Loading...
HomeMy WebLinkAboutSTEEL & CONCRETE SPECAL INSPECTIONS - 21-00551 - City of Rexburg - Nature Park - Restroomw Page 1 of 1 - 017553 NATURE PARK RESTROOM - BRIGHAM - 351250 - 02/04/2022 INTERMOUNTAINTesting Services Inc. 02/08/2022 MT. WEST PRECAST 1047 W. 600 N. #1 BRIGHAM CITY UT 84302 STEEL SPECIAL INSPECTION REPORT Project #: 017553 NATURE PARK RESTROOM -BRIGHAM ReportNumber: 351250 Inspection Date: 02/04/2022 Observations: VISUAL WELD INSPECTION FOR NATURE PARK RESTROOM REXBURG @ MOUNTAIN WEST PRECAST IN BRIGHAM CITY, UT. FILLET WELD INSPECTION FOR CONCRETE FLOOR PANEL EMBEDS TO CONCRETE WALL PANELS AND ROOF PANELS EMBEDS WELDS ARE 1/4" FILLET WELDS, WELDING HAS BEEN DONE AS PER PLANS SHEET E-06 FOR THE NATURE PARK RESTROOM, REXBURG, ID. REVIEWED AND COLLECTED WELDER CERTIFICATIONS AND WILL BE KEPT ON FILE AT INTERMOUNTAIN TESTING. OBSERVATION OF WELDING OPERATIONS AND EQUIPMENT. WELDING PROCESS WAS SMAW USING E7018 ELECTRODE. WELDS ARE ACCEPTABLE IN ACCORDANCE WITH AWS D1.1, VISUAL INSPECTION ACCEPTANCE CRITERIA TABLE 6.1. VISUAL INSPECTION OF COMPLETED WELDS CONSISTED OF VERIFYING WELD TYPES, WELD LOCATION, WELD SIZE, SPACING, CLEANING, QUALITY, AND GENERAL WORKMANSHIP. *ALL WORK APPEARED TO BE IN CONFORMANCE WITH CONTRACT DOCUMENTS, AISC, AWS STANDARDS. The above noted work requiring special inspection was in accordance with the approved plans and specifications, and the applicable workmanship provisions of AWS Specification (s). Inspection results relate only to the items inspected as indicated above. This report shall not be reproduced, except in full, without the prior written approval of the agency. Sincerely, SHAWN BRID LL Special Inspector 1955 West 5200 South, Roy, Utah 84067 - Phone 801-776-5355 Fax 801-776-1345 Toll Free 1-888-488-5355 INTERMOUNTAINTesting Services Inc. February 11, 2022 MTN WEST 1047 W. 600 N. #1 BRIGHAM CITY, UT 84302 CONCRETE SPECIAL INSPECTION REPORT Project #: (#17553) MT WEST NATURE PARK RESTROOM Report Number: 350101 Inspection Date: 12/28/2021 Observation: OBSERVATION/INSPECTION WAS PROVIDED FOR IN THE FOLLOWING LOCATION: 1) RESTROOM RIGHT SIDE WALL PANEL (WP -103). - PANEL SIZE — 10' 8" X TI " X 3" THICK. - PRIMARY REINFORCEMENT — W4 X W4 X W.225 WIRE MESH (CENTERED IN PANEL THICKNESS). - ADDITIONAL - #3 TRIM BARS AROUND OPENINGS; #3 HAIRPINS, #3 PERIMETER BARS AND EMBED PLATES AS PER DETAILS ON WP -104. 2) RESTROOM ROOF PANEL (RP -101). - PANEL SIZE 11' 11" X 9'-81/2" X 4" THICK. - PRIMARY REINFORCEMENT — SAME AS ABOVE (CENTERED IN PANEL THICKNESS). - ADDITIONAL - #3 TRIM BARS @ PICK POINTS & LIFTERS, #3 HAIRPINS, AND EMBED PLATES AS PER DETAILS ON RP -101. - ''/z" X 50'._ PT CABLE, PLUS #3 CONTAINMENT BARS AT RADII OF PT CABLE. A TOTAL OF APPROXIMATELY 2 YARDS OF 5000 PSI CONCRETE WAS PLACED. ONE SET OF CYLINDERS WAS CAST FOR COMPRESSIVE STRENGTH. 12/30/21 — PT CABLE AT ABOVE ROOF PANEL, TENSIONED TO THE REQUIRED 33 KIPS (DIAL READING — 7500 PSI). REBAR WAS INSPECTED FOR SIZE, GRADE, CONDITION, LOCATION, SPACING, COVER, CLEARANCE, HOOKS, BENDS -AND LAP SPLICE. THE ABOVE NOTED WORK REQUIRING SPECIAL INSPECTION WAS IN GENERAL ACCORDANCE WITH THE APPROVED PLANS AND SPECIFICATIONS AND THE APPLICA LE WORKMANSHIP PROVISIONS OF THE UBC, ICBG, IBC, OR AWS SPECIFICATION(S). �1 ISRAEL BRAVO ROSS YOSHIMURA IIT Special Inspector Inspection results related only to the items inspected as indicated above. This report shall not be reproduced, except in full, without the prior written approval of the agency. Page 1 of I 1955 West 5200 South, Roy, Utah 84067 - Phone 801-776-5355 Fax 801-776-1345 Toll Free 1-888-488-5355 INTERMOUNTAINTesting Services Inc. February 11, 2022 MTN WEST 1047 W. 600 N. #1 BRIGHAM CITY, UT 84302 CONCRETE SPECIAL INSPECTION REPORT Project #: (#17553) MT WEST NATURE PARK RESTROOM - BRIGHAM Report Number: 350100 Inspection Date: 12/30/2021 Observation: OBSERVATION/INSPECTION WAS PROVIDED FOR IN THE FOLLOWING LOCATION: 1) RESTROOM LEFT SIDE WALL PANEL (WP -104). - PANEL SIZE —10' 8" X TI " X 3" THICK. - PRIMARY REINFORCEMENT — W4 X W4 X W.225 WIRE MESH (CENTERED IN PANEL THICKNESS). - ADDITIONAL - #3 TRIM BARS AROUND OPENINGS; #3 HAIRPINS, #3 PERIMETER BARS AND EMBED PLATES AS PER DETAILS ON WP -104. 2) RESTROOM FLOOR PANEL (FP -101). - PANEL SIZE 17'-6 3/4" X 9'-1 l t/4" X 5" - PRIMARY REINFORCEMENT — SAME AS ABOVE (2" BOTTOM CLEARANCE). - ADDITIONAL - #3 TRIM BARS AROUND OPENINGS, #3 HAIRPINS, #3 PERIMETER BARS, AND EMBED PLATES AS PER DETAILS ON FP -101. - ESW P-4 LIFTING ANGLES — 4" X 4" X 12" X 3/8" W/2 95 X 30" A706 DBA'S. - %" X 68'8" PT CABLE, PLUS #3 CONTAINMENT BARS AT RADII OF PT CABLE. A TOTAL OF APPROXIMATELY 2 YARDS OF 5000 PSI CONCRETE WAS PLACED. ONE SET OF CYLINDERS WAS CAST FOR COMPRESSIVE STRENGTH. REBAR WAS INSPECTED FOR SIZE, GRADE, CONDITION, LOCATION, SPACING, COVER, CLEARANCE, HOOKS, BENDS -AND LAP SPLICE. THE ABOVE NOTED WORK REQUIRING SPECIAL INSPECTION WAS IN GENERAL ACCORDANCE WITH THE APPROVED PLANS AND SPECIFICATIONS AND THE APPLICABLE WORKMANSHIP PROVISIONS OF THE UBC, ICBO, IBC, OR AWS SPECIFICATION S). i ISRAEL BRAVO ROSS YOSHIMURA IIT Special Inspector Inspection results related only to the items inspected as indicated above. This report shall not be reproduced, except in full, withortt the prior written approval of the agency. Page 1 of I 1955 West 5200 South, Roy, Utah 84067 - Phone 801-776-5355 Fax 801-776-1345 Toll Free 1-888-488-5355 INTERMOUNTAINTesting Services Inc. February 11, 2022 MTN WEST 1047 W. 600 N. #1 BRIGHAM CITY, UT 84302 CONCRETE SPECIAL INSPECTION REPORT Project #: (#17553) MT WEST NATURE PARK RESTROOM Report Number: 350099 Inspection Date: 12/31/2021 Observation: OBSERVATION/INSPECTION WAS PROVIDED FOR IN THE FOLLOWING LOCATION: 1) RESTROOM PARTITION WALL (PW -105). PANEL SIZE 7'-1 '/2" X 8'-7'/4" X 3" THICK. - PRIMARY REINFORCEMENT — W4 X W4 X W.225 WIRE MESH (CENTERED IN PANEL THICKNESS). ADDITIONAL - #3 TRIM BARS AROUND OPENINGS, 43 HAIRPINS, #3 PERIMETER BARS, #3 LIFTER BARS, AND EMBED PLATES AS PER DETAILS ON (PW -105). A TOTAL OF APPROXIMATELY 1 YARD OF 5000 PSI CONCRETE WAS PLACED. REBAR WAS INSPECTED FOR SIZE, GRADE, CONDITION, LOCATION, SPACING, COVER, CLEARANCE, HOOKS, BENDS AND LAP SPLICE. THE ABOVE NOTED WORK REQUIRING SPECIAL INSPECTION WAS IN GENERAL ACCORDANCE WITH THE APPROVED PLANS AND SPECIFICATIONS AND THE APPLICABLE WORKMANSHIP PROVISIONS OF THE UBC, ICBG, IBC, OR AWS SPECIFICATION(S). ISRAEL BRAVO IIT ROSS YOSHIMURA Special Inspector Inspection results related only to the items inspected as indicated above. This report shall not be reproduced, except in full, without the prior written approval of the agency. Page 1 of 1 1955 West 5200 South, Roy, Utah 84067 • Phone 801-776-5355 Fax 801-776-1345 Toll Free 1-888-488-5355 INTERMOUNTAINTesting services Inc. February 25, 2022 MTN WEST 1047 W. 600 N. #1 BRIGHAM CITY, UT 84302 CONCRETE SPECIAL INSPECTION REPORT Project #: (# 17553) MT WEST NATURE PARK RESTROOM Report Number: 350092 Inspection Date: 01/03/2022 Observation: OBSERVATION/INSPECTION WAS PROVIDED FOR IN THE FOLLOWING LOCATION: 1) RESTROOM ROOF PANEL (RP -102). - PANEL SIZE — l 1' 11" X 9' 8/2" X 4" THICK. - PRIMARY REINFORCEMENT — W4 X W4 X W.225 WIRE MESH (CENTERED IN PANEL THICKNESS). ADDITIONAL BARS - #3 TRIM BARS @PICK POINTS &LIFTERS, #3 HAIRPINS, #3 PERIMETER BARS AND EMBED PLATES AS PER DETAILS ON RP -102. '`/2" X 50' PT CABLE, PLUS #3 CONTAINMENT BARS @ RADII OF PT CABLE. 2) RESTROOM WALL PANEL (WP -107) - 17' X 19'-1 3/4" X 3" THICK. - PRIMARY REINFORCEMENT — SAME AS ABOVE (CENTERED IN PANEL THICKNESS). - ADDITIONAL BARS — SAME AS ABOVE; DETAILS ON WP -107. A TOTAL OF APPROXIMATELY 4 YARDS OF 5000 PSI CONCRETE WAS PLACED. REBAR WAS INSPECTED FOR SIZE, GRADE, CONDITION, LOCATION, SPACING, COVER, CLEARANCE, HOOKS, BENDS AND LAP SPLICE. P4 -E' BOVE NOTED WORK RE� NG SPECIAL INSPECTION WAS IN GENERAL ACCORDANCE WITH THE APPROVED P S AND SPECIFICATIONS AND THE APPLICABLE WnuK1vI/A N"IP PMnVISIONS OF THE UBC, CBO, IBC, OR AWS SPECIFICATION(S). ISRAEL BRAVO IIT ROSS YOSHIMURA Special Inspector Inspection results related only to the items inspected as indicated above. This report shall not be reproduced, except in full, without the prior written approval of the agency. Page I of 1 1955 West 5200 South, Roy, Utah 84067 - Phone 801-776-5355 Fax 801-776-1345 Toll Free 1-888-488-5355 INTERMOUNTAINTesting services Inc. February 11, 2022 MTN WEST 1047 W. 600 N. #1 BRIGHAM CITY, UT 84302 CONCRETE SPECIAL INSPECTION REPORT Project #: (# 17553) MT WEST NATURE PARK RESTROOM Report Number: 350196 Inspection Date: 01/05/2022 Observation: INSPECTIONS WERE PROVIDED FOR IN THE FOLLOWING LOCATION: 1) RESTROOM WALL PANEL (PW -106). - PANEL SIZE — 7'-1 ''/z" X 8'-1 '/z" X 3" THICK. - PRIMARY REINFORCEMENT — W4 X W4 X W.225 WIRE MESH (REINFORCEMENT CENTERED IN PANEL THICKNESS). - ADDITIONAL BARS - #3 TRIM BARS AROUND OPENINGS, #3 HAIRPINS, #3 PERIMETER BARS AND EMBED PLATES AS PER DETAILS ON PW -106. 2) RESTROOM WALL PANEL (WP -101) - PANEL SIZE, 17' X 9'-1 %" XT' THICK. - PRIMARY REINFORCEMENT — SAME AS ABOVE. - ADDITIONAL BARS — #3 JAMS/LINTEL BARS, #3 HAIRPINS, #3 PERIMETER BARS, AND EMBED PLATES AS PER DETAILS ON WP -101. REBAR WAS INSPECTED FOR SIZE, GRADE, CONDITION, LOCATION, SPACING, COVER, CLEARANCE, HOOKS, BENDS AND LAP SPLICE. THE ABOVE NOTED WORK REQUIRING SPECIAL INSPECTION WAS IN GENERAL ACCORDANCE WITH THE APPROVED PLANS AND SPECIFICATIONS AND THE APPLICABLE WORKMANSHIP PROVISIONS OF THE UBC, ICBG, IBC, OR AWS SPECIFICATION(S). ISRAEL BRAVO ROSS YOSHIMURA IIT Special Inspector Inspection results related only to the items inspected as indicated above. This report shall not be reproduced, except in full, without the prior written approval of the agency. Page 1 of I 1955 West 5200 South, Roy, Utah 84067 - Phone 801-776-5355 Fax 801-776-1345 Toll Free 1-888-488-5355