Description : Iron Horse RV - Interior Finish
Address: 1076 S 12th W
Application Type:
Document Filename: 03 Iron Horse Architectural 090921.pdf Array
Comment Author Contact Information:
Author Name
Author Email
Author Phone NO.:
Stan Crittenden
Stan.Crittenden@rexburg.org
208-372-2314
Kyle Baldwin
Kyle.Baldwin@rexburg.org
208-372-2164
Cody Jones
Cody.Jones@rexburg.org
208-372-2173
Corrections in the following table need to be applied before a permit can be issued
Panic Hardware shall be installed as per IBC Section 1010.1.10
Review Report
Revisions Required
# 21-00725
Commercial - Remodel
Page Reference
Annotation
Author: Department
Status
Page
Review Comments
Applicant Response Comments
Type
G0.1
Free text
Cody Jones : Building
Open
1
as per city ordinance, buildings connot be partially sprinkled
903.3.9.1 in the code analysis now states that
even if only some areas require sprinklers and others do not.
"full building to be fire sprinklered".
G0.1
Free text
Cody Jones : Building
Open
1
seating at tables, counters and work areas comply with section
Note 1109.11 stating a min. o or seating
... shall be accessible" has been added to the
1109.11
code analysis
G0.1
Free text
Cody Jones : Building
Open
1
Special inspector needs to be identified.
Atlas Technical Consultants has been added tc
the project consultant list on the cover sheet.
G0.1
Free text
Cody Jones : Building
Open
1
Need Envelope COMM check. See attached.
G0.1
Free text
Cody Jones : Building
Open
1
Restrooms, rooms, occupant load and other directional
Note 10.04 on sheet A1.1 has been modified
signage to be installed.
to include the listed signage needs.
A1.1
Free text
Cody Jones : Building
Open
2
Exit lighting and exit signs to comply with sections 1008 and
These IBC references were added to the
1013.
Code Analysis on the cover sheet.
A4.1
Free text
Cody Jones : Building
Open
8
Grade to slope away from building 6" in first 10'.
Note 31.01 on sheet A4.1 has been modified.
A4.1
Free text
Cody Jones : Building
Open
8
36" min
Req'd dims have been added on sheet A4.1
A5.1
Comment
Cody Jones : Building
Open
9
Handrails and Guards meet the requirements of IBC Sections
General reference note 01.01 has been
1014 and 1015
modified to reference the IBC sections noted.
Approval of plans does not constitute approval of variance from code
Report Date: 10.06.2021 Pagel of 2
Page Reference
Annotation
Author: Department
Status
Page
Review Comments
Applicant Response Comments
Type
A5.1
Free text
Cody Jones : Building
Open
9
Minimum of one restroom to be ADA accessible.(with 60"
Restroom 108 is now shown with 60" ADA
turning radius.)
compliant turning radius.
A6.1
Comment
Cody Jones : Building
Open
11
Panic Hardware shall be installed as per IBC Section 1010.1.10
IBC Section 1010.1.10 does not require the us
of panic hardware in this project. No change
made.
A6.1
Free text
CodYJones Building
Open
11
Glass and glazing to meet requirements of Chapter 24.
A6.2
Free text
Cody Jones : Building
Open
12
Suspended ceiling to be installed to manufacturer
specifications.
This note has been added to window types A6
G0.1
Free text
Stan Crittenden : Fire
Open
1
The building will need to have fire sprinklers through out.
Noted on cover sheet.
G0.1
Free text
Stan Crittenden : Fire
Open
1
Will need to install a Knox Box for keys at or near the front of
Noted on cover sheet.
building. This is usually 1-2 months to order.
G0.1
Free text
Stan Crittenden : Fire
Open
1
Will need to verify that the existing fire hydrant on 12th West
or the new hydrant on the north end of the developement is
Noted on cover sheet.
close enough.
Approval of plans does not constitute approval of variance from code
Report Date: 10.06.2021 Page 2 of 2