Re: Just4Kids Pediatric Urgent Care
1218 Bond Avenue
Rexburg, ID
Plans – 21‐00586
Dear Cody,
The following plan review responses are hereby submitted to address your comments dated
8/10/2021.
Comment: Is this building considered an ambulatory health facility? If so, it would need to meet
the requirements of section 422. Services offered do not render patients incapable of self‐
preservation.
Response: The clinic does not meet the definition for an Ambulatory Care Facility per section 422
and is classified as a Business Occupancy per section 304.1 Professional Services (architects,
attorneys, dentists, physicians, engineer, etc.). Services offered do not render patients incapable
of self‐preservation, and patients are provided care on less than a 24‐hour basis, with no overnight
stays.
Comment: Rear lot line within 5’, allows 10% in exterior wall openings.
Response: The exterior wall openings on the rear wall are 8.85%; below the allowed 10% threshold.
Comment: Need COMM check.
Response: ComCheck energy calculations were intended to be uploaded with the plan set.
ComCheck is now hereby provided.
Comment: Draft stopping in attic shall subdivide combustible attic space so that no horizontal area
exceeds 3,000 square feet per section 718.4.
12 Sunnen Dr. Suite 100
St. Louis, MO 63143
314.821.1100
The CASCO Diversified Corporation Companies
Response: The location of the draft stopping has been indicated on the A2.0 sheet.
Comment: Suspended ceiling to be installed to manufacturer’s specifications.
Response: Understood, a note stating such has been added to the ceiling plan A2.0.
Comment: Concealed spaces need to be fire blocked/draft stopped per section 718.
Response: Revised detail 7/A8.1.
Comment: Special inspector to be identified.
Response: Owner is in the process of hiring the Special Inspection agency and the information will
be supplied to the City upon receipt from the Owner.
Comment: Roof and roof fire classification?
Response: The roof classification has been added to the A1.2 sheet.
Comment: Signs to be posted.
Response: A note has been added to the floor plan A1.0 indicating the General Contractor shall
provide a maximum occupancy sign within the Lobby area indicating the building occupancy of 32.