSPublisherVersion 1169.55.55.100
E100
E101
B. LEDFORD
SHEET TITLE:
JOBNUMBER:
REVISION DATE
RE
X
B
U
R
G
,
ID
PR
O
J
E
C
T
:
CONTRACTOR SHALL VERIFY
ALL DIMENSIONS & CONDITIONS
SHOWN OR IMPLIED
21553-21B
OCTOBER 2021
M
y
e
r
s
92
7
Ma
i
n
St
r
e
e
t
,
Su
i
t
e
30
0
■
Ev
a
n
s
t
o
n
,
Wy
o
m
i
n
g
82
9
3
0
■
Te
l
.
(30
7
)
78
9
-
09
3
4
12
2
So
u
t
h
Ma
i
n
St
r
e
e
t
■
Po
c
a
t
e
l
l
o
,
Id
a
h
o
83
2
0
4
■
Te
l
.
(20
8
)
23
2
-
37
4
1
■
Fa
x
(20
8
)
23
2
-
37
8
2
AI
A
NC
A
R
B
AS
I
D
DRAWNBY:
PROJECTDATE:
SHEET
MR
I
ZO
N
E
S
DRAWING SCALE APPLIES TO22" X 34" SHEET SIZE
■ Ar
c
h
i
t
e
c
t
u
r
e
A
n
d
e
r
s
o
n
■ In
t
e
r
i
o
r
De
s
i
g
n
■ Hi
s
t
o
r
i
c
Pr
e
s
e
r
v
a
t
i
o
n
MA
D
I
S
O
N
ME
M
O
R
I
A
L
HO
S
P
I
T
A
L
1
J
(E)
CR1
CR
J
J
J
J
J
J
3
3
3
3
2
4 4
4 4
STUB UP 4"ABOVE CEILING
ON OPPOSITE SIDE OF DOOR
ACCESSIBLE CEILING
FINISHED FLOOR
SINGLE GANG DEVICE COVER
RANDL D-51GO12 OR EQUAL
WALL STUD
ANTI-SHORT PLASTIC BUSHING
ARLINGTON INDUSTRIES EMT75
OR EQUAL ON OPPOSITE SIDE OF DOOR
VA
R
I
E
S
FLOOR PLATE
TOP PLATE
ELECTRICAL CONTRACTOR RESPONSIBLE FOR
INSTALLATION OF CARD READER ROUGH-IN
TYPICAL DETAIL - ACTUAL INSTALLATION MAY VARY
MAGNETIC DOOR LOCK
SEE ARCHITECTURAL DOOR
SCHEDULE
STUB 3/4"C INTO DOOR FRAME
ON OPPOSITE SIDE OF DOOR
3/4"C EMT WITH PULLSTRING
ON OPPOSITE SIDE OF DOOR
MAGNETIC DOOR LOCK ON
OPPOSITE SIDE OF DOOR
SEE ARCHITECTURAL DOOR
SCHEDULE
DOOR EXIT DEVICE ON
OPPOSITE SIDE OF DOOR
SEE ARCHITECTURAL DOOR
SCHEDULE
STUB UP 4"ABOVE CEILING
WALL STUD
ANTI-SHORT PLASTIC BUSHING
ARLINGTON INDUSTRIES EMT75
OR EQUAL
STUB 3/4"C INTO DOOR FRAME
3/4"C EMT WITH PULLSTRING
SINGLE GANG DEVICE COVER
RANDL D-51GO12 OR EQUAL
FINISHED FLOOR
4-11/16" SQUARE JUNCTION BOX
WITH SINGLE GANG MUDRING
RANDL TB55057 OR EQUAL
FOR ADA OPERATOR
4-11/16" SQUARE JUNCTION BOX
WITH SINGLE GANG MUDRING
RANDL TB55057 OR EQUAL FOR
ACCESS CONTROL
4-11/16" SQUARE JUNCTION BOX
WITH SINGLE GANG MUDRING
RANDL TB55057 OR EQUAL FOR
ADA OPERATOR
ADA DOOR OPERATOR
SEE ARCHITECTURAL DOOR
SCHEDULE
ACCESSIBLE CEILING
FINISHED FLOOR
WALL STUD
VA
R
I
E
S
FLOOR PLATE
TOP PLATE
CARD READER ROUGH-IN ELEVATION
ELECTRICAL CONTRACTOR RESPONSIBLE FOR
INSTALLATION OF CARD READER ROUGH-IN
TYPICAL DETAIL - ACTUAL INSTALLATION MAY VARY
MAGNETIC DOOR LOCK
SEE ARCHITECTURAL DOOR
SCHEDULE
MAGNETIC DOOR LOCK ON
OPPOSITE SIDE OF DOOR
SEE ARCHITECTURAL DOOR
SCHEDULE
DOOR EXIT DEVICE ON
SEE ARCHITECTURAL DOOR
SCHEDULE
STUB UP 4"ABOVE CEILING
WALL STUD
ANTI-SHORT PLASTIC BUSHING
ARLINGTON INDUSTRIES EMT75
OR EQUAL
STUB 3/4"C INTO DOOR FRAME
3/4"C EMT WITH PULLSTRING
SINGLE GANG DEVICE COVER
RANDL D-51GO12 OR EQUAL
FINISHED FLOOR
4-11/16" SQUARE JUNCTION BOX
WITH SINGLE GANG MUDRING
RANDL TB55057 OR EQUAL FOR
ADA OPERATOR
ADA DOOR OPERATOR
SEE ARCHITECTURAL DOOR
SCHEDULE
4-11/16" SQUARE JUNCTION BOX
WITH SINGLE GANG MUDRING
RANDL TB55057 OR EQUAL
FOR ADA OPERATOR.
ON OPPOSITE SIDE OF DOOR
3/4"C EMT WITH PULLSTRING
ON OPPOSITE SIDE OF DOOR
SHEET TITLE:
CHECKED
BY:
JOB
NUMBER:
REVISION DATE
RE
X
B
U
R
G
,
I
D
PR
O
J
E
C
T
:
CONTRACTOR SHALL VERIFY
ALL DIMENSIONS & CONDITIONS
SHOWN OR IMPLIED
M
y
e
r
s
92
7
M
a
i
n
S
t
r
e
e
t
,
S
u
i
t
e
3
0
0
■
E
v
a
n
s
t
o
n
,
W
y
o
m
i
n
g
8
2
9
3
0
■
T
e
l
.
(
3
0
7
)
7
8
9
-
0
9
3
4
12
2
S
o
u
t
h
M
a
i
n
S
t
r
e
e
t
■
P
o
c
a
t
e
l
l
o
,
I
d
a
h
o
8
3
2
0
4
■
T
e
l
.
(
2
0
8
)
2
3
2
-
3
7
4
1
■
F
a
x
(
2
0
8
)
2
3
2
-
3
7
8
2
AI
A
N
C
A
R
B
A
S
I
D
DRAWN
BY:
PROJECT
DATE:
SHEET
MR
I
Z
O
N
E
S
DRAWING SCALE APPLIES TO
22" X 34" SHEET SIZE
■ Ar
c
h
i
t
e
c
t
u
r
e
A
n
d
e
r
s
o
n
■ I
n
t
e
r
i
o
r
D
e
s
i
g
n
■ Hi
s
t
o
r
i
c
P
r
e
s
e
r
v
a
t
i
o
n
MA
D
I
S
O
N
M
E
M
O
R
I
A
L
HO
S
P
I
T
A
L
PROJECT NO.21-468
POWER
PLAN
E100
POWER PLAN
1/8" = 1'-0"
SYMBOL USED FOR NOTE CALLOUT.
KEYED NOTES:
1.SEE CARD READER ROUGH-IN ELEVATION DETAIL THIS PAGE.
CONNECT TO EXISTING POWER CIRCUIT IN ROOM.
2.EXISTING JUNCTION BOX FOR RECEPTACLES. EXTEND 120VOLT
POWER TO NEW DOOR OPERATORS.
3.JUNCTION BOX ADJACENT TO ACCESS CONTROL JUNCTION BOX
FOR ADA OPERATOR CONNECTING CONDUCTORS.
4.CONNECT POWER TO NEW ELECTRIC DOOR OPERATORS. SEE
ARCHITECTURAL SCHEDULE FOR ACTUATOR MODEL NUMBER
#
NORTH DOOR ACCESS CONTROL AND ADA OPERTOR ROUGH-IN
NOT TO SCALE
SOUTH DOOR ACCESS CONTROL AND ADA OPERTOR ROUGH-IN
NOT TO SCALE