HomeMy WebLinkAboutSTRUCTURAL LETTER OF APPROVAL - 22-00076 - 367 Talon Dr - Solar PanelsDate: 4 February 2022
Big Dog Solar Energy
620 Pheasant Ridge Dr
Chubbuck, ID 83202
Matthew Maroon Residence: 367 Talon Dr, Rexburg, ID 83440
Dear Sir/ Madam,
Design Method
Results
Structural Letter of Approval
Terra Engineering Consulting (TEC) has performed a structural load comparison for the
existing roof based on the existing and proposed load conditions, and determined that the
structure can support the additional weight of the proposed solar panel system. The attached
calculations are based off the assumptions that the existing structural components are in good
condition and that they meet industry standards. The design information and assumptions that
the calculations are based off are located in the attached References page. The contractor shall
notify TEC of any damage to the roof system encountered at the time of installation. The
design of the solar panel’s mounting hardware is to be provided by the manufacturer or
installer. Structural observation or construction inspections will not be performed by TEC or
their representatives.
This engineering analysis was performed in accordance with ASCE 7-16 design method. In
general, this design method is a comparison of the roof loads before and after the solar panel
installation. The attached engineering analysis is based on the before and after load comparison
and it does not include structural analysis of the existing structure nor its framing members.
The snow load in the area of the panels will be reduced due to the roof pitch and the solar
panel’s slippery surface, as justified in Section 7.4 in ASCE 7-16. Due to the reduction of
snow load the total roof loads and the stresses of the structural elements are decreased after the
solar panels are installed.
The total additional roof load of the solar panel system is 3 psf, and the typical 20 psf live load
will not be present in the area of the panels, as defined per Section 1607.13.5.1 in IBC 2018.
The slippery surface snow load reduction allowed in ASCE 7-16 is greater than the weight of
the solar system, therefore, the total combined vertical loads are reduced when considering the
worse case load combination (ASD). Regarding lateral wind loads, the solar panel structure is
considered to be “partially enclosed" due to the low profile of the panels (3" to 6") and airflow
restrictions below the panels caused by the pv frame, wiring, conduit, and frame brackets.
Because the system is considered to be partially enclosed additional wind pressure on the
structure is considered negligible. The attached connection calculations demonstrate the
proposed connection capability to withstand the applied uplift forces. The addition of total PV
system weight result in an increase under 10% of the total roof weight, and meets the seismic
requirements in Section 502.5 of 2018 IEBC. See the attached calculations for further details.
Page 1 of Matthew Maroon letter
1863 GOLDENROD WAY / NORTH SARATOGA SPRINGS, UT 84045 / T (801)-616-6204
General Instructions
Best Regards,
Terra Engineering Consulting, PLLC
Brice Somers, PE
President
TEC concludes that the installation of solar panels on existing roof will decrease the worst case
scenario total vertical loads and will reduce stresses in the structural members. The reduction
in total loads will increase the structure's existing factors of safety against failure. The
calculations performed to support these conclusions are attached to this letter.
Conclusions
The solar array mounting system shall be connected to every other truss/rafter (48" maximum
penetration spacing) in order to distribute the load evenly. The installer shall stagger the
connections into the roof framing to not overload any existing structural members. Installation
and waterproofing shall be performed within accepted industry standards.
Page 2 of Matthew Maroon letter
2/4/2022
1863 GOLDENROD WAY / NORTH SARATOGA SPRINGS, UT 84045 / T (801)-616-6204
References
Design Parameter
Load Combination: ASD
Risk Category: II
Ground Snow load: 50 psf
Roof Snow load: 35 psf
Design Wind Speed: 115 mph (3 sec gust) per ASCE 7-16
Seismic Design Category: D
Wind Exposure Category: C
Existing Roof Structure
Roof framing: 2x4 Pre-fab Trusses at 24” O.C.
Roof material: Composite shingles
Roof slope: 35°
Roof type: Gable
Solar Panels
Weight: 3 psf
Code: 2018 International Building Code/ International Existing Building Code, ASCE 7-16,
and National Design Specification for Wood Construction (NDS) 2015 Edition
Connections: (1) 5/16” Lag screw with 2.5” min. embedment into the framing at 48” O.C.
spaced along the rail
Page 3 of Matthew Maroon letter
1863 GOLDENROD WAY / NORTH SARATOGA SPRINGS, UT 84045 / T (801)-616-6204
Date:2/4/2022
Client:Matthew Maroon
Subject:Gravity load
Gravity load calculations
Snow load (S)Existing w/ solar panels
Roof slope (°):35 35
Ground snow load, pg (psf):50 50 ASCE 7-16, C7.2
Terrain category:C C ASCE 7-16, table 7.3-1
Exposure of roof:Fully exposed Fully exposed ASCE 7-16, table 7.3-1
Exposure factor, Ce:0.9 0.9 ASCE 7-16, table 7.3-1
Thermal factor, Ct:1.1 1.1 ASCE 7-16, table 7.3-2
Risk Category:II II ASCE 7-16, table 1.5-1
Importance Factor, Is:1 1 ASCE 7-16, table 1.5-2
Flat roof snow load, pf (psf):35.0 35.0 ASCE 7-16, equation 7.3-1
Minimum roof snow load, pm (psf):0 0 ASCE 7-16, equation 7.3-4
Roof Surface type:Other
Unobstructed
slippery surface ASCE 7-16, C7.4
Roof slope factor, Cs:1 0.58 ASCE 7-16, C7.4
Sloped roof snow load, ps [psf]:35.0 20.3
Roof dead load (D)
Roof pitch/12 8.4
Composite shingles 3 psf 1/2" Gypsum clg.0 psf
1/2" plywood 1 psf insulation 0.8 psf
Framing 3 psf M, E & Misc 1.5 psf
Roof DL without PV
arrays 11.4 psf
PV Array DL 3 psf
Roof live load (Lr)Existing w/ solar panels
Roof Live Load 20 0 2018 IBC, Section 1607.13.5.1
ASD Load combination:
Existing With PV array
D [psf]11.4 14.4 ASCE 7-16, Section 2.4.1
D+L [psf]11.4 14.4 ASCE 7-16, Section 2.4.1
D+[Lr or S or R] [psf]46.4 34.7 ASCE 7-16, Section 2.4.1
37.7 29.6 ASCE 7-16, Section 2.4.1
Maximum gravity load [psf]:46.4 34.7
Ratio proposed load to existing load:74.78%
The stresses due to gravity load in the area of the solar panels is reduced, allowing the
structure to remain unaltered.
ASCE 7-16, equation 7.4-1, Design
Snow Load (S)
D+0.75L+0.75[Lr or S or R] [psf]
Date:2/4/2022
Client:Matthew Maroon
Subject:
Wind Pressure Calculations
Basic wind speed (mph)115
Risk category II
Exposure category C
Roof type Gable
Figure for GCp values ASCE 7-16 Figure 30.3-2A-I
Zone 1 Zone 2 Zone 3
GCp (neg)-1 -1.2 -1.2
GCp (pos)0.9 0.9 0.9
zg (ft)900 (ASCE 7-16 Table 26.11-1)
α 9.5 (ASCE 7-16 Table 26.11-1)
Kzt 1 (ASCE 7-16 Equation 26.8-1)
Kh 0.9 (ASCE 7-6 Table 26.10-1)
Kd 0.85 (ASCE 7-16 Table 26.6-1)
Velocity Pressure,qh (psf)25.90 (ASCE 7-16 Equation 26.10-1)
Gcpi 0 (ASCE 7-16 Table 26.13-1)(0 for enclosed buildings)
Zone 1 Zone 2 Zone 3
W Pressure, (neg) [psf]-25.90 -31.08 -31.08
W Pressure, (pos) [psf]23.31 23.31 23.31
W Pressure, (Abs. max) [psf]25.9 31.08 31.08
Connection Calculations
Capacity
Connection type:Lag screw Lag screw diameter:5/16
Embedment (in):2.5
Framing grade:SPF#2 G:0.42
Capacity [lbs/in]:205 (2015 NDS table 12.2A)
Number of screws:1
Total capacity [lbs]:512.50
Demand
Anchor spacing:48 in
Anchor spacing in roof corners:48 in
Zone
( 0.6 W
Pressure,
psf), see
Note 1
Max.
tributary
area (ft^2)Max Uplift force (lbs)
1 15.5 11 170.9
2 18.6 11 205.1
3 18.6 11 205.1
(only changes if structure located
on a hill or ridge)
Connection Meets Demand
Wind load and
Connection
Note 1: 0.6W results from dominant ASD combo [0.6D+ 0.6W] (ASCE 7-16 2.4.1).