HomeMy WebLinkAboutLOAD SHORT FORM - 22-00316 - 635 S 2470 W - New SFRCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-May-05 17:24:04 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF6B17 princeton.rup Calc = MJ8 House faces: E SF6B17Job:Load Short Form Date:Entire House Vince ByramBy: High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com Project Information Cody PuzeyFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Information InfiltrationClgHtg SimplifiedMethod89-6Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1476Design TD (°F) H-Daily range 5050Inside humidity (%) -3162Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Goodman Mfg.Make Goodman Mfg. Trade GOODMAN Trade GOODMAN, JANITROL, AMANA DISTI... Model GMH950703BX Cond GSX130241C* AHRI ref 2002183 Coil Capf3030bx AHRI ref 4765510 Efficiency 95 AFUE Efficiency 11.0 EER, 13 SEER Heating input Btuh69000 Sensible cooling Btuh16100 Heating output Btuh52440 Latent cooling Btuh6900 Temperature rise °F62 Total cooling Btuh23000 Actual air flow cfm920 Actual air flow cfm767 Air flow factor cfm/Btuh0.027 Air flow factor cfm/Btuh0.062 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Room2 52 0 0 0 0 Room3 150 2249 280 61 17 Room4 250 3514 1227 95 76 Room5 242 2129 1649 58 103 Room6 169 2805 1448 76 90 Room7 50 589 88 16 5 Room8 154 2146 1120 58 70 Room9 132 2793 1157 76 72 Room10 35 898 414 24 26 Room11 82 3287 878 89 55 Room1 604 13605 4056 368 253 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-May-05 17:24:04 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 2 S:\High Country\Wrightsoft\SF6B17 princeton.rup Calc = MJ8 House faces: E Entire House d 1920 34014 12318 920 767 Other equip loads 1821 335 Equip. @ 0.94 RSM 11894 Latent cooling 0 TOTALS 1920 35835 11894 920 767 2022-May-05 17:24:04 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF6B17 princeton.rup Calc = MJ8 House faces: E SF6B17Job:Building Analysis Date:Entire House Vince ByramBy: High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com Project Information Cody PuzeyFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) SimplifiedMethod)H(34-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Doors Ceilings Floors Infiltration Ventilation % of loadBtuhBtuh/ft²Component 30.5109234.9Walls 15.9570122.8Glazing 2.590022.0Doors 5.017771.5Ceilings 12.846003.93.9Floors 28.2101144.0Infiltration 00Ducts 00Piping 00Humidification 5.11821Ventilation0Adjustments 100.035835Total Cooling Walls Glazing Other Ceilings InfiltrationVentilation % of loadBtuhBtuh/ft²Component 8.310490.5Walls 70.8896535.9Glazing 1.72195.4Doors 7.89820.8Ceilings 1.11340.1Floors 7.79690.4Infiltration 00Ducts 2.7335Ventilation 00Internal gains 00Blower 0Adjustments 100.012653Total Latent Cooling Load = 0 Btuh Overall U-va lue = 0.0 65 Btuh/ft²-°F Data entries checked. 2022-May-05 17:24:05 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF6B17 princeton.rup Calc = MJ8 House faces: E SF6B17Job:Component Constructions Date:Entire House Vince ByramBy: High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com Project Information Cody PuzeyFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) SimplifiedMethod)H(34-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Frm wall, vnl ext, 3/8" wood shth, r-22 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 2780.4728904.9422.00.065585n 2510.4726184.9422.00.065530e 2700.4728164.9422.00.065570s 2500.4725994.9422.00.065526w 10490.47109234.9422.00.0652211all Partitions (none) Windows 61C: 61C; NFRC rated (SHGC=0.32); 6.67 ft head ht 0.30095e 324934.1216922.80 27918.634222.800.30015s 477634.1318922.800.300140w 830433.2570122.800.300250all Doors 11P0: Door, mtl pur core type 2195.3790022.010.50.29041e Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 5/8" gypsum board int fnsh 9820.8417771.5250.00.0201169 Floors 19A-30bscp: Part floor, carpet flr fnsh, r-30 ins, frm flr, 12" thkns, 1/2" gypsum board int fnsh 1340.407292.1730.00.034336 22B-10cpm: Bg floor, heavy dry or light damp soil, on grade depth, r-10 edge ins, carpet flr fnsh 00377727.010.00.355140 009427.010.00.3553 00387127.010.00.355143all Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-May-05 17:24:05 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF6B17 princeton.rup Calc = MJ8 House faces: E SF6B17Job:Project Summary Date:Entire House Vince ByramBy: High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com Project Information Cody PuzeyFor:3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Notes: Design Information Idaho Falls, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-6 Outside db °F89Inside db °F70 Inside db °F75 Design TD °F76 Design TD °F14Daily range H Relative humidity %50Moisture difference gr/lb-31 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh34014 Structure Btuh12318 Ducts Btuh0 Ducts Btuh0Central vent (26 cfm)1821 Btuh Central vent (26 cfm)Btuh335 Outside air Outside airHumidificationBtuh0Blower Btuh0 Piping Btuh0Equipment load Btuh35835 Use manufacturer's data n Rate/swing multiplier 0.94InfiltrationEquipment sensible load Btuh11894 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh-1347 Ducts Btuh0Central vent (26 cfm)Btuh-466 CoolingHeating Outside air19201920Area (ft²)Equipment latent load Btuh0 1728017280Volume (ft³)Air changes/hour 0.260.50 Equipment Total Load (Sen+Lat)Btuh11894 Equiv. AVF (cfm)75144 Req. total capacity at 0.70 SHR ton1.4 Heating Equipment Summary Cooling Equipment Summary Make Goodman Mfg.Make Goodman Mfg.Trade GOODMAN Trade GOODMAN, JANITROL, AMANA DISTI... Model GMH950703BX Cond GSX130241C*AHRI ref 2002183 Coil Capf3030bx AHRI ref 4765510Efficiency95 AFUE Efficiency 11.0 EER, 13 SEER Heating input Btuh69000 Sensible cooling Btuh16100Heating output Btuh52440 Latent cooling Btuh6900 Temperature rise °F62 Total cooling Btuh23000Actual air flow cfm920 Actual air flow cfm767 Air flow factor cfm/Btuh0.027 Air flow factor cfm/Btuh0.062Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 1.00 2022-May-05 17:24:05 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF6B17 princeton.rup Calc = MJ8 House faces: E SF6B17Job:AED Assessment Date:Entire House Vince ByramBy: High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com Project Information Cody PuzeyFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) )H(34-Da ily ra nge (°F) 60-We t bu lb (°F) 7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limit Gl a z i n g l o a d ( B t u h ) Hour of Day 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 39.2%. House does not have adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 661 Btuh (PFG - 1.3*AFG) Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-May-05 17:24:05Right-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1S:\High Country\Wrightsoft\SF6B17 princeton.rup Calc = MJ8 House faces: E SF6B17Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com 1 Room name Entire House Room2 2 Exposed wall 278.0 ft 17.0 ft 3 Room height 9.0 dft 9.0 heat/coolft 4 Room dimensions ft4.0x13.0 5 Room area 1920.0 f t²52.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 585 585 2890 278 36 36 178 17 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 666 530 2618 251 117 117 578 56 .GG 61C61C 0.3000.300 ee 22.8022.80 34.1434.14 95 0 2169 3249 0 0 0 0 .DD 11P011P0 0.2900.290 ee 22.0422.04 5.365.36 41 41 900 219 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 585 570 2816 270 0 0 0 0 GG 61C61C 0.3000.300 ss 22.8022.80 18.6018.60 15 0 342 279 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 666 526 2599 250 0 0 0 0 GG 61C61C 0.3000.300 ww 22.8022.80 34.1434.14 140 0 3189 4776 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 1169 1169 1777 982 0 0 0 0 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 336 336 729 134 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 773 140 3777 0 52 17 459 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 60 3 94 0 0 0 0 0 6 c) AED excursion 661 -16 Envelope loss/gain 23900 11349 1214 56 12 a)Infiltration 10114 969 618 59 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)34014 12318 1833 115 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 -1833 -115 14 Subtotal 34014 12318 0 0 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 34014 12318 0 0 Air required (cfm)Air required (cfm)920 767 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-May-05 17:24:05Right-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 2S:\High Country\Wrightsoft\SF6B17 princeton.rup Calc = MJ8 House faces: E SF6B17Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com 1 Room name Room3 Room4 2 Exposed wall 25.0 ft 31.0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft15.0x10.0 ft250.0x1.0 5 Room area 150.0 f t²250.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 0 0 0 0 135 115 567 54 .GG 61C61C 0.3000.300 ee 22.8022.80 34.1434.14 0 0 0 0 20 0 459 688 .DD 11P011P0 0.2900.290 ee 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 135 135 667 64 144 129 637 61 GG 61C61C 0.3000.300 ss 22.8022.80 18.6018.60 0 0 0 0 15 0 342 279 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 90 90 445 43 0 0 0 0 GG 61C61C 0.3000.300 ww 22.8022.80 34.1434.14 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 150 150 228 126 250 250 380 210 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -40 -174 Envelope loss/gain 1339 193 2386 1119 12 a)Infiltration 910 87 1128 108 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2249 280 3514 1227 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 2249 280 3514 1227 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2249 280 3514 1227 Air required (cfm)Air required (cfm)61 17 95 76 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-May-05 17:24:05Right-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 3S:\High Country\Wrightsoft\SF6B17 princeton.rup Calc = MJ8 House faces: E SF6B17Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com 1 Room name Room5 Room6 2 Exposed wall 14.0 ft 26.0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft242.0x1.0 ft13.0x13.0 5 Room area 242.0 f t²169.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 0 0 0 0 117 117 578 56 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 0 0 0 0 0 0 0 0 .GG 61C61C 0.3000.300 ee 22.8022.80 34.1434.14 0 0 0 0 0 0 0 0 .DD 11P011P0 0.2900.290 ee 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ss 22.8022.80 18.6018.60 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 126 96 474 46 117 92 454 44 GG 61C61C 0.3000.300 ww 22.8022.80 34.1434.14 30 0 684 1024 25 0 570 854 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 242 242 368 203 169 169 257 142 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 60 3 94 0 0 0 0 0 6 c) AED excursion 327 262 Envelope loss/gain 1620 1600 1859 1357 12 a)Infiltration 509 49 946 91 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2129 1649 2805 1448 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 2129 1649 2805 1448 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2129 1649 2805 1448 Air required (cfm)Air required (cfm)58 103 76 90 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-May-05 17:24:05Right-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 4S:\High Country\Wrightsoft\SF6B17 princeton.rup Calc = MJ8 House faces: E SF6B17Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com 1 Room name Room7 Room8 2 Exposed wall 5.0 ft 14.0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft5.0x10.0 ft14.0x11.0 5 Room area 50.0 f t²154.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 45 45 222 21 18 18 89 9 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 0 0 0 0 99 74 366 35 .GG 61C61C 0.3000.300 ee 22.8022.80 34.1434.14 0 0 0 0 25 0 570 854 .DD 11P011P0 0.2900.290 ee 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 0 0 0 0 9 9 44 4 GG 61C61C 0.3000.300 ss 22.8022.80 18.6018.60 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ww 22.8022.80 34.1434.14 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 50 50 76 42 154 154 234 129 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 50 50 108 20 154 154 334 62 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -13 -21 Envelope loss/gain 407 71 1637 1071 12 a)Infiltration 182 17 509 49 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)589 88 2146 1120 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 589 88 2146 1120 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 589 88 2146 1120 Air required (cfm)Air required (cfm)16 5 58 70 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-May-05 17:24:05Right-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 5S:\High Country\Wrightsoft\SF6B17 princeton.rup Calc = MJ8 House faces: E SF6B17Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com 1 Room name Room9 Room10 2 Exposed wall 23.0 ft 7.0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft12.0x11.0 ft5.0x7.0 5 Room area 132.0 f t²35.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 108 108 534 51 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 99 74 366 35 0 0 0 0 .GG 61C61C 0.3000.300 ee 22.8022.80 34.1434.14 25 0 570 854 0 0 0 0 .DD 11P011P0 0.2900.290 ee 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ss 22.8022.80 18.6018.60 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 0 0 0 0 63 55 272 26 GG 61C61C 0.3000.300 ww 22.8022.80 34.1434.14 0 0 0 0 8 0 182 273 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 132 132 201 111 0 0 0 0 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 132 132 286 53 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 35 7 189 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -27 91 Envelope loss/gain 1956 1077 643 390 12 a)Infiltration 837 80 255 24 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2793 1157 898 414 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 2793 1157 898 414 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2793 1157 898 414 Air required (cfm)Air required (cfm)76 72 24 26 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-May-05 17:24:05Right-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 6S:\High Country\Wrightsoft\SF6B17 princeton.rup Calc = MJ8 House faces: E SF6B17Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com 1 Room name Room11 Room1 2 Exposed wall 15.0 ft 101.0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft82.0x1.0 ft604.0x1.0 5 Room area 82.0 f t²604.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 81 81 400 38 180 180 889 85 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 0 0 0 0 216 150 742 71 .GG 61C61C 0.3000.300 ee 22.8022.80 34.1434.14 0 0 0 0 25 0 570 854 .DD 11P011P0 0.2900.290 ee 22.0422.04 5.365.36 0 0 0 0 41 41 900 219 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 0 0 0 0 297 297 1467 141 GG 61C61C 0.3000.300 ss 22.8022.80 18.6018.60 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 54 39 193 19 216 154 761 73 GG 61C61C 0.3000.300 ww 22.8022.80 34.1434.14 15 0 342 512 62 0 1411 2113 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 0 0 0 0 22 22 33 18 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 82 15 405 0 604 101 2725 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 168 102 Envelope loss/gain 1339 738 9499 3677 12 a)Infiltration 546 52 3675 352 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1885 790 13173 4029 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 1402 88 431 27 14 Subtotal 3287 878 13605 4056 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 3287 878 13605 4056 Air required (cfm)Air required (cfm)89 55 368 253 Job #: SF6B17 Performed by Vince Byram for: Cody Puzey 3758 Yellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 High Country Heating P.O. Box 627 Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 highcountryhtg@gmail.com Scale: 1 : 62 Page 1 Ri ght -Suit e ® Un iv ersal 2019 19.0.13 RSU20477 2022-May-05 17:24:19 ...Wrightsoft\SF6B17 princeton.rup N 2nd Story Room3 Room4 Room5 Room6 Room7 Room8 Room9 103 cfm 70 cfm 156 cfm 108 cfm 48 cfm 61 cfm 48 cfm 90 cfm 16 cfm 70 cfm 76 cfm 90 cfm 76 cfm Job #: SF6B17 Performed by Vince Byram for: Cody Puzey 3758 Yellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 High Country Heating P.O. Box 627 Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 highcountryhtg@gmail.com Scale: 1 : 62 Page 2 Ri ght -Suit e ® Un iv ersal 2019 19.0.13 RSU20477 2022-May-05 17:24:19 ...Wrightsoft\SF6B17 princeton.rup N Main Floor Room1 Room2 Room10 Room11 36'-0" 6 " 92 cfm 92 cfm 92 cfm 92 cfm 26 cfm 89 cfm 481 cfm 14x3.25 6 " 14x3.25 12 x 8 6 " 14x3.25 6 "6 "6 " 6 "6 "6 " 6 " 6 " 16 x 8 6 " 4-14x3.25 16 x 814x3.25 14x3.25 6 " 12 x 8 12 x 8 6 " 2022-May-05 17:24:06 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF6B17 princeton.rup Calc = MJ8 House faces: E SF6B17Job:Duct System Summary Date:Entire House Vince ByramBy: High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com Project Information Cody PuzeyFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0.34in H2O0.34 Available static pressure in H2O0.36in H2O0.36 Supply / return available pressure 0.165 / 0.195 in H2O in H2O0.165 / 0.195 Lowest friction rate in/100ft0.075in/100ft0.075 Actual air flow cfm767cfm920 Total effective length (TEL)ft481 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st1B180.040.0ShMt0x06.00.07563923401hRoom1 st1150.023.0ShMt0x06.00.09563923401hRoom1-A st1B170.049.0ShMt0x06.00.07563923401hRoom1-B st1A180.038.0ShMt0x06.00.07663923401hRoom1-C st1165.013.0ShMt0x06.00.0932624414cRoom10 st1175.011.0ShMt0x06.00.08955893287hRoom11 st1A150.039.0ShMt0x06.00.08717612249hRoom3 st1A170.041.0ShMt0x06.00.07838481757hRoom4 st1A160.046.0ShMt0x06.00.08038481757hRoom4-A st1130.025.0ShMt0x06.00.106103581649cRoom5 st1160.015.0ShMt0x06.00.09490761448cRoom6 st1175.09.0ShMt0x06.00.089516589hRoom7 st1140.033.0ShMt0x06.00.09570581120cRoom8 st1175.020.0ShMt0x06.00.08472762793hRoom9 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st1 Peak AVF 920 767 0.075 1035 13.7 16x8 ShtMetl st1A Peak AVF 432 283 0.075 648 10.7 12x8 ShtMetl st1 st1B Peak AVF 184 126 0.075 276 7.8 12x8 ShtMetl st1A 2022-May-05 17:24:06 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 2 S:\High Country\Wrightsoft\SF6B17 princeton.rup Calc = MJ8 House faces: E Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb2 0x 760 90 105.0 0.186 285 4.9 3.25x14 10x9 SJSp rt1 rb4 0x 580 70 96.0 0.203 221 4.4 3.25x14 10x9 SJSp rt1 rb3 0x 760 72 127.0 0.154 239 4.8 3.25x14 10x9 SJSp rt1 rb1 0x 4810 333 261.0 0.075 381 11.1 4-3.25x14 4-10x36 SJSp rt1 rb6 0x 740 108 141.0 0.139 342 5.6 3.25x14 10x9 SJSp rt1 rb5 0x 1560 94 194.0 0.101 493 6.9 3.25x14 10x9 SJSp rt1A Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 920 767 0.075 1035 13.7 16x8 ShtMetl rt1A Peak AVF 156 94 0.101 234 6.9 12x8 ShtMetl rt1