HomeMy WebLinkAboutAPPROVED FOUNDATION PLAN - 21-00075 - Winder Station - New Commercial - Bldg BAuthor Name Author Email Author Phone No.:
Cody Jones Cody.Jones@rexburg.org 208-372-2173
Description : Winder Station - New Commercial - Bldg A
Address :
Record Type : Madison County - Commercial
Document Filename : FOUNDATION PLAN - 21-00075 - Winder Station - New Commercial - Bldg A.pdf
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report
Approved
# 21-00075
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
Pg 1 Free text Cody Jones : Building Open 1 Footing to be below frost depth of 36".
Pg 1 Free text Cody Jones : Building Open 1 On steel build specs
Pg 1 Free text Cody Jones : Building Open 1 Type VB construction.
Madison County - Commercial
Approval of plans does not constitute approval of variance from code
Powered by TCPDF (www.tcpdf.org)
KEYNOTES1FINISHEDGRADEWHEREOCCURS2DONOTEXCAVATEATRENCHCLOSERTHANA45DEGREEANGLETOBELOWBOTTOMFOOTINGORFOUNDATION3BOTTOMOFCONCRETEFOOTING4BOTTOMOFTRENCHNOTEADONOTUNDERCUTEXISTINGFOOTINGSBNOPIPEOROTHERUTILITIESSHALLPASSTHRUWALLFOOTINGSORUNDERCOLUMNFOOTINGS111234FORCONSTRUCTIONABOVEFOOTINGSEEDETAILST1TRENCHPARALLELTOCONTINUOUSSTRAPFOOTINGTD01NOSCALEKEYNOTES1CONCRETEFOOTING2SLEEVEPROVIDE12MINIMUMCLEARANCEAROUNDPIPEORCONDUIT3PIPEORCONDUIT4CONCRETEFILLTOBEPLACEDBEFOREFOOTINGISPOUREDFORMSAMEASFOOTINGANDPOURFULLWIDTHOFPIPETRENCH5STEMWALLNOTEANOPIPESHALLPASSTHRUFOOTINGORUNDERCOLUMNFOOTINGSFORTRENCHESGREATERTHAN36BELOWBOTTOMOFFOOTINGSEEPIPEPASSINGBELOWWALLFOOTINGDETAIL1234554213T2PIPEPASSINGUNDERWALLFOOTINGINSHALLOWTRENCHTD02NOSCALE
6" MIN 8" MIN
3'-0" MAX
8MIN ASECTIONAKEYNOTES1STEMWALL2CONCRETEFOOTING316MAXIMUMWHERETRENCHEXCEEDS16NOTIFYSTRUCTURALENGINEERPRIORTOPLACEMENTOFFOOTINGS4BACKFILLANDRECOMPACTTRENCHPERSOILSREPORTANDSPECIFICATIONS5BOTTOMOFTRENCHNOTEADONOTUNDERCUTEXISTINGFOOTINGSBNOPIPESOROTHERUTILITIESSHALLPASSTHRUWALLFOOTINGSORUNDERCOLUMNFOOTINGS1543
23'-1" OR GREATER
FORCONSTRUCTIONABOVEFOOTINGSEEDETAILST3PIPEPASSINGBELOWFOOTINGINDEEPTRENCHTD03NOSCALEKEYNOTES1SLOPEDFINISHGRADE2MINIMUMFOOTINGDEPTHPERGSN12MINIMUM3DEEPENFOOTINGASREQUIREDTOACCOUNTFORSLOPEDGRADE4CONCRETEFOOTINGNOTEAFORADDITIONALINFORMATIONSEEPLANSANDDETAILS14
3 2
50T4TYPICALDETAILFORFOUNDATIONEMBEDMENTTD04NOSCALE KEYNOTES1CONCRETESLABONGRADE2CONTKEYEDJOINT3SAWCUT18WIDEx14SLABTHICKNESSINDEPTHCUTSHALLBEMADESOONENOUGHTOPREVENTSHRINKAGECRACKINGBUTNOTSOSOONASTOCAUSESPALLINGOFTHECONCRETEWHILESAWINGWORKMUSTBECOMPLETEWITHIN16HOURSOFCONCRETEPLACEMENTNOTEAKEYEDJOINTSNEEDONLYOCCURATEXPOSEDEDGESDURINGPLACEMENTUNLESSSPECIFICALLYNOTEDONTHEPLANSBTOOLWETJOINTZIPSTRIPETCSHALLMATCHSAWCUTREQUIREMENTS1231126612XSAWCUTJOINTXKEYEDJOINTT5CONTROLJOINTSINCONCRETESLABONGRADETD07NOSCALE6MINBAROFFSETBARCLEARANCESPLICEDETAILBENDHOOKDETAILSCOLUMNTIESBEAMSTIRRUPSd45dd124561098
7
3 1559108 KEYNOTES1LAPSEEGSN2MAXIMUM15LAPBUTNOTMORETHAN63WIRETIES41d1MINIMUM5RADIUS3dFORBARSNOTOVER84dFOR910AND1BARS5dFOR14AND18BARS5dFORALLGRADE40BARSWITH180DEGREEHOOK64D4MINIMUM712d90DEGREEHOOK86d4MINIMUM9135DEGREEBEND10BENDAROUND112PINFOR3BARSBENDAROUND2PINFOR4BARSBENDAROUND212PINFOR5BARST6TYPICALREINFORCINGDETAILSTD10NOSCALENOTES1TOPBARSAREANYHORIZONTALBARSPLACEDSOTHATMORETHAN12OFFRESHCONCRETEISCASTINTHEMEMBERBELOWTHEREINFORCEMENT2UNLESSNOTEDOTHERWISELAPSPLICESINCONCRETEBEAMSSLABSANDWALLSSHALLBECLASSBTENSIONLAPSPLICESBARSIZECLASSBTENSIONSPLICELENGTHSfc3000PSIfc4000PSIfc5000PSIHOIRZONTALBARSW12OFCONCBELOWVERTICALANDBOTTOMHORIZONTALBARSHOIRZONTALBARSW12OFCONCBELOWVERTICALANDBOTTOMHORIZONTALBARSHOIRZONTALBARSW12OFCONCBELOWVERTICALANDBOTTOMHORIZONTALBARS3121212121212419151713151252923262023186322528212519754414736423287054614754429896877596953101128797758767T7STEELREINFORCINGLAPSPLICESINCONCRETETD14NOSCALE
PROFE
S IONALENG
I
N
E R
S
T
ATE O F I D A HO
A
1/14/21
14134
D
VID B .P O R TER
LICENSED
PROJECT MANAGER:CAD OPERATOR:
DATE
JOB NO.:
STRUCTURAL ENGINEERS SEAL:PROJECT:
CLIENT:
REV.DATE BY DESCRIPTION
2
3
4
5
CURRENTREV
This drawing is the property of FROST Structural Engineering,
Inc. Legally, the drawing can NOT be copied in whole or in
pieces. It is only to be used for the project and site specifically
identified hereon and is not to be used on any other project.
Contractor shall carefully review all dimensions, details, and
conditions and report at once any error, inconsistency or
omission discovered before construction.
The contractor assumes full liability for deviations from the
intent of these plans.
1
Structural Engineering
fax: 208.227.8405
1020 E. Lincoln Road
Idaho Falls, ID 83401
phone: 208.227.8404
contact@frost-structural.com
S10 11421
LUTHY 60 X 125 METAL BUILDING
TITAN STEEL LLC
RMSDBPIF20-467
GSN-TYPICAL DETAILS
5101 W 5000 SOUTH
REXBURG, IDAHO
SHEETINDEXDESCRIPTIONDETAILSGSNTYPICALDETAILSTSERIESFOUNDATIONPLANFOUNDATIONDETAILS100SERIES TEELKSIDEFORMEDBARSFORALLBARS4ANDLARGERKSIDEFORMEDBARSFORALLBARS3ANDSMALLERHALLBEUSEDFORCONCRETEWALLSBEAMSUMNREINFORCINGARSSHALLBEMADEONLYTOASTMA706GRADE60ERIESRODSWELDINGOFREINFORCINGBARSSHALLSHOWNONPLANSORDETAILSIVENAREMAXIMUMONCENTERSALLBARSPERCRSIOOKDOWELALLVERTICALREINFORCINGTOALLBARSINLOCATIONBEFOREPLACINGCONCRETEETESHALLBEREGULARWEIGHTOF150POUNDSPERCKAGGREGATESAGGREGATEUSEDINCONCRETE3FLOORSLABSSLABSSHALLBEACCORDINGTOPSCHEDULEONTHESEDRAWINGSOFONELAPLENGTHNOTACKWELDINGOFWITHOUTPRIORREVIEWOFPROCEDUREWITHTHEESTACICODEANDDETAILINGMANUALAPPLYPROVIDEHANDLAPWITHHORIZONTALBARSATALLCORNERSICALDETAILSVERTICALWALLBARSSHALLBELINESHELOCATIONOFREINFORCINGSTEELNOTNOTEDASNTEROFSTEELMINIMUMCOVERFOREREINFORCINGSHALLBEASFOLLOWSNCRETESHALLBE6PORTLANDCEMENTSHALLEVCEMENTSHALLBEUSEDFORCONCRETEINLANDTYPEIIELSEWHEREHALLELAPSEBETWEENCONCRETEBATCHINGANDSSAPPROVEDBYTHETESTINGAGENCYQUALITYSHALLBEPERRECOMMENDATIONSINACI614CALLYVIBRATEALLCONCRETEWHENPLACEDDENEEDBEVIBRATEDONLYAROUNDANDUNDEROSUREPOURWHERESHOWNONPLANSAROUNDADLOADISAPPLIEDREMOVEALLDEBRISFROMCRETECRETESUCHASREINFORCINGDOWELSBOLTSTCSHALLBESECURELYPOSITIONEDINTHEFORMSETEADESHALLBEDIVIDEDINTOAREASBYCONTROLSUCHTHATONESLABAREADOESNOTEXCEEDASTHESLABTHICKNESSINBOTHDIRECTIONSGTHSQUARELAYOUTSAREPREFERREDBUTTHEEOTHERWISETHERATIOOFTHELONGTOSHORTD13ITISRECOMMENDEDTHATSAWCUTSBEMADETEBATCHINGDONLYOCCURATEXPOSEDEDGESDURINGPOURINGWCUTTRICALCONDUITSSHALLNOTBEEMBEDDEDINSLABSONGRADEEXCEPTWHERESPECIFICALLYSTRUCTURALENGINEERPIPESANDCONDUITSSHALLFTHEWORKFPERMITTEDBYARCHITECTURALSPECIFICATIONSPERCENTOFCEMENTITIOUSMATERIALSANDSHALLROF12RELATIVETOCEMENTREPLACEDNOFLYASHFLATWORKORARCHITECTURALLYEXPOSEDTECONSTRUCTIONPROTECTCONCRETEFROMGTHINCOMPLIANCEWITHACI305AND306ESIGNEDBYACERTIFIEDLABORATORYANDRALENGINEERASRTO01EXPANSIONAT28DAYSINCONCRETEETEANDINTERIORCONCRETEEXPOSEDTOMOISTUREMINIMUMCOVERTOLERANCE338112145ANDSMALLER112386ANDLARGER238CONTACTWITHTHE1183418REINFORCEMENT11238ENGTHSHALLBEASFOLLOWSCONCRETESTRENGTHMAXWCRATIOAIRENTRAINMENT4500PSI0455513500PSI045NA
Footing to be below frost
depth of 36".
On steel build specs
Type VB construction.
3456ABCD5CONCRETESLABONGRADEOVERCOMPACTEDFILLSEEGSNPROVIDESLABJOINTSPERTYPICALDETAILWITHIN16HOURSOFBATCHTIMEFINISHFLOOR1000CONCRETESLABONGRADEF36F361125025025024661250561405656140562333WF16W1
WF10
WF10
WF10
WF16W1
WF16 / W1
333 TYP 101OPP103102102103YP01TYP101103103105105105TOW1010TOF980F66 104F66104F66104F48F54F66104F66104F66104SCALEFOUNDATIONPLAN31610
PROFE
S IONALENG
I
N
E R
S
T
ATE O F I D A HO
A
1/14/21
14134
D
VID B .P O R TER
LICENSED
HEADEDANCHORRODEMBEDSCHEDULEDIAMETERMINIMUMEMBEDMENTFROMTOPOFPIERWALL121258143416781812011425 WALLWSCHEDULEVERTICALREINFORCINGHORIZONTALREINFORCINGREMARKS4AT18OC4AT18OCFOOTINGSCHEDULENOTES1FORCONSTRUCTIONABOVEFOOTINGSEEDETAILS2FORMINIMUMCLEARANCECLROFREINFORCINGSEEGENERALSTRUCTURALNOTESGSNMARKLENGTHWIDTHTHICKNESSFOOTINGREINFORCINGREMARKSF3636361234EACHWAYTOPANDBOTTOMF4848481244EACHWAYTOPANDBOTTOMF5454541254EACHWAYTOPANDBOTTOMF6666661265EACHWAYTOPANDBOTTOMWF10CONT10826CONTBOTTOMWF16CONT161224CONTBOTTOMMONOPOURWSLABSTRIPFOOTING
PROJECT MANAGER:CAD OPERATOR:
DATE
JOB NO.:
STRUCTURAL ENGINEERS SEAL:PROJECT:
CLIENT:
REV.DATE BY DESCRIPTION
2
3
4
5
CURRENTREV
This drawing is the property of FROST Structural Engineering,
Inc. Legally, the drawing can NOT be copied in whole or in
pieces. It is only to be used for the project and site specifically
identified hereon and is not to be used on any other project.
Contractor shall carefully review all dimensions, details, and
conditions and report at once any error, inconsistency or
omission discovered before construction.
The contractor assumes full liability for deviations from the
intent of these plans.
1
Structural Engineering
fax: 208.227.8405
1020 E. Lincoln Road
Idaho Falls, ID 83401
phone: 208.227.8404
contact@frost-structural.com
S20 11421
LUTHY 60 X 125 METAL BUILDING
TITAN STEEL LLC
RMSDBPIF20-467
FOUNDATION PLAN
5101 W 5000 SOUTH
REXBURG, IDAHO
AVERIFYALLDIMENSIONSWITHALLARCHITECTURALDRAWINGSBALLSCHEDULEDMARKDESIGNATIONSMAYNOTNECESSARILYBEFOUNDONTHISPLANSCHEDULESARETYPICALTOTHISPROJECTCTHEDEPTHOFFOOTINGDIMENSIONINDICATEDINTHEGSNISAMINIMUMFOUNDATIONCONTRACTORSHALLCOORDINATEWITHTHESOILSREPORTANDOTHERTRADESTOINSURETHATTHESEMINIMUMSARESUFFICIENTFORTHEWORKSEETYPICALDETAILSFORADDITIONALREQUIREMENTSDW1W2ETCASSHOWNONPLANINDICATESCONCRETEORMASONRYWALLSSEEWALLSCHEDULEFORADDITIONALINFORMATIONEWF18WF24ETCASSHOWNONPLANINDICATESACONTINUOUSWALLFOOTINGSEEWALLFOOTINGSCHEDULEFORADDITIONALINFORMATIONFF36F48ETCASSHOWNONPLANINDICATESACONCRETEFOOTINGSEEFOOTINGSCHEDULEFORADDITIONALINFORMATION FOUNDATIONPLANNOTES1VERIFYDOOROPENINGWMETALBUILDINGMANUFACTURERDRAWINGS2PROVIDE20DIAMETEROR18SQUARECONCRETEPIERW105HOOKEDDOWELSAND33TIESINTOP5ANDAT8OCREMAINDERSIMILARTODETAIL104316x100LONG50EACHLEGHAIRPINWIDENGRADEBEAMATCONCRETEPIERASNECESSARYTOMAINTAIN3CLRAROUNDALLREINFORCING PLANKEYNOTES X
KEYNOTES1PREENGINEEREDBUILDING2CONCRETESTEMWALLSEEPLAN3SIDEWALKPAVEMENTORFINISHGRADEPERARCH4MINIMUMFOOTINGDEPTHSEEGSN5CONCRETEFOOTINGSEEPLAN6COMPACTEDSUBGRADEBELOWFOOTINGSEEPLAN7CONCRETESLABONGRADESEEPLAN101PREENGINEEREDBUILDINGATCONCRETEFOOTINGCSMB101NOSCALE3CLR
3"
CLR
1567332
4
KEYNOTES1PREENGINEEREDBUILDINGBEYOND2CONCRETESTEMWALLSEEPLAN3SIDEWALKPAVEMENTORFINISHGRADEPERARCH4MINIMUMFOOTINGDEPTHSEEGSN5CONCRETEFOOTINGSEEPLAN6COMPACTEDSUBGRADEBELOWFOOTINGSEEPLAN7CONCRETESLABONGRADESEEPLAN84BENTDOWELAT18OC102PREENGINEEREDBUILDINGATCONCRETEFOOTINGCSMB102NOSCALE3CLR
3"
CLR
15678323
4
1818KEYNOTES1PREENGINEEREDCOLUMNSEEPLAN2ANCHORBOLTSWNUTATBOTTOM3SIDEWALKPAVEMENTORFINISHGRADEPERARCH4MINIMUMFOOTINGDEPTHSEEGSN5CONCRETEFOOTINGANDCONCRETESTEMWALLBEYONDCONTREINFORCEMENTTROUGHPIERNOTSHOWNFORCLARITY6COMPACTEDSUBGRADEBELOWFOOTINGSEEPLAN7CONCRETEFOOTINGSEEPLAN8CONCRETEPIERW65HOOKEDDOWELSAND33TIESINTOP5ANDAT8OCREMAINDER9CONCRETESLABONGRADESEEPLAN103PREENGINEEREDCOLUMNATCONCRETEFOOTINGCSMB103NOSCALE3CLR
3"
CLR
76 39 3MIN3 1285
4
KEYNOTES1PREENGINEEREDCOLUMNSEEPLAN2SIDEWALKPAVEMENTORFINISHGRADEPERARCH3CONCRETESTEMWALLBEYONDCONTREINFORCEMENTTROUGHPIERNOTSHOWNFORCLARITY4MINIMUMFOOTINGDEPTHSEEGSN5COMPACTEDSUBGRADEBELOWFOOTINGSEEPLAN6CONCRETEFOOTINGSEEPLAN718ØCONCRETEPIERW85HOOKEDDOWELSAND33TIESINTOP5ANDAT8OCREMAINDER8CONCRETEGRADEBEAMSEEPLAN9HAIRPINASOCCURSSEEPLAN10CONCRETESLABONGRADESEEPLAN11ANCHORBOLTSWNUTATBOTTOM12CENTERLINEOFSTEELCOLUMNFOOTING104PREENGINEEREDCOLUMNATCONCRETEFOOTINGCSMB107NOSCALE3CLR
3"
CLR
5 3 1097 36MINLAP8922 11211
4
6 KEYNOTES1CONCRETESLABONGRADESEEPLAN2CONCRETEGRADEBEAMSEEPLAN105CONCRETEGRADEBEAMATCONCRETESLABCSMB104NOSCALE213CLR
3"
CLR
PERPLAN
PER
PLAN
PROFE
S IONALENG
I
N
E R
S
T
ATE O F I D A HO
A
1/14/21
14134
D
VID B .P O R TER
LICENSED
PROJECT MANAGER:CAD OPERATOR:
DATE
JOB NO.:
STRUCTURAL ENGINEERS SEAL:PROJECT:
CLIENT:
REV.DATE BY DESCRIPTION
2
3
4
5
CURRENTREV
This drawing is the property of FROST Structural Engineering,
Inc. Legally, the drawing can NOT be copied in whole or in
pieces. It is only to be used for the project and site specifically
identified hereon and is not to be used on any other project.
Contractor shall carefully review all dimensions, details, and
conditions and report at once any error, inconsistency or
omission discovered before construction.
The contractor assumes full liability for deviations from the
intent of these plans.
1
Structural Engineering
fax: 208.227.8405
1020 E. Lincoln Road
Idaho Falls, ID 83401
phone: 208.227.8404
contact@frost-structural.com
S30 11421
LUTHY 60 X 125 METAL BUILDING
TITAN STEEL LLC
RMSDBPIF20-467
FOUNDATION DETAILS
5101 W 5000 SOUTH
REXBURG, IDAHO