HomeMy WebLinkAboutFOUNDATION DESIGN - 22-00385 - Tri-Steel - Commercial ShopFOUNDATION DESIGN FOR TRISTEEL BUILDING REXBURG, IDAHO For SteelVision Construction NOTES: 1. Foundation configuration provided by Trevor Haslem of SteelVision Construction. 2. Foundation loads from Behlen Drawings, Sheet 4, Job No. X3491 dated 02/2212022. 3. Exact anchor bolt locations shall be as shown on Behlen Drawings. 4. Concrete 28 -day strength shall be 3000 psi minimum. Slump shall be 3-4.5 in. 5. Reinforcement bars shall be ASTM A615 with Fy = 60,000 psi. 6. Concrete construction per ACI -318. 7. Allowable soil bearing pressure was assumed to be 2000 psf. 8. Rectangular piers shown on drawings may be replaced with circular piers formed by sonotubes if the reinforcement is the same, the concrete area is equal to that of the rectangular pier, and there is sufficient cover for the reinforcement as required by ACI -318- 9. The "jab" method of placing anchor bolts or vertical reinforcing bars is acceptable if the following conditions are met. a. The anchor bolts and vertical bars are placed when the footing concrete is still fluid enough for it to fill in around the bolts and bars when they are placed and hand vibrated into the correct position as shown on the Behlen drawings and the foundation details. b. The vertical bars are located, relative to the horizontal bars in the footing, as shown on the foundation details. The details show the horizontal bend on the vertical bars going below the horizontal bars in the footing. c. The vertical bars meet the ACI code development length requirements. INDEX TO ATTACHED DOCUMENTS Detail Page Foundation Plan 1 Detail 1— Foundation for Corner Column D1 2 Detail 2 — Foundation for Corner Column J1 3 Detail 3 — Foundation for Interior Column F1 4 Detail 4 - Foundation for Columns on Frameline 2 5 Detail 5 — Foundation for Corner Columns A3, A8, J3 & J8 6 Detail 6 — Foundation for Interior Columns on Framelines 3 & 8 7 Except Columns D3 & D8 Detail 7 — Foundation for Exterior Columns on Framelines 4 Thru 7 8 Except Columns J4 & J5 Detail 8 - Foundation for Columns J4 & J5 9 Detail 9 — Foundation for Column D3 (Detail G & Detail Q) 10 Page 1 of 2 Detail 14 — Foundation for Interior Columns D4 & Db 11 Detail 11 — Foundation for Interior Column DS 12 Detail 12 — Foundation for Interior Column. D7 13 Detail 13 Foundation for Column D8 14 Page 2 of 2 (9 @ i> m 9 ■ (a (U 0i 0 CLP Lr) CD C'l 0 i zco ED 4 Q � Z h C7R z � J 0E3 �z L4 R g Z0 lYn� 0D 73J 0 � LAW Li U C"l Cid W O d LTJ - f- LLJ - Q 0 d� W <1t0 R R W W F 4 F- A 0 0 LY_ p Irl (z W Li A OW� Liz �.� a �� �Wao Q W zJ DW d'� Z� 0 Jots Z(W3 �� o LL 0„ W L._C7 O �Q ] <LfZ `D �zm QdR CD l E CL ZrJ 0Q <L co Q MCL b LLZJ Jr UL1J t -W Z rJi(U F- (Y) ppU DL`z ~�J GlQ �DJ QL1l J L� D Z� L d J W g RLYCJ Z W O PUC 2(4OC! 0J�~ 0Zn W Z 0q LLJ W Q� W ❑a W~< d Z Z� W L)> - 0 LLJ 0 h 0 U U J X W �Ll J Q J DWS R : ZZ D Q L I- W L� z U �� U X r-- 00 (T R �z< ��h LL] ly a�LJ LSU JJ� 0 faW I-�' W� Q Q0�, CC)U n,-, 00 4R Q U W XT: F- W W o6 a- L, W Z I -W W tY J M W W vl F- W Z - l=l Z U Z rJ- Z W J W0 wn/ W 0 r AU (/i F O WLR A W L. ! z L] 0 r7l1- W F- 1- Q d Z R < A R R Z Z W 0 Z O L`6! z Li7 W C7R L, nWw 0 00 z OJ L�.DU Liu L,_� J <L � 0 IT J M ae (U U `-'U za-0 J Z (Y J[Y W ClJ Q 7) --i Q W �-- --i W Q Z Qz OF �JJ W O W z -QY W O w 7 RUU Ar RU qU WL�CL WLY WIY W OY 0 W 0 >- i Li % W O £fl L� LJ D Cn LL � i> m 9 ■ (a (U 0i 0 CLP Lr) CD C'l 0 ENDWALL 4 a a ` o a 16' SIDEWALL SILEWALL FTG, REINFORCEMENT: 2 #4 LONGITUDINAL BARS EVENLY �2n SPACED AND 44 TRANSVERSE BARS AT 18' ❑,C. ENDWALL FTG, REINFORCEMENT: 24'--I 3 #4 LONGITUDINAL BARS EVENLY SPACES AND #4 TRANSVERSE BARS AT 18' D.C. PLAN VIEW r -r1110 -7) in - nIA, ANCI-I❑R I)nl TS 24'� SECTION >; 4 IN AREA OF OLTS, THEN AT =LOW. 'YP, SIDEWALL & ENDWALL REINFORCEMENT i #4 H❑RIZ❑NTAL BARS EVENLY PACED, #4 VERTICAL BARS @ 18' D.C. 44 VERT. BARS IN ENLARGED WALL, EE PLAN VIEW, #4 LONGITUDINAL BARS q ENDWALL FO❑TING A TPAIVC'VF7r?CF" RAP'Z ra 1R" n_r_ TRISTEEL BUILDING DETAIL I F-EUNDATIAN EER CORNER CELUMN Ul 03/03/2022 18" 0 0 0 0 SIDEWALL 22' SIDEWALL FTG. REINFORCEMENT: 2 44 LONGITUDINAL BARS EVENLY SPACED AND #4 TRANSVERSE BARS AT 18° O.C. �2p FNDWALL FTG. REINF®RCEMFNT: 3 #4 LONGITUDINAL BARS EVENLY ENDWALL SPACED AND #4 TRANSVERSE BARS AT 18' D.C. 24` — -- 4 PLAN VIEW DIA, ANCH❑R BOLTS 4�1/2" ate' SECTIHN =S; 4 IN AREA ❑F BOLTS, THEN AT BELOW. TYP, SIDEWALL & ENDWALL RLINF"❑RCEMENT 5 #4 HORIZONTAL BARS EVENLY SPACED. #4 VERTICAL BARS @ 18" D.C. 5 #4 VERT, BARS IN ENLARGED WALL SEE PLAN VIEW. 3 #4 LLNGITUDINAL BARS IN ENDWALL F❑❑TING #4 TRANSVERSE BARS @ 18" ❑,C, TRISTE L BUILDING DETAIL 2 O❑UNDATION FOR CORNER COLUMN J1 03i0:3i2022 3' - PLAN VIEW TYPICAL ENDWALL REINFORCEMENT #4 VERT. BARS 18° O.C. 5 #4 HORIZ. BARS CONTINUOUS EVENLY SPACED IN WALL S[- Ell 11N TRISTEEL BUILDING OF ANCHOR BOLTS �S IN CORNERS 'ALL 4 44 BARS EACH WAY IN ENLARGED FOOTING DETAIL 3 FOUNDATILN FOR INTERI❑R COLUMN E1 03/C3/2022 5'- I I I I I I I I I I I GRADE I I I I I I I I I I 4 #6 VERTICAL BARS, EXTEND INTO FOOTING AS SHOWN I I 5'-0' SQ. 45 HAIRPIN BAR, EXTEND, INIMUM OF 5 FT, INT❑ SLAB, SIDEWALL FOUR 3/4" DIA. ANCHOR BOLTS, �--19.5" �- 5 #3 TIES; 4 IN AREA OF ANCHOR BOLTS, AND 1 AT 10' O.C. #5 HAIRPIN BAR INTO SLAB. PROVIDE MIN, /-❑F 3" CONCRETE BETWEEN BARSS & S❑IL, 24' 12" 5 #4 BARS EACH WAY SPACED AS SHOWN TRISTEEL BUILDIN❑ DETAIL 4 F❑UNDATI❑N FOR COLUMNS ON FRAMELINE 2 03/03/2022 11' I I I 3" SQ, 12' El I I I I I I I I I I I GRADE I I I I I I I I I I 4 #6 VERTICAL BARS, EXTEND INTO FOOTING AS SHOWN I I 5'-0' SQ. 45 HAIRPIN BAR, EXTEND, INIMUM OF 5 FT, INT❑ SLAB, SIDEWALL FOUR 3/4" DIA. ANCHOR BOLTS, �--19.5" �- 5 #3 TIES; 4 IN AREA OF ANCHOR BOLTS, AND 1 AT 10' O.C. #5 HAIRPIN BAR INTO SLAB. PROVIDE MIN, /-❑F 3" CONCRETE BETWEEN BARSS & S❑IL, 24' 12" 5 #4 BARS EACH WAY SPACED AS SHOWN TRISTEEL BUILDIN❑ DETAIL 4 F❑UNDATI❑N FOR COLUMNS ON FRAMELINE 2 03/03/2022 4' - /---18° WIDE SIDEWALL FOOTING PLAN, VIEW SIDEWALL 8. 14' I I I I I { I I I GRADE I E I I I E I I I I I I 4 46 VERTICAL BARS, EXTEND INT❑ F❑❑TING AS SHOWN I t 4'-6" SQ. SECTI❑N FOUR 3/4" DIA. X I8" - I/-- -- HAIRPIN BAR; EXTEND INT❑ AB MINIMUM OF 5'. ENDWALL ANCHER BOLTS, 5 #3 TIES; 4 IN AREA OF ANCHOR BOLTS AND ONE 10" ❑,C. #5 HAIRPIN BAR INTO SLAB. PR❑VIDE MIN, OF 3" CONCRETE BETWEEN BARS & SOIL. R4" 12" 6 #4 BARS EACH WAY EQUALLY SPACED TRISTEEL BUILDING DETAIL 5 FOUNDATION FOR CORNER COLUMNS Al A8 J3 & JS 03/03/2022 PLAN_ VIEW SECTION 'IN BAR. EXTEND 5' INT❑ SLAB. 3/4' DIA. ANCHOR DOLTS 19.51 7 #3 TIES; 4 IN AREA OF ANCHOR BOLTS, THEN AT 10' ❑,C. BELOW. #4 HAIRPIN INT❑ SLAB; PR❑VIDF MIN, OF 3' C❑NCRETE COVER BETWEEN BAR & S❑IL. i TYP. SIDEWALL & ENDWALL REINFORCEMENT 5 #4 HURIZENTAL BARS EVENLY SPACED. #4 VERTICAL BARS @ 18' U.C. 4 #4 VERT. BARS IN CORNERS OF ENLARGED WALL 3 #4 LONGITUDINAL BARS IN WALL FOUTING 4 TRANSVERSE BARS @ 18' U.C. TRISTEEL BUILDING DETAIL 6 F❑UNDATI❑N F❑R INTERI❑R COLUMNS ON FRAMELINES 3 & 8 EXCEPT COLUMNS D3 & T)8 -03/03/2022 4'-A i ---f ----18" WIDE SIDEWALL F❑❑TING PLAN VIEW SIDEWALL r8- 14' I ! I � ! I ! I ! I GRADE ! I I I I I I I I I I I I I 4 #6 VERTICAL BARS. EXTEND INTO FOOTING AS SHOWN 4'-6' SQ, WNUMIL111111 HAIRPIN BAR; EXTEND INTO �B MINIMUM OF 5'. FTWEEN PIERS FOR A5 & A6. EXTEND HNuuimu "lNumum PR❑VIDE MIN. Fl E- 3 " CONCRETE COVER BETWEEN BARS & S❑IL. FOUR 3/4" DIA. X 18" ANCHOR BOLTS. �- -19.5" 5 43 TIES; 4 IN AREA OF ANCHOR BOLTS AND ONE 10" ❑.C, #5 HAIRPIN BAR INT❑ SLAB, PR❑VIDE MIN, ❑F 3" CONCRETE BETWEEN BARS & S❑IL. 84" 12' 6 #4 BARS EACH WAY EQUALLY SPACED TRISTEEL BUILDING DETAIL 7 F❑UNATI❑N F❑R EXTERI❑R COLUMNS ❑N ERAMELINES 4 THRU 7 EXCEPT COLUMNS- J4 & J5 osiaaieozz I I I I I I � I 7'-6' SQ. 30' I I I I I I I j I 18' WIDE CONTINUOUS- WALL ❑NTINU❑US WALL FOOTING I 4 #6 VERTICAL BARS, EXTEND INT❑ FOOTING AS SHOWN IN SECTI❑N VIEW. 45 HAIRPIN BAR: EXTEND INT❑ SLAB MINIMUM OF 5'. 6 #6 VERTICAL BARS, EXTEND INTO FOOTING AS SHOWN IN SECTION VIEW. P #4 X -TIE BARS BETWEEN WIND BENT COLUMNS PLACE IN SLAB AND PROVIDE MINIMUM OF 3' OF CONCRETE BETWEEN S❑IL & BARS PLAN VIEW_ SIX 3/4' DIA. ANCH❑R BOLTS SEE BEHLEN ANCH❑R BOLT PLAN. 6' -{� 14' I I I 10 #3 TIES] 5 FOR EACH COLUMN LIN PIER. I SEE PLAN VIEW, 8 IN AREA OF ANCHOR BOLTS, THEN 2 AT 10' I #5 HAIRPIN BAR INT❑ SLAB, PR❑VIDE GRADE i MINIMUM OF 3' CONCRETE BETWEEN ° I BAR & S❑IL. FITTE l I 3' MIN. CL. I 24' 1 I 1 i 12' 7'-6' SQ. 9 #5 BARS EACH WAY EQUALLY SPACED TRISTEEL BUILDING DETAIL 8 FOUNDATION E❑R COLUMNS J4 & .J5 03/03/2022 SIDE WALL ON COLUMN LINE D SEVEN #3 TIES, FOUR IN AREA ❑F ANCHOR BOLTS, & THREE BELOW @ 10' SPACING, I I s 3 I 1 I I I 1 I ENDWALL REINFORCEMENT; #4 VERT. @ 18' O.C., AND 5 #4 HORIZ, EQUALLY SPACED„ FOUR #4 VERT, BARS IN ENLARGED WALL, EXTEND INT❑ FOOTING AS SHOWN, I I I I 1 I I I I I_ 0 0 ° ° ° o ° °10' 1 6'-0' SQ, -F4- T 1 I I I I i I I I I I I I I ISR-LMv/ialA FOUR 3/4' ANCHOR SULTS (DETAIL Q) —�'F—lrz• rn 12' 101— n 0' �. 19.s• -I FOUR 3/4' ANCH❑R BOLTS (DETAIL G) �F--lrz• -19.5' 4 �— FLOOR SLAB FOUR #3 TIES IN AREA j OF ANCH❑R BOLTS. 2`—�° FOUR #5 VERT, BARS IN PIER. EXTEND INT❑ FO❑TING AS SHOWN. I I V 16' 6'-0' SQ. ilwallm 7 #5 BARS EACH WAY EQUALLY SPACED TRISTEEL BUILDING DETAIL 9 FOUNDATION E MN D (DETAIL & DFTAIL. ) 03/04/2022 8'-0" SQ. PLAN VIEW TRISTEEL BUILDING DETAIL 10 F❑UNDATI❑N F❑R INTERI❑R COLUMNS D4 & D6 03/04/2022 6" SLAB 0 0 0 fl 4 PLAN VIEW TRISTEEL BUILDING DETAIL 10 F❑UNDATI❑N F❑R INTERI❑R COLUMNS D4 & D6 03/04/2022 6" SLAB 8'-6" SQ PLAN VIEW TUU i IUiN TRIST EL BUILDING DETAIL 1.1 FOUNDATION FOR INTERIOR COLUMN D5 6" SLAB 0 0 0 0 a 0 0 0 PLAN VIEW TUU i IUiN TRIST EL BUILDING DETAIL 1.1 FOUNDATION FOR INTERIOR COLUMN D5 6" SLAB 6'-01 SQ, o ll o oil 0 PLAN, VIEW rMl IM " /AP AA1f1Imm nns TC eT—TATI rN TRISTEEL BUDDING DETAIL 12 F❑UNDATIUN FOR INTERI❑R SULUMN__-7 m_ • I I I I I I 2"1 r I I I I I I i II I I I I I I I I I I ! I I I J (� j E I p p /-6' I/ Q. L0� /I I p p I I I I I I I I I I l I I I I I J I I I I I I I 18" ENDWALL I I I I PLAN VIEW Ir--� I I I I I I I I I I I I € I I I I I 4'-0" I I I I I I I I I I I I I I I I I I I FOUR 3/48 ANCHOR DOLTS FLOOR SLAB FOUR #3 TIES IN AREA I OF ANCHOR BOLTS, 24" -FOUR #5 VERT. BARS IN PIER. EXTEND INTO] POUTING AS SHOWN. 4'-6" SQ. 6 #4 BARS EACH WAY EQUALLY SPACED SECTIUN TRISTEEL BUILDING DETAIL 13 FOUNDATION FOR COLUMN D3 03/05/2022