HomeMy WebLinkAboutFIRE SPRINKLER PLAN REVIEW - 20-00273 - Madison High School Field House Madison High School Field House – Rexburg 1 of 1
STATE FIRE MARSHAL
IDAHO DEPARTMENT OF INSURANCE
700 W. State Street, 3rd Floor
P.O. Box 83720
Boise, ID 83720-0043
(208) 334-4370 | www.doi.idaho.gov/sfm
PLAN REVIEW FOR FIRE SPRINKLER SYSTEMS
PLANS RECEIVED: July 30, 2020 APPROVED: August 4, 2020
REVIEWED BY: Javier Cervantes, ISFM Fire Plan Reviewer
PROJECT: Madison High School Field House
STREET ADDRESS: 2300 University Boulevard CITY: Rexburg
AHJ: Madison Fire Department
SPRINKLER CONTRACTOR: Viking Automatic Sprinkler Company
2022 N. Elder Street
Nampa, ID 83687
IDAHO LICENSE: FPSC-003
CONTACT NAME: Chris Green
chris.green@vikingsprinkler.net
PHONE NO: (208) 888-2762
SYSTEM DESIGNED BY: Chris Green
chris.green@vikingsprinkler.net
PHONE NO: (208) 888-2762
TYPE OF SYSTEM: NFPA 13 HEAD COUNT: 338
TOTAL SYSTEMS: 1 OCCUPANCY CLASSIFICATION: Light Hazard
CONSTRUCTION TYPE: Combustible AREA SQUARE FOOTAGE: 45,715
SCOPE OF WORK: Viking to install and to fully protect the Field House building with a wet fire
sprinkler system. Viking to install a complete wet fire sprinkler riser that
includes backflow preventer, FDC, and Wall P.I.V. as per the guildlines set
in NFPA-13 2016.
PLAN REVIEW COMMENTS: Approved with the following comment:
1. General information sign per NFPA 13, 25.6.1.
Approval of shop drawings is not intended to imply waiver or modification of any requirements of the Idaho State Statutes or
Rules, International Fire Code, NFPA Standards or any other applicable criteria.
It is acknowledged that backflow preventer is installed per the demand of the local water purveyor. The State Fire Marshal’s
Office and its personnel does not take any responsibility for the back flow device.