Corrections in the following table need to be applied before a permit can be issued
Review Report
Approved
# 21-00076
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
Pg 2 Free text Cody Jones : Building Open 2 2018 International Building Code.
Pg 2 Free text Cody Jones : Building Open 2 Plan review for foundation and the shell of the building only.
Pg 4 Free text Cody Jones : Building Open 4 Man doors to be installed to the side of overhead doors.
Doors must meet the requirements of IBC Section 1010.
Madison County - Commercial
Approval of plans does not constitute approval of variance from code
Powered by TCPDF (www.tcpdf.org)
JOB #
LOCATION
CUSTOMER
BUILDER
PROJECT
BUILDERS PO#
VP BUILDINGS
VARCO PRUDEN
FILENAME:
VPC VERSION:
DATE
DRAWN / CHECK
PAGE
VP Buildings 3200 Players Club Circle Memphis TN 38125
DRAWING RELEASE HISTORY
TYPE DATE DESCRIPTION
DRAWING INDEX
DRAWING TITLE PAGES
Cover Sheet
Anchor Rod Plan
Primary Structural
Secondary Structural
Covering
Special Drawings
Standard Erection Details
Codes and Loads
REVERSALS ON CONNECTIONS.
IT IS THE RESPONSIBILITY OF THE ERECTOR TO ENSURE PROPER BOLT TIGHTNESS IN ACCORDANCE WITH APPLICABLE
REGULATIONS. SEE RCSC SPECIFICATION FOR STRUCTURAL JOINTS USING HIGH STRENGTH BOLTS FOR MORE INFORMATION.
SEE ERECTION GUIDE FOR BOLT TIGHTENING INSTRUCTIONS. THE FOLLOWING CRITERIA MAY BE USED TO DETERMINE
THE BOLT TIGHTNESS (I.E.-SNUG TIGHT OR PRE-TENSION) UNLESS REQUIRED OTHERWISE BY LOCAL JURISDICTION
OR CONTACT.
PRE-TENSION A325 BOLTS IF BUILDING SUPPORTS A CRANE GREATER THAN 5 TON CAPACITY.
PRE-TENSION A325 BOLTS IF BUILDING SUPPORTS MACHINERY THAT CREATES VIBRATION, IMPACT, OR STRESS
PRE-TENSION A325 BOLTS IF LOCATED IN HIGH SEISMIC AREAS. FOR IBC BASED CODES; HIGH SEISMIC IS
PRE-TENSION ANY CONNECTION WITH DESIGNATION A325-SC. SLIP CRITICAL (SC) CONNECTIONS MUST BE FREE OF PAINT,
OIL, OR OTHER MATERIALS THAT REDUCE FRICTION AT CONTACT SURFACES. GALVANIZED OR LIGHTLY RUSTED SURFACES
IN CANADA ALL A325 AND A490 BOLTS SHALL BE "PRE-TENSIONED", EXCEPT FOR SECONDARY MEMBERS AND FLANGE
SECONDARY MEMBERS AND FLANGE BRACE CONNECTIONS ARE ALWAYS "SNUG TIGHTENED" UNLESS INDICATED OTHERWISE IN
ALL A490 BOLTS SHALL BE "PRE-TENSIONED". A325 BOLTS IN PRIMARY FRAMING AND BRACING CONNECTIONS MAY BE
" SNUG-TIGHT" EXCEPT AS FOLLOWS;
DESIGN CATEGORY D, E OR F. SEE CODES AND LOADS SECTION BELOW FOR DETAILS.
ARE ACCEPTABLE.
BRACES.
ERECTION DRAWING DETAILS.
GRADE 50A529, A572, A588, A992HOT ROLLED ANGLES
GRADE BA500HOLLOW STRUCTURAL SECTION (HSS)
HIGH STRENGTH BOLT TIGHTENING REQUIREMENTS
MATERIALS
GENERAL NOTES
ASTM DESIGNATION
GRADE 50 OR GRADE 80
GRADE 36 OR 50
GRADE 50
GRADE 60
GRADE 55A529, A572, A1011, A1018
A653, A1011
A572, A510
A36, A529, A572, A588, A992
A653, A792CLADDING
HOT ROLLED MILL SHAPES
BRACE RODS
COLD FORMED LIGHT GAGE SHAPES
3 PLATE WELDED SECTIONS
R
a division of BlueScope Buildings North America, Inc.
VP BUILDINGS
VARCO PRUDEN
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP BUILDINGS. IT IS
PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE APPLICABLE PURCHASE ORDER AND
MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT SHALL NOT BE MODIFIED, REPRODUCED OR USED
FOR ANY OTHER PURPOSE WITHOUT PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP BUILDINGS. IT IS
PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE APPLICABLE PURCHASE ORDER AND
MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT SHALL NOT BE MODIFIED, REPRODUCED OR USED
FOR ANY OTHER PURPOSE WITHOUT PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE GOOD QUALITY WORKMANSHIP
IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL
APPLICABLE VP BUILDINGS ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP BUILDINGS. IT IS
PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE APPLICABLE PURCHASE ORDER AND
MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT SHALL NOT BE MODIFIED, REPRODUCED OR USED
FOR ANY OTHER PURPOSE WITHOUT PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE GOOD QUALITY WORKMANSHIP
IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL
APPLICABLE VP BUILDINGS ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO THE WORK PRODUCT OF VP
AND DESIGN AND PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO THE PERFORMANCE OR
DESIGN OF ANY OTHER PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE REQUIREMENTS SPECIFIED
BY VP.
Planograph Details
Notes
C
INSPECTION AND TESTING
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP BUILDINGS. IT IS
PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE APPLICABLE PURCHASE ORDER AND
MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT SHALL NOT BE MODIFIED, REPRODUCED OR USED
FOR ANY OTHER PURPOSE WITHOUT PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE GOOD QUALITY WORKMANSHIP
IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL
APPLICABLE VP BUILDINGS ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO THE WORK PRODUCT OF VP
AND DESIGN AND PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO THE PERFORMANCE OR
DESIGN OF ANY OTHER PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE REQUIREMENTS SPECIFIED
BY VP.
SPECIAL INSPECTIONS AND TESTING REQUIRED BY AUTHORITY HAVING JURISDICTION (AHJ) DURING CONSTRUCTION AND/OR STEEL
FABRICATION IS THE RESPONSIBILITY OF THE OWNER OR OWNERS AUTHORIZED AGENT. WHEN REQUIRED, THE OWNER SHALL
EMPLOY A QUALITY ASSURANCE AGENCY (QAA) APPROVED BY THE AHJ. THE BUILDER IS RESPONSIBLE TO COORDINATE BETWEEN
THE QAA FIRM AND BBNA FABRICATION FACILITIES. THE TYPE AND EXTENT OF SPECIAL INSPECTIONS AND NDT WELD TESTING MUST
BE SPECIFICALLY STIPULATED IN CONTRACT DOCUMENTS OR BBNA WILL ASSUME SPECIAL INSPECTIONS AND/OR NDT TESTING ARE
WAIVED AS PERMITTED BY THE BUILDING CODE BASED ON BBNA FACILITIES IAS AC472 ACCREDITATION.
COVER SHEET
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
1
Tom Luthy 60x20
2020.4b
15:09:1212/23/2020
1 Anchor Rod Drawings 12/23/20 FOR CONSTRUCTION
2
3
4-5
6-15
16-24
25-31
32-35
Anchor Rod Drawings Rev 1 (page 5) 1/14/21 FOR CONSTRUCTION
Final Erection Drawings 1/14/21 FOR CONSTRUCTION
NOTE:
MASONRY WALLS ARE SELF-SUPPORTING
AND CANNOT BE ATTACHED TO THE VP
FRAMES OR SECONDARY MEMBERS TO
ENSURE NO TRANSFER OF LOADS BETWEEN
NBVP MASONRY AND VP STRUCTURE
VP Erection Guides
BASIC ERECTION GUIDE 4001
BASIC PANELS AND ACCESSORIES ERECTION GUIDE 4003
31
1/15/21 01/15/2021
I am approving this document
2021.01.15 09:22:56-08'00'
WHEN MULTIPLE BUILDINGS ARE INVOLVED, SPECIFIC LOAD FACTORS FOR DIFFERING OCCUPANCIES, BUILDING DIMENSIONS,
Codes and Loads
HEIGHTS, FRAMING SYSTEMS, ROOF SLOPES, ETC., MAY RESULT IN DIFFERENT LOAD APPLICATION FACTORS THAN
INDICATED BELOW. SEE CALCULATIONS FOR FURTHER DETAILS. WIND LOADS ARE APPLIED TO OVERALL BUILDING ENVELOPE.
COMMON WALLS BETWEEN CONNECTED SHAPES ARE NOT SUBJECT TO EXTERNAL WIND LOADS.
City: Rexburg County: Madison State: Idaho Country: United States
Building Code: 2017 Idaho State Building Code
Building Code
Structural: 10AISC - ASD Rainfall: I: 4.00 inches per hour
Based on Building Code: 2015 International Building Code Cold Form: 12AISI - ASD f'c: 3000.00 psi Concrete
Building Risk/Occupancy Category: II (Standard Occupancy Structure)
Collateral Gravity:1.00 psf
Dead and Collateral Loads
Collateral Uplift: 0.00 psf
Wind Load
Wind Speed: Vult: 115.00 (Vasd: 89.08) mph
The 'Envelope Procedure' is Used
Wind Exposure: C - Kz: 0.860
Parts Wind Exposure Factor: 0.860
Wind Enclosure: Enclosed
Topographic Factor: Kzt: 1.0000
NOT Windborne Debris Region
Base Elevation: 0/0/0
Primary Zone Strip Width: 2a: 12/0/0
Parts / Portions Zone Strip Width: a: 6/0/0
Basic Wind Pressure: q: 24.76 psf
Roof Covering + Second. Dead Load: 1.97 psf
Material Dead Weight
Frame Weight (assumed for seismic):2.50 psf
Snow Load
Ground Snow Load: pg: 50.00 psf
Flat Roof Snow: pf: 31.50 psf
Design Snow (Sloped): ps: 31.50 psf
Rain Surcharge: 0.00
Specified Minimum Roof Snow: 35.00 psf (USR)
Exposure Factor: 1 Fully Exposed - Ce: 0.90
Snow Importance: Is: 1.000
Thermal Factor: Heated - Ct: 1.00
Ground / Roof Conversion: 0.70
Obstructed or Not Slippery
Roof Live Load: 20.00 psf Reducible
Roof Live Load
Seismic Load
Lateral Force Resisting Systems using Equivalent Force Procedure
Mapped MCE Acceleration: Ss: 43.00 %g
Mapped MCE Acceleration: S1: 14.30 %g
Site Class: Stiff soil (D)
Seismic Importance: Ie: 1.000
Design Acceleration Parameter: Sds: 0.4174
Design Acceleration Parameter: Sd1: 0.2124
Seismic Design Category: D
Seismic Snow Load: 6.30 psf
% Snow Used in Seismic: 20.00
Diaphragm Condition: Rigid
Fundamental Period Height Used: 17/3/0
Transverse Direction Parameters
Ordinary Steel Moment Frames
Redundancy Factor: Rho: 1.00
Fundamental Period: Ta: 0.2733
R-Factor: 3.50
Overstrength Factor: Omega: 3.00
Deflection Amplification Factor: Cd: 3.00
Base Shear: V: 0.1193 x W
Longitudinal Direction Parameters
Ordinary Steel Concentric Braced Frames
Redundancy Factor: Rho: 1.30
Fundamental Period: Ta: 0.1693
R-Factor: 3.25
Overstrength Factor: Omega: 3.00
Deflection Amplification Factor: Cd: 3.25
Base Shear: V: 0.1284 x W
Roof: A
Shop
X
Y
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C CODES AND LOADS
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
12/23/2020
NHL
2
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
12/23/2020 15:09:12
Application of Specified Minimum Uniform Roof Snow loads, “SMS”:
- The specified minimum uniform roof snow will be applied as a separate roof
load check, combined with dead loads only.
- It is considered the net sloped roof load, i.e., none of the other snow
load related factors such as Importance, Thermal, Unobstructed Slippery, Ex-
posure, etc., would apply.
- It is not considered in conjunction with the bracing second order effects.
Note:
This building has been Designed with a Collateral Gravity Loading of only 1
psf. Do not exceed 1 psf of Collateral Gravity when hanging equipment from
the purlins.
01/15/2021
2018 International Building
Code.
Plan review for foundation and the shell of the building only.
BUILDER/CONTRACTOR RESPONSIBILITIES
VP Buildings follows the guidelines as outlined in the AISC and MBMA Codes of Standard Practice.
PANELS
Oil canning is an inherent characteristic of cold formed steel panels. It is the result of several
factors that include induced stresses in the raw material delivered to VP, fabrication methods,
installation procedures, and post installation thermal forces. Thru fastened panels will exhibit some
dimpling when installed, especially when insulation is installed between panels and secondary
supports. Dimpling can be minimized by careful installation, taking care not to over drive fasteners.
springing back into place. All panels experience this action to some degree, especially with
concealed clip Standing Seam panels. Roof rumble noise may be minimized by providing a layer
of blanket insulation between the panels and any hard support surface such as steel secondary
members, substrates such as plywood, steel decking, or rigid board insulation. A minimum of
3 inch thick blanket is recommended over steel secondary members, or 2 inch over substrates.
Oil canning, dimpling, and roof rumble do not affect the structural integrity or weather tightness
of the panels and is not grounds for rejection of panels.
RAIN WATER RUNOFF
Drainage systems must be designed by the project professional to comply with code requirements.
VP is not responsible for drainage designs, overflow scuppers, down piping, etc. The project
professional and contractor are responsible to ensure that primary drains and overflow devices
such as scuppers and auxiliary drains are provided as required for the required rain intensity at
Roof rumble is a phenomenon that is caused by wind gusts lifting up on the roof panels and then
the building perimeter and at valley conditions to prevent ponding.
However, it is imperative that installed Standing Seam panels be secured to the secondary
The Standing Seam joint detail is designed with an interlocking feature for ease of installation.
structural members and properly seamed prior to departure from the job site each day.
SKYLIGHTS
Local building departments may require added fall restraint due to conditions that may affect the
skylight structural integrity. It is the responsibility of the builder to determine and provide any
added fall restraint under the skylight as may be required by your building department.
STEEL SHOP COAT
The purpose of VP's shop coat is to provide protection for the steel members during
transportation, during temporary job site storage and during erection. Standard shop formulation
is not designed to perform as a finish coat when exposed to environmental conditions. Members
shall be kept free of the ground and properly drained during job site storage. It is the Builder's
responsibility to ensure that if a finish coat is being applied over VP shop coat that the
painting contractor verifies compatibility between his finish coat and VP's shop coat.
VP Buildings standard product specifications, design, fabrication, quality criteria shall govern all work
unless stipulated otherwise in the contract documents. In case of discrepancies between
VP Buildings structural plans and plans for other trades, VP Buildings structural plans shall govern.
It is the responsibility of the Builder to obtain approvals and permits from all governing agencies and
jurisdictions as required. Approval of VP Buildings drawings constitutes the builders acceptance of VP
interpretation of the contract purchase order. Unless specific design criteria concerning interface
design and details are furnished as part of the contract, VP Buildings design assumptions shall govern.
CONSTRUCTION & ERECTION RESPONSIBILITY
The Builder is responsible for construction in strict accordance with VP Buildings "FOR CONSTRUCTION"
drawings and all applicable product installation guides. VP is not responsible for work done from any
other VP drawings that are not marked "FOR CONSTRUCTION", nor any drawings prepared by others.
As erected field assemblies of members shall be as specified in MBMA Code of Standard Practice
(in Canada - CSA S16), which require L/500 tolerance of installed members. Occasional
field work including shimming, cutting, coping, and drilling for final fit-up are considered part of
erection. Specified field work and field welding conditions indicated on these drawings shall
also be included in the erectors scope of work. See Erection Guide for shimming procedure.
For building with top riding bridge cranes see Crane Data drawing for column plumb tolerance.
The building erector shall be properly licensed and experienced in erecting metal building systems.
The Builder is responsible for having knowledge of, and shall comply with, all OSHA requirements
and all other governing site safety criteria. The builder is responsible for designing, supplying,
locating and installing temporary supports and bracing during erection of the building. VP
bracing is designed for code required loads after building completion and shall not be considered
as adequate erection bracing. See Erection Guide.
EXISTING STRUCTURES
BRACING
Tension brace rods work in pairs to balance forces caused by initial tensioning. Care must be
taken while tightening brace rods so as not to cause accidental or misalignment of components.
All rods must be installed loose and then tightened. Rods should not exhibit excessive sag. For
long or heavy rods, or angles it may be necessary to support the rods at mid-bay by suspending
them from secondary members.
Bracing for seismic or wind loading of objects or equipment that are not a part of the VP
structure must be designed by a qualified professional to deliver lateral loads to primary frames
and rod bracing struts. Equipment bracing and suspension connections must not impose torsion
or minor axis loads, or cause local distortion in any VP components. VP accepts no
responsibility for design or installation of bracing systems not furnished by VP.
FIELD WELDING
All field welding shall be done at the direction of a design professional, and done in accordance
with governing requirements (AWS in USA, CWB in Canada) by welders qualified to perform the
welding as directed by the applicable welding procedure specification (WPS). A WPS shall be
prepared by the contractor for each welding variation specified. The contractor is responsible for
any special welding inspection as required by local jurisdiction. Filler metal shall be
70 ksi (480 MPa) tensile strength. For welds in high seismic force resisting system
(Seismic Cat D, E or F), minimum Charpy V-Notch toughness shall meet AISC-341 criteria
(20 ft-lbs min @ 0Deg F). Interpass temperatures shall not exceed 550Deg F (300Deg C).
DELIVERIES
It is the responsibility of the builder to have adequate equipment available at the job site to
unload trucks in a safe and timely manner. The Builder will be responsible for all retention
charges from carriers as a result of job site unloading delays.
Claims for damage or shorts MUST be noted on the Bill-of-Lading or delivery
receipt and filed against the carrier by the consignee as per VP's Terms of Sales (F.O.B. Plant)
under the Uniform Commercial Code. It is critical that damages or shorts be noted on the
Bill-of-Lading or you have little recourse with the carrier. Immediately upon delivery of material,
material quantities are verified by the Builder against quantities billed on the shipping document.
Neither the Manufacturer nor the carrier is responsible for material shortages against quantities
billed on the shipping document if such shortages are not noted on the shipping documents upon
delivery of material and acknowledged by the carriers agent. For materials concealed in bundles,
boxes, or crates, shortages must be reported immediately upon unpacking. Should products get
wet, bundled and crated materials must be unpacked and unbundled immediately to provide
drainage of trapped moisture. See Erection Guide for proper job site storage procedure.
SEALANTS
Sealants shall be applied in strict accordance with VP details or weather tightness will be compromised.
Sealant must be applied in temperatures and weather conditions consistent with labeling.
INDEPENDENT MEZZANINES
Independent mezzanines must be designed by a professional engineer. The engineer must ensure
that proper isolation from the VP building has been provided to avoid structural damage due to
differential movements, or inadvertently apply loads to the VP structure. VP accepts no
responsibility for the design of the independent mezzanine.
FIRE CODE COMPLIANCE
It is the responsibility of the project design professional and builder to comply with local fire code
regulations including consideration of, but not limited to, building use and occupancy, all building
construction materials, separation requirements, egress requirements, fire protection systems, etc.
Builder shall advise VP of any special requirements to be furnished by VP.
FIELD MODIFICATIONS
Modifications to this building from details and instructions contained on these drawings must be
approved in writing by VP Buildings engineers, or other licensed structural engineer. This includes,
but is not limited to, removal of roof or wall cladding, removing or moving any flange braces or
rod braces, cutting of openings for doors, windows or RTU's, correction of fabrication errors, etc.
The owner shall not impose loads to this structure beyond what is specified for this building in
the contract documents. VP Buildings accepts no responsibility for the consequences of any
unauthorized additions, alterations, or added loads to this structure.
If the builder intends to invoice VP Buildings for modifications in excess of $1000, The builder
must notify VP Buildings immediately, and obtain a Work Authorization from VP Buildings prior to
proceeding. All final claims must be submitted to VP Buildings with all supporting documentation
within 30 days of the building completion. Claims submitted without work authorizations, or after
30 days will not be accepted. Correction of minor misfits, shimming and plumbing, moderate
amount of reaming, drilling, chipping / cutting and minor welding are considered by Code of
Standard Practice to be part of erection are not subject to claim reimbursement.
CONCRETE/MASONRY/CONVENTIONAL STUD WALLS
The engineer responsible for the design of the wall system is responsible for coordinating with, or
specifying to VP Buildings, any wall to steel compatibility issues such as drift and deflection
compatibility, special base details, and wall to VP steel connections. All fasteners, sealant and
counter flashing of wall systems are to be provided by contractor. The engineer responsible for
the wall shall design the anchorage to VP supporting elements consistent with Code required forces.
Dade Co. Product Approval (www.miamidade.gov/buildingcode)
Approved Products Listed Under Varco Pruden Buildings, Inc.
Underwriter's Laboratory Approvals (Available only when specified in contract)
SSR Roof-UL#TGKX-113; SSR Composite Roof Class 90-UL#TGKX-113A;
SSR Roof w/Super Block; Class 90-UL#TGKX-328;
Panel Rib Roof UL Class 60-UL#TGKX-60; Panel Rib Roof UL Class 90-UL#TGKX-64;
VP SLR II Roof Class 90-UL#TGKX-90, -180, -435, -435A, -176, -238, -238A, -238B
Factory Mutual Approved Assemblies (Available only when specified in contract)
SSR Roof Systems are approved in various type applications and listed in FM Approval Guide.
24 Ga SSR (0.0227" Nominal), is available in Class 1-60, 1-75, 1-90. 22Ga SSR (0.0277"
Nominal), is available in Class 1-75, 1-90-, 1-120.
ICC Evaluation Reports (www.icc-es.org)
SSR Roof System - #ESR-2527
SLR II Roof Systems are approved in various type applications and listed in FM Approval Guide.
24 Ga SLR II (0.0227" Nominal), is available in Class 1-75 and 1-120.
State of Florida Product Approvals (www.floridabuilding.org)
VP TextureClad - See Transamerican Structuroc, Inc.
VP TextureClad - See Transamerican Structuroc, Inc.
Approved Products Listed Under VP Buildings, Inc.
(www.cwbgroup.org)
Canadian CSA A660 Certifications
Listed under BlueScope Buildings North America, Inc.
IAS AC472 Approvals: (www.iasonline.org/services/metal-building-inspection)
Fabricator Approvals
MO#E-2010007736; NC#F-0998; OK#CA4170PE; SD#C-1787; TX#F4828; WV#C03059-00;
Engineering Certifications of Authorization
USA--AR#576; FL#30427; ID#C-2470; IL#184-002649; KS#E-29; MS#E-0592;
CAN--AB#P08900; NS#30123; ON#100148796; and YT#PP134
VP BUILDINGS ACCREDITATIONS AND APPROVALS
City of Los Angeles, CA #FB00031; City of Houston, TX 767 & 429;
City of Phoenix, AZ C19-02008; Clark County, NV 43 & 833, San Bernardino County, CA 289
Listed under BlueScope Buildings North America, Inc.
Listed under Varco Pruden Buildings, a Division of BlueScope Buildings North America, Inc.
IAS AC472 Approvals: (www.iasonline.org/services/metal-building-inspection)
Design Approvals
SIGNAGE
The Builder is responsible for furnishing signs as required by Code and the Building Department,
including but not limited to, exits, occupancy limits, floor loading limits, and bulk storage limits.
Floor loading signs shall clearly indicate maximum floor live load permitted.
Bulk storage facilities shall have signs clearly posted on all loaded walls indicating the type
of commodity stored and the maximum storage height. Signs shall be clearly visible when
building is fully loaded to design level. Overloading of floors or walls may result in failure.
State of Utah, City of Richmond, CA.
VP engineers are not Project Engineers or Engineer of Record for the overall project. VP engineering
supply sealed engineering design data and drawings for VP supplied material as part of the overall
project for use by others to obtain permits, approvals, and coordinate with other trades. All interface
and/or compatibility of any materials not furnished by VP are to be considered and coordinated by
the builder or A/E firm.
VP must be advised of any structure that is within 20 ft. of VP's building. Load effects from
snow drifting, wind effects, and seismic separation must be considered for both the new and
existing structures. VP has designed the new VP building for these effects. The owner/builder are
responsible for employing a Professional Engineer to review and verify the existing structure for all
load effects from the adjacent VP building.
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C ERECTION NOTES
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
12/23/2020
NHL
3
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
12/23/2020 15:09:14
01/15/2021
1 6"
Dimension Key
1 6"
Dimension Key
<*>
<*><*>
<*>
6 0 '-0 "
200'-0"
1 3 '-0 "
2 5 '-0 "
2 2 '-0 "
2 2 '-0 "
2 5 '-0 "
1 3 '-0 "
1 24'-6"25'-0"25'-0"25'-0"25'-0"25'-0"25'-0"24'-6"1
5'-6"14'-0"
J=8.50 5'-6"5'-6"14'-0"
J=8.50 5'-6"5'-6"14'-0"
J=8.50 5'-6"5'-6"14'-0"
J=8.50 5'-6"
D1
D1
D2
D2
D3
D3
D4
D3
D4
D3
D3
D3
D3
D3
D4
D3
D4
D3
D1
D1
D2
D2
D5 D5 D5 D5
ANCHOR ROD PLAN
A B L
B
C
D B L
1
BL
2 3 4 5 6 7 8 9
BL
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C ANCHOR ROD PLAN
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
12/23/2020
NHL
4
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
<*> THE BUILDING IS DESIGNED WITH BRACING DIAGONALS IN THE DESIGNATED
BAYS. COLUMN BASE REACTIONS, BASE PLATES AND ANCHOR RODS ARE
AFFECTED BY THIS BRACING AND DIAGONALS MAY NOT BE RELOCATED
WITHOUT CONSULTING THE BUILDING SUPPLIERS ENGINEER.
Finished Floor Elevation = 100'-0" (Unless Noted Otherwise)
12/23/2020 15:09:15
NOTE:
THE BUILDER MUST BE AWARE THAT
CORNER COLUMNS NEED TO BE ERETED
BEFORE MAONRY WALL OR TAKE
PRECAUTIONS FOR BOLTING PLATE ACCESS
LOW SIDE
HIGH SIDE
01/15/2021
Man doors to be installed to the side of overhead doors.
Doors must meet the requirements of IBC Section 1010.
D1 (4)3/4" Dia. GR36 Anchor Rods
Plate W=8" L=1'-1"
Dim: A=1'-0"
Elev.=101'-0"
D2 (4)3/4" Dia. GR36 Anchor Rods
Plate W=8" L=11"
Dim: A=4 1/8"
Gage=5" Pitch=5" Edge Out=3"
Elev.=101'-0"
D3 (4)3/4" Dia. GR36 Anchor Rods
Plate W=8" L=1'-1"
Dim: A=1'-0"
Elev.=100'-0"
D4 (4)3/4" Dia. GR36 Anchor Rods
Plate W=9" L=1'-1"
Dim: A=1'-0"
Elev.=100'-0"
D5 (4)3/4" Dia. GR36 Anchor Rods
Plate W=8" L=1'-5"
Dim: A=11 1/2" B=1'-1"
Gage=5" Pitch=5" Edge Out=4"
Elev.=100'-0"
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C ANCHOR ROD PLAN - DETAILS
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
12/23/2020
NHL
5
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1/14/2021 14:04:01
1
1 1/14/21 NHL BASE PLATE REVISED
INFO:L,DimA,Edge Out
01/15/2021
Id
Rod, Strut, and Misc. Connection Bolts
Qty Grade Bolt Diam.Bolt Length PartNo Washer
1 2 F1852 3/4"2"0097388 Yes
1 6"
Dimension Key
Part
Bracing Part Schedule
Qty Length Detail
03RT3303 4 33'-3"BR02K1,BR01G2
03RS3504 4 35'-4"BR01G2
04RT2700 4 27'-0"BR01G2,BR02K1
3BSE22106142 23'-4 3/4"BR15L1
0 3 R T 3 3 0 3
0
3
R
T
3
3
0
3
0 3 R S 3 5 0 4
0
3
R
S
3
5
0
4
0 4 R T 2 7 0 0
04RT2700
1 13BSE2210614
0 3 R T 3 3 0 3
0
3
R
T
3
3
0
3
0 3 R S 3 5 0 4
0
3
R
S
3
5
0
4
0 4 R T 2 7 0 0
04RT2700
1 13BSE2210614
60
'
-
0
"
200'-0"
13
'
-
0
"
25
'
-
0
"
22
'
-
0
"
22
'
-
0
"
25
'
-
0
"
13
'
-
0
"
1 24'-6"25'-0"25'-0"25'-0"25'-0"25'-0"25'-0"24'-6"1
CX001
RB
X
0
0
1
RB
X
0
0
2
RB
X
0
0
3
CX002
EP
X
0
0
1
EP
X
0
0
2
CX003
RB
X
0
0
4
RB
X
0
0
5
CX004
CX005CX005
RB
X
0
0
6
RB
X
0
0
7
CX006
CX007CX007
RB
X
0
0
6
RB
X
0
0
8
CX006
CX003
RB
X
0
0
4
RB
X
0
0
5
CX004
CX003
RB
X
0
0
4
RB
X
0
0
5
CX004
CX005CX005
RB
X
0
0
6
RB
X
0
0
7
CX006
CX008CX008
RB
X
0
0
6
RB
X
0
0
8
CX006
CX009
RB
X
0
0
9
RB
X
0
1
0
RB
X
0
1
1
CX010
EP
X
0
0
3
EP
X
0
0
4
CX011 RBX012 CX011 CX011 RBX012 CX011
A BL
B
C
D BL
1
BL
2 3 4 5 6 7 8 9
BL
PRIMARY AND ROOF BRACING PLAN
HIGH SIDE
LOW SIDE
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C PRIMARY AND ROOF BRACING PLAN
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
6
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1. USE 1/2 X 1 1/2 A325T BOLT (49080) AND NUT (47120)
W/O WASHERS. SNUG TIGHTEN BOLTS FOR ALL SECONDARY CONNECTIONS,
SECONDARY CLIP CONNECTIONS, AND FLANGE BRACE CONNECTIONS,
UNLESS NOTED OTHERWISE.
2. SLOT REINFORCEMENT PLATES NEED NOT BE LOCATED ON THE SAME
SIDE OF THE WEB AS THE HILLSIDE WASHER.
Shape Name = Shop
1/14/2021 16:02:33
01/15/2021
Part
Frame Member Schedule
Mem Width Thick WebThk.Depth1 Depth2 Approx.Lgth Approx.Weight Detail
CX001 1 5.0000 .1875 .1345 1'-0"1'-0"16'-9 1/8"228#
RBX001 2-5 5.0000 .2500 .1345 10"10"25'-3 9/16"338#
RBX002 6 5.0000 .1875 .1345 10"10"15'-5 3/8"176#
RBX003 7-9 5.0000 .1875 .1345 10"10"17'-6 3/4"198#
CX002 10 5.0000 .1875 .1345 1'-0"1'-0"13'-6 5/16"184#
EPX001 11 5.0000 .1345 .1345 10"10"15'-0 9/16"154#BR25CA
EPX002 12 5.0000 .1345 .1345 10"10"14'-0 1/16"145#BR25CA
Id
Bolt Connection & Plate Schedule
Qty Grade Bolt Bolt Plate Rows Rows Tension Washer PartNo
Dia.Length Thick.Out In Bolt
A 4 A325 1/2"1 1/2"3/8"1 1 49080
B 4 F1852 3/4"1 3/4"1/4"1 1 Yes Yes 0097387
<S> - (2) Washers (095872) req'd at Flange Brace to Secondary.
1 8 1/2"
Dimension Key
2 4'-0"
3 3'-6"
4 2 @ 4'-3"
5 2 @ 3'-3 5/16"
6 4'-6"
Horiz. Clearance between members 1(CX001) and 10(CX002): 56'-7"
Frame Clearances
Vert. Clearance at member 1(CX001): 16'-10 1/8"
Vert. Clearance at member 10(CX002): 14'-6 5/16"
Vert. Clearance at member 11(EPX001): 16'-0 1/2"
Vert. Clearance at member 12(EPX002): 14'-11 15/16"
Finished Floor Elevation = 100'-0" (Unless Noted Otherwise)
22'-0"25'-0"13'-0"
D
BL
A
BL
CL
C
CL
B
60'-0"
FRAME CROSS SECTION AT FRAME LINE(S) 1
KMA1
(2)WBBC2
1
GFB2006
2
3
5'
-
0
"
6'
-
0
"
GF
B
2
0
3
7
GF
B
2
0
3
7
<
S
>
GF
B
2
0
3
7
<
S
>
GF
B
2
0
3
7
GF
B
2
0
3
7
<
S
>
GF
B
2
0
3
7
<
S
>
GF
B
2
0
3
7
4
9 @ 5'-0"
5
KMA1
(2)WBBC2
1
GFB2006
2
3
6
2
18
'
-
6
"
16
'
-
0
"
60'-0 5/8" 0.500:12
CX
0
0
1
RBX001
RBX002 RBX003
CX
0
0
2
EP
X
0
0
1
EP
X
0
0
2
A
B
B
A
A
A
101'-0"101'-0"101'-0"101'-0"
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C FRAME CROSS SECTION AT FRAME LINE(S) 1
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
7
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1. USE 1/2 X 1 1/2 A325T BOLT (49080) AND NUT (47120)
W/O WASHERS. SNUG TIGHTEN BOLTS FOR ALL SECONDARY CONNECTIONS,
SECONDARY CLIP CONNECTIONS, AND FLANGE BRACE CONNECTIONS,
UNLESS NOTED OTHERWISE.
2. SLOT REINFORCEMENT PLATES NEED NOT BE LOCATED ON THE SAME
SIDE OF THE WEB AS THE HILLSIDE WASHER.
Shape Name = Shop Wall 4, Frame 1
1/14/2021 16:02:34
01/15/2021
Part
Frame Member Schedule
Mem Width Thick WebThk.Depth1 Depth2 Approx.Lgth Approx.Weight
CX003 1 5.0000 .3750 .1875 1'-0"2'-11"17'-9 1/8"591#
RBX004 2 5.0000 .3750 .1875 2'-8"1'-4"26'-5 5/8"729#
3 5.0000 .3125 .1644 1'-4"2'-8"
RBX005 4 5.0000 .3125 .1644 2'-8"1'-4"29'-11 1/16"816#
5 5.0000 .3125 .1875 1'-4"2'-8"
CX004 6 5.0000 .3750 .1644 1'-0"2'-9"12'-9"367#
Id
Bolt Connection & Plate Schedule
Qty Grade Bolt Bolt Plate Rows Rows Tension Washer PartNo
Dia.Length Thick.Out In Bolt
A 8 F1852 3/4"2 1/4"1/2"3 1 Yes Yes 0097389
B 12 F1852 3/4"2"3/8"2 4 Yes Yes 0097388
C 10 F1852 3/4"2 1/4"1/2"3 2 Yes Yes 0097389
1 8 1/2"
Dimension Key
2 2'-9"
3 3'-3"
4 2 @ 4'-3"
5 2 @ 3'-3 5/16"
6 4'-6"
7 4'-0"
Horiz. Clearance between members 1(CX003) and 6(CX004): 52'-11"
Frame Clearances
Vert. Clearance at member 1(CX003): 14'-11 1/8"
Vert. Clearance at member 6(CX004): 12'-9"
Finished Floor Elevation = 100'-0" (Unless Noted Otherwise)
D
BL
A
BL
60'-0"
FRAME CROSS SECTION AT FRAME LINE(S) 2, 5 & 6
KMA1
(2)WBBC2
(2)KMA1
(4)WBBC2
1
GFB2066
(2)GFB3077
7'
-
6
"
5'
-
0
"
2
3
EA
P
1
ES
B
S
B
ES
B
S
B
(2
)
G
F
B
4
0
0
7
GF
B
2
0
8
1
GF
B
3
0
0
0
GF
B
4
0
0
7
GF
B
3
1
1
1
GF
B
2
0
8
1
GF
B
2
0
9
7
(2
)
G
F
B
3
0
2
1
4
9 @ 5'-0"5
KMA1
(2)WBBC2
(2)KMA1
(4)WBBC2
1
GFB2066
(2)GFB3077
7'
-
6
"
6
7
18
'
-
6
"
16
'
-
0
"
60'-0 5/8" 0.500:12
C X 0 0 3
R B X 0 0 4
R B X 00 5
C
X
0
0
4
A
B
C
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C FRAME CROSS SECTION AT FRAME LINE(S) 2, 5 & 6
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
8
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1. USE 1/2 X 1 1/2 A325T BOLT (49080) AND NUT (47120)
W/O WASHERS. SNUG TIGHTEN BOLTS FOR ALL SECONDARY CONNECTIONS,
SECONDARY CLIP CONNECTIONS, AND FLANGE BRACE CONNECTIONS,
UNLESS NOTED OTHERWISE.
2. SLOT REINFORCEMENT PLATES NEED NOT BE LOCATED ON THE SAME
SIDE OF THE WEB AS THE HILLSIDE WASHER.
Shape Name = Shop Wall 4, Frame 2
1/14/2021 16:02:36
NOTE:
Installation of tension control bolts may not be possible in areas where ex-
treme pitch,stiffener location,beam depth or other obstructions may occur.
In these cases,substitution of nuts and bolts tightened with wrenches are
required.
01/15/2021
Part
Frame Member Schedule
Mem Width Thick WebThk.Depth1 Depth2 Approx.Lgth Approx.Weight
CX005 1 8.0000 .3750 .1644 1'-0"2'-6 3/8"17'-9 1/8"705#
2 8.0000 .3750 .1875 2'-6 3/8"2'-7"
RBX006 3 5.0000 .3750 .1875 2'-9"1'-5"26'-8 5/8"750#
4 5.0000 .3125 .1644 1'-5"2'-8"
RBX007 5 5.0000 .3125 .1644 2'-8"1'-4"30'-0 1/16"841#
6 5.0000 .3125 .1875 1'-4"2'-8"
CX006 7 5.0000 .3750 .1644 1'-0"2'-9"12'-9"369#
Id
Bolt Connection & Plate Schedule
Qty Grade Bolt Bolt Plate Rows Rows Tension Washer PartNo
Dia.Length Thick.Out In Bolt
A 10 F1852 3/4"2 1/4"1/2"3 2 Yes Yes 0097389
B 12 F1852 3/4"2"3/8"2 4 Yes Yes 0097388
1 8 1/2"
Dimension Key
2 2'-9"
3 3'-3"
4 2 @ 4'-3"
5 2 @ 3'-3 5/16"
6 4'-6"
7 4'-0"
Horiz. Clearance between members 1(CX005) and 7(CX006): 53'-3 5/8"
Frame Clearances
Horiz. Clearance between members 2(CX005) and 7(CX006): 53'-3"
Vert. Clearance at member 2(CX005): 14'-7 9/16"
Vert. Clearance at member 7(CX006): 12'-9"
Finished Floor Elevation = 100'-0" (Unless Noted Otherwise)
D
BL
A
BL
60'-0"
FRAME CROSS SECTION AT FRAME LINE(S) 3 & 7
1
7'
-
6
"
5'
-
0
"
2
3
EA
P
1
ES
B
S
B
EA
P
1
ES
B
S
B
(2
)
G
F
B
4
0
2
7
GF
B
2
0
8
1
GF
B
3
0
0
0
GF
B
4
0
0
7
GF
B
3
1
1
1
GF
B
2
0
8
1
GF
B
2
0
9
7
(2
)
G
F
B
3
0
2
1
4
9 @ 5'-0"
5
KMA1
(2)WBBC2
(2)KMA1
(4)WBBC2
1
GFB2066
(2)GFB3077
7'
-
6
"
6
7
18
'
-
6
"
16
'
-
0
"
60'-0 5/8" 0.500:12
C X 0 0 5
C X 0 0 5
R B X 0 0 6
R B X 0 0 7
C
X
0
0
6
A
B
A
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C FRAME CROSS SECTION AT FRAME LINE(S) 3 & 7
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
9
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1. USE 1/2 X 1 1/2 A325T BOLT (49080) AND NUT (47120)
W/O WASHERS. SNUG TIGHTEN BOLTS FOR ALL SECONDARY CONNECTIONS,
SECONDARY CLIP CONNECTIONS, AND FLANGE BRACE CONNECTIONS,
UNLESS NOTED OTHERWISE.
2. SLOT REINFORCEMENT PLATES NEED NOT BE LOCATED ON THE SAME
SIDE OF THE WEB AS THE HILLSIDE WASHER.
Shape Name = Shop Wall 4, Frame 3
1/14/2021 16:02:37
NOTE:
Installation of tension control bolts may not be possible in areas where ex-
treme pitch,stiffener location,beam depth or other obstructions may occur.
In these cases,substitution of nuts and bolts tightened with wrenches are
required.
01/15/2021
Part
Frame Member Schedule
Mem Width Thick WebThk.Depth1 Depth2 Approx.Lgth Approx.Weight
CX007 1 8.0000 .3750 .1644 1'-0"2'-6 3/8"17'-9 1/8"705#
2 8.0000 .3750 .1875 2'-6 3/8"2'-7"
RBX006 3 5.0000 .3750 .1875 2'-9"1'-5"26'-8 5/8"750#
4 5.0000 .3125 .1644 1'-5"2'-8"
RBX008 5 5.0000 .3125 .1644 2'-8"1'-4"30'-0 1/16"841#
6 5.0000 .3125 .1875 1'-4"2'-8"
CX006 7 5.0000 .3750 .1644 1'-0"2'-9"12'-9"369#
Id
Bolt Connection & Plate Schedule
Qty Grade Bolt Bolt Plate Rows Rows Tension Washer PartNo
Dia.Length Thick.Out In Bolt
A 10 F1852 3/4"2 1/4"1/2"3 2 Yes Yes 0097389
B 12 F1852 3/4"2"3/8"2 4 Yes Yes 0097388
1 8 1/2"
Dimension Key
2 2'-9"
3 3'-3"
4 2 @ 4'-3"
5 2 @ 3'-3 5/16"
6 4'-6"
7 4'-0"
Horiz. Clearance between members 1(CX007) and 7(CX006): 53'-3 5/8"
Frame Clearances
Horiz. Clearance between members 2(CX007) and 7(CX006): 53'-3"
Vert. Clearance at member 2(CX007): 14'-7 9/16"
Vert. Clearance at member 7(CX006): 12'-9"
Finished Floor Elevation = 100'-0" (Unless Noted Otherwise)
D
BL
A
BL
60'-0"
FRAME CROSS SECTION AT FRAME LINE(S) 4
1
7'
-
6
"
5'
-
0
"
2
3
EA
P
1
EA
P
1
ES
B
S
B
ES
B
S
B
(2
)
G
F
B
4
0
2
7
GF
B
2
0
8
1
GF
B
3
0
0
0
GF
B
4
0
0
7
GF
B
3
1
1
1
GF
B
2
0
8
1
GF
B
2
0
9
7
(2
)
G
F
B
3
0
2
1
4
9 @ 5'-0"
5
KMA1
(2)WBBC2
(2)KMA1
(4)WBBC2
1
GFB2066
(2)GFB3077
7'
-
6
"
6
7
18
'
-
6
"
16
'
-
0
"
60'-0 5/8" 0.500:12
C X 0 0 7
C X 0 0 7
R B X 0 0 6
R B X 0 0 8
C
X
0
0
6
A
B
A
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C FRAME CROSS SECTION AT FRAME LINE(S) 4
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
10
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1. USE 1/2 X 1 1/2 A325T BOLT (49080) AND NUT (47120)
W/O WASHERS. SNUG TIGHTEN BOLTS FOR ALL SECONDARY CONNECTIONS,
SECONDARY CLIP CONNECTIONS, AND FLANGE BRACE CONNECTIONS,
UNLESS NOTED OTHERWISE.
2. SLOT REINFORCEMENT PLATES NEED NOT BE LOCATED ON THE SAME
SIDE OF THE WEB AS THE HILLSIDE WASHER.
Shape Name = Shop Wall 4, Frame 4
1/14/2021 16:02:39
NOTE:
Installation of tension control bolts may not be possible in areas where ex-
treme pitch,stiffener location,beam depth or other obstructions may occur.
In these cases,substitution of nuts and bolts tightened with wrenches are
required.
01/15/2021
Part
Frame Member Schedule
Mem Width Thick WebThk.Depth1 Depth2 Approx.Lgth Approx.Weight
CX008 1 8.0000 .3750 .1644 1'-0"2'-6 3/8"17'-9 1/8"704#
2 8.0000 .3750 .1875 2'-6 3/8"2'-7"
RBX006 3 5.0000 .3750 .1875 2'-9"1'-5"26'-8 5/8"750#
4 5.0000 .3125 .1644 1'-5"2'-8"
RBX008 5 5.0000 .3125 .1644 2'-8"1'-4"30'-0 1/16"841#
6 5.0000 .3125 .1875 1'-4"2'-8"
CX006 7 5.0000 .3750 .1644 1'-0"2'-9"12'-9"369#
Id
Bolt Connection & Plate Schedule
Qty Grade Bolt Bolt Plate Rows Rows Tension Washer PartNo
Dia.Length Thick.Out In Bolt
A 10 F1852 3/4"2 1/4"1/2"3 2 Yes Yes 0097389
B 12 F1852 3/4"2"3/8"2 4 Yes Yes 0097388
1 8 1/2"
Dimension Key
2 2'-9"
3 3'-3"
4 2 @ 4'-3"
5 2 @ 3'-3 5/16"
6 4'-6"
7 4'-0"
Horiz. Clearance between members 1(CX008) and 7(CX006): 53'-3 5/8"
Frame Clearances
Horiz. Clearance between members 2(CX008) and 7(CX006): 53'-3"
Vert. Clearance at member 2(CX008): 14'-7 9/16"
Vert. Clearance at member 7(CX006): 12'-9"
Finished Floor Elevation = 100'-0" (Unless Noted Otherwise)
D
BL
A
BL
60'-0"
FRAME CROSS SECTION AT FRAME LINE(S) 8
1
7'
-
6
"
5'
-
0
"
2
3
EA
P
1
EA
P
1
ES
B
S
B
ES
B
S
B
(2
)
G
F
B
4
0
2
7
GF
B
2
0
8
1
GF
B
3
0
0
0
GF
B
4
0
0
7
GF
B
3
1
1
1
GF
B
2
0
8
1
GF
B
2
0
9
7
(2
)
G
F
B
3
0
2
1
4
9 @ 5'-0"
5
KMA1
(2)WBBC2
(2)KMA1
(4)WBBC2
1
GFB2066
(2)GFB3077
7'
-
6
"
6
7
18
'
-
6
"
16
'
-
0
"
60'-0 5/8" 0.500:12
C X 0 0 8
C X 0 0 8
R B X 0 0 6
R B X 0 0 8
C
X
0
0
6
A
B
A
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C FRAME CROSS SECTION AT FRAME LINE(S) 8
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
11
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1. USE 1/2 X 1 1/2 A325T BOLT (49080) AND NUT (47120)
W/O WASHERS. SNUG TIGHTEN BOLTS FOR ALL SECONDARY CONNECTIONS,
SECONDARY CLIP CONNECTIONS, AND FLANGE BRACE CONNECTIONS,
UNLESS NOTED OTHERWISE.
2. SLOT REINFORCEMENT PLATES NEED NOT BE LOCATED ON THE SAME
SIDE OF THE WEB AS THE HILLSIDE WASHER.
Shape Name = Shop Wall 4, Frame 8
1/14/2021 16:02:45
NOTE:
Installation of tension control bolts may not be possible in areas where ex-
treme pitch,stiffener location,beam depth or other obstructions may occur.
In these cases,substitution of nuts and bolts tightened with wrenches are
required.
01/15/2021
Part
Frame Member Schedule
Mem Width Thick WebThk.Depth1 Depth2 Approx.Lgth Approx.Weight Detail
CX009 1 5.0000 .1875 .1345 1'-0"1'-0"16'-9 1/8"228#
RBX009 2-5 5.0000 .1875 .1345 11"11"25'-3 1/2"299#
RBX010 6 5.0000 .1875 .1345 11"11"15'-5 7/16"183#
RBX011 7-9 5.0000 .1875 .1345 11"11"17'-6 3/4"207#
CX010 10 5.0000 .1875 .1345 1'-0"1'-0"13'-5 5/16"183#
EPX003 11 5.0000 .1345 .1345 10"10"14'-11 9/16"153#BR25CA
EPX004 12 5.0000 .1345 .1345 10"10"13'-11 1/16"144#BR25CA
Id
Bolt Connection & Plate Schedule
Qty Grade Bolt Bolt Plate Rows Rows Tension Washer PartNo
Dia.Length Thick.Out In Bolt
A 4 A325 1/2"1 1/2"3/8"1 1 49080
B 4 F1852 3/4"1 3/4"1/4"1 1 Yes Yes 0097387
<S> - (2) Washers (095872) req'd at Flange Brace to Secondary.
1 8 1/2"
Dimension Key
2 4'-0"
3 3'-6"
4 2'-9"
5 3'-3"
6 2 @ 4'-3"
7 2 @ 3'-3 5/16"
8 4'-6"
Horiz. Clearance between members 1(CX009) and 10(CX010): 56'-7"
Frame Clearances
Vert. Clearance at member 1(CX009): 16'-9 1/8"
Vert. Clearance at member 10(CX010): 14'-5 5/16"
Vert. Clearance at member 11(EPX003): 15'-11 1/2"
Vert. Clearance at member 12(EPX004): 14'-10 15/16"
Finished Floor Elevation = 100'-0" (Unless Noted Otherwise)
22'-0"25'-0"13'-0"
D
BL
A
BL
CL
C
CL
B
60'-0"
FRAME CROSS SECTION AT FRAME LINE(S) 9
KMA1
(2)WBBC2
KMA1
(2)WBBC2
1
GFB2006
GFB2006
GFB2006
2
3
5'
-
0
"
4
5
EA
P
2
GF
B
2
0
4
3
GF
B
2
0
4
3
<
S
>
GF
B
2
0
4
3
<
S
>
GF
B
2
0
4
3
GF
B
2
0
4
3
<
S
>
GF
B
2
0
4
3
<
S
>
GF
B
2
0
4
3
6
9 @ 5'-0"
7
KMA1
(2)WBBC2
1
GFB2006
2
3
8
2
18
'
-
6
"
16
'
-
0
"
60'-0 5/8" 0.500:12
CX
0
0
9
RBX009
RBX010 RBX011
CX
0
1
0
EP
X
0
0
3
EP
X
0
0
4
A
B
B
A
A
A
101'-0"101'-0"101'-0"101'-0"
KMA1
(2)WBBC2
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C FRAME CROSS SECTION AT FRAME LINE(S) 9
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
12
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1. USE 1/2 X 1 1/2 A325T BOLT (49080) AND NUT (47120)
W/O WASHERS. SNUG TIGHTEN BOLTS FOR ALL SECONDARY CONNECTIONS,
SECONDARY CLIP CONNECTIONS, AND FLANGE BRACE CONNECTIONS,
UNLESS NOTED OTHERWISE.
2. SLOT REINFORCEMENT PLATES NEED NOT BE LOCATED ON THE SAME
SIDE OF THE WEB AS THE HILLSIDE WASHER.
Shape Name = Shop Wall 4, Frame 9
1/14/2021 16:02:47
01/15/2021
Part
Frame Member Schedule
Mem Width Thick WebThk.Depth1 Depth2 Approx.Lgth Approx.Weight
CX011 1 6.0000 .2500 .1345 1'-4"1'-4"17'-4 15/16"340#
RBX012 2-3 6.0000 .2500 .1345 1'-4"1'-4"20'-11 1/2"399#
CX011 4 6.0000 .2500 .1345 1'-4"1'-4"17'-4 15/16"340#
Id
Bolt Connection & Plate Schedule
Qty Grade Bolt Bolt Plate Rows Rows Tension Washer PartNo
Dia.Length Thick.Out In Bolt
A 8 F1852 3/4"2 1/4"1/2"2 2 Yes Yes 0097389
B 2 F1852 3/4"2"3/8"1 -Yes Yes 0097388
1 8"
Dimension Key
2 1'-0 1/2"
Horiz. Clearance between members 1(CX011) and 4(CX011): 21'-0"
Frame Clearances
Vert. Clearance at member 1(CX011): 15'-9 13/16"
Vert. Clearance at member 4(CX011): 15'-9 13/16"
Finished Floor Elevation = 100'-0" (Unless Noted Otherwise)
25'-0"
1123'-8"
3 4
PORTAL FRAME ELEVATION ALONG D
1
HFB3060
1
HFB3060
CX
0
1
1
RBX012
CX
0
1
1
A A
17
'
-
4
1
5
/
1
6
"
2
B B
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C PORTAL FRAME ELEVATION ALONG D
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
13
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1. USE 1/2 X 1 1/2 A325T BOLT (49080) AND NUT (47120)
W/O WASHERS. SNUG TIGHTEN BOLTS FOR ALL SECONDARY CONNECTIONS,
SECONDARY CLIP CONNECTIONS, AND FLANGE BRACE CONNECTIONS,
UNLESS NOTED OTHERWISE.
2. SLOT REINFORCEMENT PLATES NEED NOT BE LOCATED ON THE SAME
SIDE OF THE WEB AS THE HILLSIDE WASHER.
Shape Name = Shop Wall 4, Frame 3
1/14/2021 16:02:48
01/15/2021
Part
Frame Member Schedule
Mem Width Thick WebThk.Depth1 Depth2 Approx.Lgth Approx.Weight
CX011 1 6.0000 .2500 .1345 1'-4"1'-4"17'-4 15/16"340#
RBX012 2-3 6.0000 .2500 .1345 1'-4"1'-4"20'-11 1/2"399#
CX011 4 6.0000 .2500 .1345 1'-4"1'-4"17'-4 15/16"340#
Id
Bolt Connection & Plate Schedule
Qty Grade Bolt Bolt Plate Rows Rows Tension Washer PartNo
Dia.Length Thick.Out In Bolt
A 8 F1852 3/4"2 1/4"1/2"2 2 Yes Yes 0097389
B 2 F1852 3/4"2"3/8"1 -Yes Yes 0097388
1 8"
Dimension Key
2 1'-0 1/2"
Horiz. Clearance between members 1(CX011) and 4(CX011): 21'-0"
Frame Clearances
Vert. Clearance at member 1(CX011): 15'-9 13/16"
Vert. Clearance at member 4(CX011): 15'-9 13/16"
Finished Floor Elevation = 100'-0" (Unless Noted Otherwise)
25'-0"
1123'-8"
7 8
PORTAL FRAME ELEVATION ALONG D
1
HFB3060
1
HFB3060
CX
0
1
1
RBX012
CX
0
1
1
A A
17
'
-
4
1
5
/
1
6
"
2
B B
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C PORTAL FRAME ELEVATION ALONG D
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
14
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1. USE 1/2 X 1 1/2 A325T BOLT (49080) AND NUT (47120)
W/O WASHERS. SNUG TIGHTEN BOLTS FOR ALL SECONDARY CONNECTIONS,
SECONDARY CLIP CONNECTIONS, AND FLANGE BRACE CONNECTIONS,
UNLESS NOTED OTHERWISE.
2. SLOT REINFORCEMENT PLATES NEED NOT BE LOCATED ON THE SAME
SIDE OF THE WEB AS THE HILLSIDE WASHER.
Shape Name = Shop Wall 4, Frame 7
1/14/2021 16:02:50
01/15/2021
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C PRIMARY BRACING SED'S
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
15
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1. USE 1/2 X 1 1/2 A325T BOLT (49080) AND NUT (47120)
W/O WASHERS. SNUG TIGHTEN BOLTS FOR ALL SECONDARY CONNECTIONS,
SECONDARY CLIP CONNECTIONS, AND FLANGE BRACE CONNECTIONS,
UNLESS NOTED OTHERWISE.
2. SLOT REINFORCEMENT PLATES NEED NOT BE LOCATED ON THE SAME
SIDE OF THE WEB AS THE HILLSIDE WASHER.
1/14/2021 SEDSheet 16:02:50
01/15/2021
1 RCHB15
Part Mark Key
1 6"
Dimension Key
Mark
Secondary Part Schedule
Part Thick.Depth Lap Detail
E1 00108HS2411414B00 0.0790 8 1/2"RS12PF,RS12PE,RS14PC
E2 00108ES2411417B00 0.0600 8 1/2"RS12PH,RS12PA
E3 08H2411414DDB00 0.0790 8 1/2"RS12PE
E4 08E2411417DDB00 0.0600 8 1/2"RS12PA,RS12PE
E5 08E2411414DDB00 0.0790 8 1/2"RS12PE
E6 00208ES2411417B00 0.0600 8 1/2"RS12PH,RS12PA
P1 08Z2811413B5B0 0.0880 8 1/2"3'-10 1/2"RS02T1,RS01T1
P2 08Z301141444B0 0.0790 8 1/2"2'-10 1/2"RS01T1
Id
Secondary Bracing Schedule
Qty Mark No Spacing
1 39 PBA0406(Typ.)4'-3"
2 39 PBA0307 3'-3 5/16"
See SED:
BR09K5, BR09RY, BR09RZ, BR09K2, BR09W2
60
'
-
0
"
200'-0"
1 24'-6"25'-0"25'-0"25'-0"25'-0"25'-0"25'-0"24'-6"1
1R1B1
E1
P1(Typ.)
E2
1R1B2
E3
P2(Typ.)
E4
1R1B3
E3
P2(Typ.)
E5
1R1B4
E3
P2(Typ.)
E4
1R1B5
E3
P2(Typ.)
E4
1R1B6
E3
P2(Typ.)
E4
1R1B7
E3
P2(Typ.)
E5
1R1B8
E1
P1(Typ.)
E6
1
1
1
1
1
1
1
1
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
ROOF SECONDARY PLAN
A BL
B
C
D BL
1
BL
2 3 4 5 6 7 8 9
BL
HIGH SIDE
LOW SIDE
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C ROOF SECONDARY PLAN
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
16
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1. UNLESS NOTED, USE 1/2 X 1 1/2 A325T BOLT (49080) AND NUT (47120)
W/O WASHERS. SNUG TIGHTEN BOLTS FOR ALL SECONDARY CONNECTIONS.
2. FLANGE BRACES ARE AN INTEGRAL PART OF THE STABILITY OF THE
STRUCTURAL SYSTEM AND MUST BE PROPERLY INSTALLED PRIOR TO ERECTION
OF WALL AND ROOF SHEETS.
3. REMOVAL OR ALTERATION OF ANY COMPONENT IS PROHIBITED.
Shape Name = Shop
1/14/2021 18:12:57
01/15/2021
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C ROOF SECONDARY SED'S
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
17
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1. UNLESS NOTED, USE 1/2 X 1 1/2 A325T BOLT (49080) AND NUT (47120)
W/O WASHERS. SNUG TIGHTEN BOLTS FOR ALL SECONDARY CONNECTIONS.
2. FLANGE BRACES ARE AN INTEGRAL PART OF THE STABILITY OF THE
STRUCTURAL SYSTEM AND MUST BE PROPERLY INSTALLED PRIOR TO ERECTION
OF WALL AND ROOF SHEETS.
3. REMOVAL OR ALTERATION OF ANY COMPONENT IS PROHIBITED.
1/14/2021 SEDSheet 18:12:57
01/15/2021
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C ROOF SECONDARY SED'S
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
18
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1. UNLESS NOTED, USE 1/2 X 1 1/2 A325T BOLT (49080) AND NUT (47120)
W/O WASHERS. SNUG TIGHTEN BOLTS FOR ALL SECONDARY CONNECTIONS.
2. FLANGE BRACES ARE AN INTEGRAL PART OF THE STABILITY OF THE
STRUCTURAL SYSTEM AND MUST BE PROPERLY INSTALLED PRIOR TO ERECTION
OF WALL AND ROOF SHEETS.
3. REMOVAL OR ALTERATION OF ANY COMPONENT IS PROHIBITED.
1/14/2021 SEDSheet 18:12:58
01/15/2021
1 PG1
Part Mark Key
2 JTG1
3 GFA206
1 4'-0"
Dimension Key
2 3'-6"
Mark
Secondary Part Schedule
Part Thick.Depth Detail
G1 00108ZS031101700 0.0600 8 1/2"WSR001,BR10F5,WS20F2
G2 00208ZS110101710 0.0600 8 1/2"WSR001,BR10F5,WSV500
G3 00308ZS110101710 0.0600 8 1/2"WSR0010,WSV500
G4 08Z2409411EE10 0.1130 8 1/2"WSV500
G5 08Z2409413EE10 0.0880 8 1/2"WSV500
G6 00408ZS200101610 0.0680 8 1/2"WSR001,BR10F5,WSV500
G7 00508ZS200101410 0.0790 8 1/2"WSR001,WSV500
J1 00108JS0602217 0.0600 8 1/2"BR10F5,WS20B2,WS20B8
J2 00208JS0602217 0.0600 8 1/2"BR10F5,WS20B2,WS20B8
Part
Bracing Part Schedule
Qty Length Detail
03RS2904 1 29'-4"BR01G2,BRR052
03RS2810 1 28'-10"BR01G2,BRR052
NBVP - Masonry
60'-0"
16
'
-
0
"
18
'
-
6
"
13'-0"25'-0"22'-0"
A
BL
D
BL
CL
C
CL
B
1
1
J2
6'-0"
1
1
J1
6'-0"
2
1W1B0
G1
G2
G3
1W1B1
G4
G5
2
1W1B2
G1
G6
G7
1
2
5'
-
0
"
2
3
3
3
3
3
3
0 3 R S 2 9 0 4
03RS2810
SECONDARY ELEVATION AT 1
4
4
4
4
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C SECONDARY ELEVATION AT 1
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
19
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1. UNLESS NOTED, USE 1/2 X 1 1/2 A325T BOLT (49080) AND NUT (47120)
W/O WASHERS. SNUG TIGHTEN BOLTS FOR ALL SECONDARY CONNECTIONS.
2. FLANGE BRACES ARE AN INTEGRAL PART OF THE STABILITY OF THE
STRUCTURAL SYSTEM AND MUST BE PROPERLY INSTALLED PRIOR TO ERECTION
OF WALL AND ROOF SHEETS.
3. REMOVAL OR ALTERATION OF ANY COMPONENT IS PROHIBITED.
Shape Name = Shop, Wall = 1
1/14/2021 18:13:01
01/15/2021
1 PG1
Part Mark Key
2 JTG1
1 6"
Dimension Key
2 4'-0"
3 3'-6"
4 4'-6"
Mark
Secondary Part Schedule
Part Thick.Depth Lap Detail
G8 00608ZS050841700 0.0600 8 1/2"WSR001,BR10F5,WS20F2
G9 00708ZS251141600 0.0680 8 1/2"10 1/2"WSR001,BR10F5,WS01G3
G10 08Z2511417B100 0.0600 8 1/2"10 1/2"WSR010,WS01G3
G11 08Z26114171100 0.0600 8 1/2"10 1/2"WS01G3
G12 00808ZS251141600 0.0680 8 1/2"10 1/2"WSR001,BR10F5,WS01G3
J3 00308JS0602217 0.0600 8 1/2"BR10F5,WS20B2,WS20B8
J4 00408JS0602217 0.0600 8 1/2"BR10F5,WS20B2,WS20B8
Part
Bracing Part Schedule
Qty Length Detail
06RT2803 4 28'-3"BR01G2,BR15L2
NBVP - Masonry
200'-0"
16
'
-
0
"
1 24'-6"25'-0"25'-0"25'-0"25'-0"25'-0"25'-0"24'-6"1
9
BL
1
BL
CLCL
2
CL
3
CL
4
CL
5
CL
6
CL
7
CL
8
CL
1
1
J4
6'-0"
1
1
J3
6'-0"
2
1W2B1
G8
G9
G10
1W2B2
G11(Typ.)
1W2B3
G11(Typ.)
1W2B4
G11(Typ.)
1W2B5
G11(Typ.)
1W2B6
G11(Typ.)
1W2B7
G11(Typ.)
2
1W2B8
G8
G12
G10
2
3
4
2
0 6 R T 2 8 0 3
06RT2803
0 6 R T 2 8 0 3
06RT2803
SECONDARY ELEVATION AT A
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C SECONDARY ELEVATION AT A
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
20
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1. UNLESS NOTED, USE 1/2 X 1 1/2 A325T BOLT (49080) AND NUT (47120)
W/O WASHERS. SNUG TIGHTEN BOLTS FOR ALL SECONDARY CONNECTIONS.
2. FLANGE BRACES ARE AN INTEGRAL PART OF THE STABILITY OF THE
STRUCTURAL SYSTEM AND MUST BE PROPERLY INSTALLED PRIOR TO ERECTION
OF WALL AND ROOF SHEETS.
3. REMOVAL OR ALTERATION OF ANY COMPONENT IS PROHIBITED.
Shape Name = Shop, Wall = 2
1/14/2021 18:13:02
01/15/2021
1 PG1
Part Mark Key
2 JTG1
3 GFA206
4 GFA106
1 4'-0"
Dimension Key
2 3'-6"
Mark
Secondary Part Schedule
Part Thick.Depth Detail
G1 00108ZS031101700 0.0600 8 1/2"WSR001,BR10F5,WS20F2
G2 00208ZS110101710 0.0600 8 1/2"WSR001,BR10F5,WSV500
G3 00308ZS110101710 0.0600 8 1/2"WSR0010,WSV500
G4 08Z2409411EE10 0.1130 8 1/2"WSV500
G5 08Z2409413EE10 0.0880 8 1/2"WSV500
G6 00408ZS200101610 0.0680 8 1/2"WSR001,BR10F5,WSV500
G7 00508ZS200101410 0.0790 8 1/2"WSR001,WSV500
J5 00508JS0602217 0.0600 8 1/2"BR10F5,WS20B2,WS20B8
J6 00608JS0602217 0.0600 8 1/2"BR10F5,WS20B2,WS20B8
Part
Bracing Part Schedule
Qty Length Detail
03RS2810 1 28'-10"BR01G2,BRR052
03RS2904 1 29'-4"BR01G2,BRR052
NBVP - Masonry
60'-0"
18
'
-
6
"
16
'
-
0
"
22'-0"25'-0"13'-0"
D
BL
A
BL
CL
C
CL
B
1
1
J6
6'-0"
1
1
J5
6'-0"
2
1W3B0
G1
G6
G7
1W3B1
G4
G5
2
1W3B2
G1
G2
G3
1
2
5'
-
0
"
6'
-
0
"
3
3
3
3
3
3
0 3 R S 2 8 1 0
03RS2904
SECONDARY ELEVATION AT 9
4
4
4
4
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C SECONDARY ELEVATION AT 9
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
21
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1. UNLESS NOTED, USE 1/2 X 1 1/2 A325T BOLT (49080) AND NUT (47120)
W/O WASHERS. SNUG TIGHTEN BOLTS FOR ALL SECONDARY CONNECTIONS.
2. FLANGE BRACES ARE AN INTEGRAL PART OF THE STABILITY OF THE
STRUCTURAL SYSTEM AND MUST BE PROPERLY INSTALLED PRIOR TO ERECTION
OF WALL AND ROOF SHEETS.
3. REMOVAL OR ALTERATION OF ANY COMPONENT IS PROHIBITED.
Shape Name = Shop, Wall = 3
1/14/2021 18:13:03
01/15/2021
1 PG1
Part Mark Key
2 JTG1
3 GC5
4 TSC1
5 G19(Flip)
1 6"
Dimension Key
2 4'-0"
3 3'-6"
4 2'-9"
5 3'-3"
6 2'-0"
Mark
Secondary Part Schedule
Part Thick.Depth Detail
G8 00608ZS050841700 0.0600 8 1/2"WSR001,BR10F5,WS20F2
G13 00908ZS300241400 0.0790 8 1/2"WSR001,WS20F2,WS21D5
G14(Flip)00108CS300241100 0.1130 8 1/2"WSR001,WS20F2,WS21D5
G15 00108BB241141600 0.0680 8 1/2"WS01GA
G16 01008ZS350541600 0.0680 8 1/2"WS20F2,WS21D5
G17(Flip)00208CS350541100 0.1130 8 1/2"WS20F2,WS21D5
G18 08Z0502417BG00 0.0600 8 1/2"WSR001,WS20F2
G19(Flip)08C0502417BG00 0.0600 8 1/2"WSR001,WS20F2
G20 08Z2411411BD00 0.1130 8 1/2"WS12H6,WS01G2
H1 00808JS0500017 0.0600 8 1/2"WS20F9
H2 01008JS1400017 0.0600 8 1/2"WS20F9
J7 00708JS0602217 0.0600 8 1/2"BR10F5,WS20B2,WS20B8
J8 00908JS0503017 0.0600 8 1/2"WS20F9,WS20B6,WS20B1
J9 01108JS1311217 0.0600 8 1/2"WS20F9,WS20F2,WS20B2,WS20B8
J10 01208JS1311217 0.0600 8 1/2"WS20F9,WS20F2,WS20B2,WS20B8
Id
Framed Opening Locations
Width Height Sill Ht.Frame To Dimen.Description
FO1 5'-0"2'-0"12'-6"1 Jamb-L 9'-6"5020
FO1 5'-0"2'-0"12'-6"3 Jamb-L 10'-0"5020
FO1 5'-0"2'-0"12'-6"5 Jamb-L 10'-0"5020
FO1 5'-0"2'-0"12'-6"7 Jamb-L 10'-0"5020
NBVP - Masonry NBVP - Masonry NBVP - Masonry NBVP - Masonry NBVP - Masonry
200'-0"
18
'
-
6
"
1 24'-6"25'-0"25'-0"25'-0"25'-0"25'-0"25'-0"24'-6"1
1
BL
9
BL
CL CL
2
CL
3
CL
4
CL
5
CL
6
CL
7
CL
8
CL
1
1
J7
6'-0"
2
2
2
1 1
H1
3
4
J8
3
4
J8
1W4B1
G8
G13
G14(Flip)
1 1
H2
1
1
J9
1
1
J9
1W4B2
G15
2 2
2 2
1 1
H1
3
4
J8
3
4
J8
1W4B3
G16
G17(Flip)
1 1
H2
1
1
J9
1
1
J9
1W4B4
G15
2 2
2 2
1 1
H1
3
4
J8
3
4
J8
1W4B5
G16
G17(Flip)
1 1
H2
1
1
J9
1
1
J9
1W4B6
G15
2 2
2 2
1 1
H1
3
4
J8
3
4
J8
1W4B7
G16
G17(Flip)
2
2
2
1
1
J9
1
1
J1
0
1W4B8
G18
G18
5
G201 1
H2
1W4B8
2
3
5'
-
0
"
4
5
5'-6"14'-0"5'-6"5'-6"14'-0"5'-6"5'-6"14'-0"5'-6"5'-6"14'-0"5'-6"
10'-0"5'-0"10'-0"
10'-0"5'-0"10'-0"10'-0"5'-0"10'-0"10'-0"5'-0"10'-0"
6
14
'
-
0
"
6
14
'
-
0
"
6
14
'
-
0
"
6
14
'
-
0
"
FO1 FO1 FO1 FO1
SECONDARY ELEVATION AT D
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C SECONDARY ELEVATION AT D
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
22
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1. UNLESS NOTED, USE 1/2 X 1 1/2 A325T BOLT (49080) AND NUT (47120)
W/O WASHERS. SNUG TIGHTEN BOLTS FOR ALL SECONDARY CONNECTIONS.
2. FLANGE BRACES ARE AN INTEGRAL PART OF THE STABILITY OF THE
STRUCTURAL SYSTEM AND MUST BE PROPERLY INSTALLED PRIOR TO ERECTION
OF WALL AND ROOF SHEETS.
3. REMOVAL OR ALTERATION OF ANY COMPONENT IS PROHIBITED.
Shape Name = Shop, Wall = 4
1/14/2021 18:13:04
NOTE:
EACH JAMB OF THE 14' X 14' OHD
DOOR WAS DESIGNED TO SUPPORT 690
LBS OF DOOR WEIGHT.
01/15/2021
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C WALL SECONDARY SED'S
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
23
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1. UNLESS NOTED, USE 1/2 X 1 1/2 A325T BOLT (49080) AND NUT (47120)
W/O WASHERS. SNUG TIGHTEN BOLTS FOR ALL SECONDARY CONNECTIONS.
2. FLANGE BRACES ARE AN INTEGRAL PART OF THE STABILITY OF THE
STRUCTURAL SYSTEM AND MUST BE PROPERLY INSTALLED PRIOR TO ERECTION
OF WALL AND ROOF SHEETS.
3. REMOVAL OR ALTERATION OF ANY COMPONENT IS PROHIBITED.
1/14/2021 SEDSheet 18:13:04
01/15/2021
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C WALL SECONDARY SED'S
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
24
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1. UNLESS NOTED, USE 1/2 X 1 1/2 A325T BOLT (49080) AND NUT (47120)
W/O WASHERS. SNUG TIGHTEN BOLTS FOR ALL SECONDARY CONNECTIONS.
2. FLANGE BRACES ARE AN INTEGRAL PART OF THE STABILITY OF THE
STRUCTURAL SYSTEM AND MUST BE PROPERLY INSTALLED PRIOR TO ERECTION
OF WALL AND ROOF SHEETS.
3. REMOVAL OR ALTERATION OF ANY COMPONENT IS PROHIBITED.
1/14/2021 SEDSheet 18:13:05
01/15/2021
Id
Covering Mark Schedule
Qty Start Panel Last Panel Direction
#4 67 R37055261GTD R37055261GTD Left to Right
#5 67 R23056261GTD R23056261GTD Left to Right
Id
Covering Schedule
Qty Length Type Gage OP Fin.Color Direction
#4 67 37'-5 5/8"PR 26 1 G TD Left to Right
#5 67 23'-5 3/4"PR 26 1 G TD Left to Right
Oper. Code:1=SQ,SQ
Finish:G=Galvalume
Color:TD=Standard Color
Id
Trim Schedule
Parts Color Details
T1 (4)RKF16 Cool Zinc Gray RC30B1,RS10R1
T2 EA2L,FPRF1 Cool Zinc Gray RC38N2
T3 EA2R,FPRF1 Cool Zinc Gray RC38N2
T4 (10)PKF20A Cool Zinc Gray EN52A1,ENV003,RC00A1,RC03B1,RC35B1,WC13F1
T5 MCC1 Cool Zinc Gray RC38AJ
Part
Fastener Schedule
Description
0097584UNPNTD (T-2) #12-14 x 1 1/4", 5/16" Hex Hd, SS Cap w/Washer PANEL TO STRUCTURAL
0097581UNPNTD (T-1) 1/4-14 x 7/8", 5/16" Hex Hd, SS Cap w/Washer PANEL TO PANEL
60
'
-
0
"
200'-0"
(67)#4
(67)#5
T1 T1
T2 T3
T4T5 T5
ROOF COVERING PLAN
A BL
D BL
1
BL
9
BL
HIGH SIDE
LOW SIDE
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C ROOF COVERING PLAN
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
25
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1. PRE-DRILLING 1/8 DIAMETER HOLES FOR STRUCTURAL FASTENERS
MAY BE REQUIRED FOR HEAVY GAGE NESTED ZEE's AND/OR FASTENERS
TO STRUCTURAL BEAMS
2. STEEL PANELS ARE AN INTEGRAL PART OF THE STRUCTURAL SYSTEM.
REMOVAL OR ALTERATION WITHOUT PRIOR AUTHORIZATION IS PROHIBITED.
3. DUE TO MANUFACTURING LIMITATIONS SHORT PANELS MAY REQUIRE
FIELD CUTTING, SEE THE COVERING SCHEDULE FOR CUT LENGTHS.
4. SEE JOB DETAILS FOR COVERING AND TRIM FASTENER SPECIFICATION.
Shape Name = Shop
1/14/2021 18:43:22
NOTE:
Material provided for (8) NBVP 3070 walk doors:
8 - HTS05 Header Trim Cool Zinc Gray
16 - JT07 Jamb Trim Cool Zinc Gray
200 - 0097584-116 Structural Fasteners Cool Zinc Gray
20 - 0097581-116 Stitch Fasteners Cool Zinc Gray
16 - 80130 Panel Closures
01/15/2021
Id
Covering Mark Schedule
Qty Start Panel Last Panel Increment Direction Start Dim.
#2 20 W1411026FKGG W1703426FKGG 1 1/2"Left to Right 0'-0"
Id
Covering Schedule
Qty Type Start Length Gage OP Fin.Color Increment Direction
#2 20 PR 14'-11"26 F K GG 1 1/2"Left to Right
Oper. Code:F=CR,SQ
Finish:K=KXL (Kynar)
Color:GG=Cool Granite Gray
Id
Trim Schedule
Parts Color Details
T1 (4)BG2415 Galvanized EN52A1,ENV003,RC00A1,WC01D9,WC04G1,
WS27B2,WS27D2
T2 CT16 Cool Zinc Gray WC20A1
T3 CT20 Cool Zinc Gray WC20A1
Part
Fastener Schedule
Color Description
0097597-112 Cool Granite Gray(T-2) #17/#12-14 x 1 7/8" Stand-Off, 5/16" Hex Hd, SS Cap w/Washer PANEL TO STRUCTURAL AT GIRTS
0097585-112 Cool Granite Gray(T-2) #12-14 x 1 1/2", 5/16" Hex Hd, SS Cap w/Washer PANEL TO STRUCTURAL AT BASE AND EAVE
0097581-112 Cool Granite Gray(T-1) 1/4-14 x 7/8", 5/16" Hex Hd, SS Cap w/Washer PANEL TO PANEL
NBVP - Masonry
60'-0"
16
'
-
0
"
18
'
-
6
"
A
BL
D
BL
14
'
-
1
1
"
15
'
-
0
1
/
2
"
15
'
-
2
"
15
'
-
3
1
/
2
"
15
'
-
5
"
15
'
-
6
1
/
2
"
15
'
-
8
"
15
'
-
9
1
/
2
"
15
'
-
1
1
"
16
'
-
0
1
/
2
"
16
'
-
2
"
16
'
-
3
1
/
2
"
16
'
-
5
"
16
'
-
6
1
/
2
"
16
'
-
8
"
16
'
-
9
1
/
2
"
16
'
-
1
1
"
17
'
-
0
1
/
2
"
17
'
-
2
"
17
'
-
3
1
/
2
"
(20)#2
1'
-
0
"
T1
T2
T3
COVERING ELEVATION AT 1
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C COVERING ELEVATION AT 1
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
26
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1. PRE-DRILLING 1/8 DIAMETER HOLES FOR STRUCTURAL FASTENERS
MAY BE REQUIRED FOR HEAVY GAGE NESTED ZEE's AND/OR FASTENERS
TO STRUCTURAL BEAMS
2. STEEL PANELS ARE AN INTEGRAL PART OF THE STRUCTURAL SYSTEM.
REMOVAL OR ALTERATION WITHOUT PRIOR AUTHORIZATION IS PROHIBITED.
3. DUE TO MANUFACTURING LIMITATIONS SHORT PANELS MAY REQUIRE
FIELD CUTTING, SEE THE COVERING SCHEDULE FOR CUT LENGTHS.
4. SEE JOB DETAILS FOR COVERING AND TRIM FASTENER SPECIFICATION.
Shape Name = Shop, Wall = 1
1/14/2021 18:43:25
01/15/2021
Id
Covering Mark Schedule
Qty Start Panel Direction Start Dim.
#3 67 W1503726GKGG Left to Right 0'-0"
Id
Covering Schedule
Qty Type Start Length Gage OP Fin.Color Direction
#3 67 PR 15'-3 7/8"26 G K GG Left to Right
Oper. Code:G=CR,NT
Finish:K=KXL (Kynar)
Color:GG=Cool Granite Gray
Id
Trim Schedule
Parts Color Details
T1 (13.3)BG2415 Galvanized EN52A1,ENV003,RC00A1,WC01D9,WC04G1,
WS27B2,WS27D2
Part
Fastener Schedule
Color Description
0097597-112 Cool Granite Gray(T-2) #17/#12-14 x 1 7/8" Stand-Off, 5/16" Hex Hd, SS Cap w/Washer PANEL TO STRUCTURAL AT GIRTS
0097585-112 Cool Granite Gray(T-2) #12-14 x 1 1/2", 5/16" Hex Hd, SS Cap w/Washer PANEL TO STRUCTURAL AT BASE AND EAVE
0097581-112 Cool Granite Gray(T-1) 1/4-14 x 7/8", 5/16" Hex Hd, SS Cap w/Washer PANEL TO PANEL
NBVP - Masonry
200'-0"
16
'
-
0
"
9
BL
1
BL
(67)#3
1'
-
0
"
T1
COVERING ELEVATION AT A
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C COVERING ELEVATION AT A
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
27
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1. PRE-DRILLING 1/8 DIAMETER HOLES FOR STRUCTURAL FASTENERS
MAY BE REQUIRED FOR HEAVY GAGE NESTED ZEE's AND/OR FASTENERS
TO STRUCTURAL BEAMS
2. STEEL PANELS ARE AN INTEGRAL PART OF THE STRUCTURAL SYSTEM.
REMOVAL OR ALTERATION WITHOUT PRIOR AUTHORIZATION IS PROHIBITED.
3. DUE TO MANUFACTURING LIMITATIONS SHORT PANELS MAY REQUIRE
FIELD CUTTING, SEE THE COVERING SCHEDULE FOR CUT LENGTHS.
4. SEE JOB DETAILS FOR COVERING AND TRIM FASTENER SPECIFICATION.
Shape Name = Shop, Wall = 2
1/14/2021 18:43:26
01/15/2021
Id
Covering Mark Schedule
Qty Start Panel Last Panel Increment Direction Start Dim.
#1 20 W1703426FKGG W1411026FKGG -1 1/2"Left to Right 0'-0"
Id
Covering Schedule
Qty Type Start Length Gage OP Fin.Color Increment Direction
#1 20 PR 17'-3 1/2"26 F K GG -1 1/2"Left to Right
Oper. Code:F=CR,SQ
Finish:K=KXL (Kynar)
Color:GG=Cool Granite Gray
Id
Trim Schedule
Parts Color Details
T1 (4)BG2415 Galvanized EN52A1,ENV003,RC00A1,WC01D9,WC04G1,
WS27B2,WS27D2
T2 CT16 Cool Zinc Gray WC20A1
T3 CT20 Cool Zinc Gray WC20A1
Part
Fastener Schedule
Color Description
0097597-112 Cool Granite Gray(T-2) #17/#12-14 x 1 7/8" Stand-Off, 5/16" Hex Hd, SS Cap w/Washer PANEL TO STRUCTURAL AT GIRTS
0097585-112 Cool Granite Gray(T-2) #12-14 x 1 1/2", 5/16" Hex Hd, SS Cap w/Washer PANEL TO STRUCTURAL AT BASE AND EAVE
0097581-112 Cool Granite Gray(T-1) 1/4-14 x 7/8", 5/16" Hex Hd, SS Cap w/Washer PANEL TO PANEL
NBVP - Masonry
60'-0"
18
'
-
6
"
16
'
-
0
"
D
BL
A
BL
17
'
-
3
1
/
2
"
17
'
-
2
"
17
'
-
0
1
/
2
"
16
'
-
1
1
"
16
'
-
9
1
/
2
"
16
'
-
8
"
16
'
-
6
1
/
2
"
16
'
-
5
"
16
'
-
3
1
/
2
"
16
'
-
2
"
16
'
-
0
1
/
2
"
15
'
-
1
1
"
15
'
-
9
1
/
2
"
15
'
-
8
"
15
'
-
6
1
/
2
"
15
'
-
5
"
15
'
-
3
1
/
2
"
15
'
-
2
"
15
'
-
0
1
/
2
"
14
'
-
1
1
"
(20)#1
1'
-
0
"
T1
T2
T3
COVERING ELEVATION AT 9
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C COVERING ELEVATION AT 9
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
28
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1. PRE-DRILLING 1/8 DIAMETER HOLES FOR STRUCTURAL FASTENERS
MAY BE REQUIRED FOR HEAVY GAGE NESTED ZEE's AND/OR FASTENERS
TO STRUCTURAL BEAMS
2. STEEL PANELS ARE AN INTEGRAL PART OF THE STRUCTURAL SYSTEM.
REMOVAL OR ALTERATION WITHOUT PRIOR AUTHORIZATION IS PROHIBITED.
3. DUE TO MANUFACTURING LIMITATIONS SHORT PANELS MAY REQUIRE
FIELD CUTTING, SEE THE COVERING SCHEDULE FOR CUT LENGTHS.
4. SEE JOB DETAILS FOR COVERING AND TRIM FASTENER SPECIFICATION.
Shape Name = Shop, Wall = 3
1/14/2021 18:43:27
01/15/2021
Id
Covering Mark Schedule
Qty Start Panel Direction Start Dim.
#6 53 W1708026FKGG Left to Right 0'-0",42'-0",93'-0",144'-0",192'-0"
#7 14 W04054261KGG Left to Right 33'-0",81'-0",132'-0",183'-0"
Id
Covering Schedule
Qty Type Start Length Gage OP Fin.Color Direction
#6 53 PR 17'-8"26 F K GG Left to Right
#7 14 PR 4'-5 1/2"26 1 K GG Left to Right
Oper. Code:F=CR,SQ
Oper. Code:1=SQ,SQ
Finish:K=KXL (Kynar)
Color:GG=Cool Granite Gray
Id
Trim Schedule
Parts Color Details
T1 (2.0)BG2415 Galvanized EN52A1,ENV003,RC00A1,WC01D9,WC04G1,
WS27B2,WS27D2
T2 (2.4)BG2415 Galvanized EN52A1,ENV003,RC00A1,WC01D9,WC04G1,
WS27B2,WS27D2
T3 (0.4)BG2415 Galvanized EN52A1,ENV003,RC00A1,WC01D9,WC04G1,
WS27B2,WS27D2
T4 DFT05,JT05 Cool Zinc Gray WC24A1
T5 DFT05,HTS05 Cool Zinc Gray WC24A2
T6 TDFH05 Cool Zinc Gray WC24A4
T7 DFT14,JT14 Cool Zinc Gray WC24A1
T8 DFT14,HTS14 Cool Zinc Gray WC24A2
Part
Fastener Schedule
Color Description
0097597-112 Cool Granite Gray(T-2) #17/#12-14 x 1 7/8" Stand-Off, 5/16" Hex Hd, SS Cap w/Washer PANEL TO STRUCTURAL AT GIRTS
0097585-112 Cool Granite Gray(T-2) #12-14 x 1 1/2", 5/16" Hex Hd, SS Cap w/Washer PANEL TO STRUCTURAL AT BASE AND EAVE
0097581-112 Cool Granite Gray(T-1) 1/4-14 x 7/8", 5/16" Hex Hd, SS Cap w/Washer PANEL TO PANEL
NBVP - Masonry NBVP - Masonry NBVP - Masonry NBVP - Masonry NBVP - Masonry
200'-0"
18
'
-
6
"
1
BL
9
BL
(11)#6
(3)#7
(13)#6
(4)#7
(13)#6
(4)#7
(13)#6
(3)#7
(3)#6
1'
-
0
"
T1 T2 T2 T2 T3
T4 T4 T4 T4 T4 T4 T4 T4
T5 T5 T5 T5
T6 T6 T6 T6
T7 T7 T7 T7 T7 T7 T7 T7
T8 T8 T8 T8
30'-6"14'-0"36'-0"14'-0"36'-0"14'-0"36'-0"14'-0"5'-6"
COVERING ELEVATION AT D
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C COVERING ELEVATION AT D
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
29
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1. PRE-DRILLING 1/8 DIAMETER HOLES FOR STRUCTURAL FASTENERS
MAY BE REQUIRED FOR HEAVY GAGE NESTED ZEE's AND/OR FASTENERS
TO STRUCTURAL BEAMS
2. STEEL PANELS ARE AN INTEGRAL PART OF THE STRUCTURAL SYSTEM.
REMOVAL OR ALTERATION WITHOUT PRIOR AUTHORIZATION IS PROHIBITED.
3. DUE TO MANUFACTURING LIMITATIONS SHORT PANELS MAY REQUIRE
FIELD CUTTING, SEE THE COVERING SCHEDULE FOR CUT LENGTHS.
4. SEE JOB DETAILS FOR COVERING AND TRIM FASTENER SPECIFICATION.
Shape Name = Shop, Wall = 4
1/14/2021 18:43:28
01/15/2021
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C COVERING & TRIM SED'S
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
30
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1/14/2021 SEDSheet 18:43:33
01/15/2021
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C COVERING & TRIM SED'S
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
31
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1/14/2021 SEDSheet 18:43:34
01/15/2021
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C B-081465
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
32
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1/14/2021 SEDSheet 18:56:49
01/15/2021
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C B-081765
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
33
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1/14/2021 SEDSheet 18:57:22
01/15/2021
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C S-081766
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
34
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1/14/2021 SEDSheet 18:57:56
01/15/2021
VPC VERSION:
FILENAME:
JOB #
DATE
DRAWN/CHECK
PAGE
BUILDER
CUSTOMER
LOCATION
PROJECT
BUILDERS PO#
DATEREV BY DESCRIPTION
VP BUILDINGS
VARCO PRUDEN
VP Buildings
3200 Players Club Circle Memphis TN 38125
A BlueScope Steel Company
a division of BlueScope Buildings North America, Inc.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF VP
BUILDINGS. IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE
APPLICABLE PURCHASE ORDER AND MAY BE REPRODUCED ONLY FOR THAT PURPOSE. IT
SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT
PRIOR WRITTEN APPROVAL OF VP BUILDINGS.
THE GENERAL CONTRACTOR AND/OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE
GOOD QUALITY WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS
DRAWING, DETAILS REFERENCED IN THIS DRAWING, ALL APPLICABLE VP BUILDINGS
ERECTION GUIDES, AND INDUSTRY STANDARDS PERTAINING TO PROPER ERECTION,
INCLUDING THE CORRECT USE OF TEMPORARY BRACING.
THE VP ENGINEER'S SEAL APPLIES ONLY TO
THE WORK PRODUCT OF VP AND DESIGN AND
PERFORMANCE REQUIREMENTS SPECIFIED BY VP.
THE VP ENGINEER'S SEAL DOES NOT APPLY TO
THE PERFORMANCE OR DESIGN OF ANY OTHER
PRODUCT OR COMPONENT FURNISHED BY VP
EXCEPT TO ANY DESIGN OR PERFORMANCE
REQUIREMENTS SPECIFIED BY VP.
C S-081767
TITAN STEEL LLC
Tom Luthy
Rexburg, Idaho
Luthy 60x200
20-026083-01
01/14/2021
ADCR
35
Tom Luthy 60x20
2020.4bNTS
FOR CONSTRUCTION
1/14/2021 SEDSheet 18:59:02
01/15/2021