HomeMy WebLinkAboutENGINEER LETTER - 22-00024 - 64 S 3rd E - Solar PanelsDate: 16 February 2022
Big Dog Solar Energy
620 Pheasant Ridge Dr
Chubbuck, ID 83202
Sarah Avila Residence: 64 South 3rd East, Rexburg, ID 83440
Dear Sir/ Madam,
Conclusion
Page 1 of Sarah Avila letter
Structural Letter of Approval
Terra Engineering Consulting (TEC) has performed a structural analysis for the existing framing
and load conditions and determined that the structure can support the additional load of the
proposed solar panel system. TEC has reviewed the site survey, photographs of the existing
framing, and the proposed PV array. The attached calculations are based off the assumptions that
the existing structural components are in good condition, that they meet industry standards, and
that the site survey provided by the client is accurate. The design assumptions the calculations
are based off are located in the attached References page. The contractor shall notify TEC of any
damage to the roof system encountered at the time of installation. The design of the solar panel’s
mounting hardware is to be provided by the manufacturer or installer. Structural observation or
construction inspections will not be performed by TEC or their representatives.
The total load of the solar panels is assumed to not exceed 3 psf, and the typical 20 psf live load
will not be present in the area of the panels, as defined per Section 1607.13.5.1 in 2018 IBC. The
structural evaluation shows that existing framing is able to withstand the additional load while
meeting current standards, allowing the structure to remain unaltered; see calculations and span
table attached. Regarding lateral loads, the wind load controls, and due to the low profile of the
panels (3” to 6”) as well as PV frame, wiring, conduit, and structural component below the
module causing restriction in airflow which allow it to be considered as “partially enclosed
structure”; thus the additional pressure on the structure is considered negligible. The connection
hardware is pre-engineered by manufacturer, and designed for metal roofs installations. The
addition of total PV system weight result in an increase under 10% of the total roof weight, and
meets the seismic requirements in Section 502.5 of 2018 IEBC.
TEC concludes that the installation of solar panels on existing roof will not affect the structure,
and allows it to remain unaltered under the applicable design standards. These conclusions are
based on the attached calculations.
1863 GOLDENROD WAY / NORTH SARATOGA SPRINGS, UT 84045 / T (801)-616-6204
General Instructions
Best Regards,
Terra Engineering Consulting, PLLC
Brice Somers, PE
President
Installation and waterproofing shall be performed within accepted industry standards.
Page 2 of Sarah Avila letter
2/16/2022
1863 GOLDENROD WAY / NORTH SARATOGA SPRINGS, UT 84045 / T (801)-616-6204
References
Design Parameter
Risk Category: II
Ground Snow load: 45 psf
Roof Snow load: 31.2 psf
Design Wind Speed: 115 mph (3 sec gust) per ASCE 7-16
Seismic Design Category: D
Wind Exposure Category: C
Existing Roof Structure
Roof framing: 2x6 Rafters at 24” O.C.
Roof material: Metal seam
Roof slope: 30°
Roof type: Gable
Solar Panels
Weight: 2.8 psf
Code: 2018 International Building Code/ International Existing Building Code, ASCE 7-16, and
National Design Specification for Wood Construction (NDS) 2015 Edition
Connection: Pre-engineered clamps
Page 3 of Sarah Avila letter
1863 GOLDENROD WAY / NORTH SARATOGA SPRINGS, UT 84045 / T (801)-616-6204
Date:2/16/2022
Client:Sarah Avila
Subject:Gravity load
Gravity load calculations
Snow load (S)Existing w/ solar panels
Roof slope (°):30 30
Ground snow load, pg (psf):45 45 ASCE 7-16, C7.2
Terrain category:C C ASCE 7-16, table 7.3-1
Exposure of roof:Fully exposed Fully exposed ASCE 7-16, table 7.3-1
Exposure factor, Ce:0.9 0.9 ASCE 7-16, table 7.3-1
Thermal factor, Ct:1.1 1.1 ASCE 7-16, table 7.3-2
Risk Category:II II ASCE 7-16, table 1.5-1
Importance Factor, Is:1 1 ASCE 7-16, table 1.5-2
Flat roof snow load, pf (psf):31.2 31.2 ASCE 7-16, equation 7.3-1
Minimum roof snow load, pm (psf):0 0 ASCE 7-16, equation 7.3-4
Roof Surface type:
Unobstructed
Slippery surface
Unobstructed slippery
surface ASCE 7-16, C7.4
Roof slope factor, Cs:0.67 0.67 ASCE 7-16, C7.4
Sloped roof snow load, ps [psf]:20.9 20.9
Roof dead load (D)
Roof pitch/12 6.9
Metal seam 0.8 psf 1/2" Gypsum clg.0.5 psf
1/2" plywood 1 psf Insulation 0.5 psf
Framing 2.5 psf M, E & Misc 1 psf
Roof DL without PV
arrays 7.3 psf
PV Array DL 2.8 psf
Roof live load (Lr)Existing w/ solar panels
Roof Live Load 20 0 2018 IBC, Section 1607.13.5.1
ASD Load combination:
Existing With PV array
D [psf]7.3 10.1 ASCE 7-16, Section 2.4.1
D+L [psf]7.3 10.1 ASCE 7-16, Section 2.4.1
D+[Lr or S or R] [psf]28.2 31.0 ASCE 7-16, Section 2.4.1
23.0 25.8 ASCE 7-16, Section 2.4.1
Maximum gravity load [psf]:28.2 31.0
ASCE 7-16, equation 7.4-1, Design
Snow Load (S)
D+0.75L+0.75[Lr or S or R] [psf]
Date:2/16/2022
Client:Sarah Avila
Subject:Beam calculator
Beam Design (Roof)2x6 Rafters at 24 in o.c., span 11 ft max.
Load Combination
Combo DL LL W SL LLR E Sum
1 1.4 10.1 0 0 0 0 0 20.9 0 0 0 14.14
2 1.2 10.1 1.6 0 0 0 0.5 20.9 0 0 0 22.57
3 1.2 10.1 1 0 1 0 1.6 20.9 0 0 0 45.56
4 1.2 10.1 1 0 1 0 0.5 20.9 0 0 0 22.57
5 1.2 10.1 0 0 0 0 0.2 20.9 0 1 0 16.3
6 0.9 10.1 0 0 1 0 0 20.9 0 0 0 9.09
7 0.9 10.1 0 0 0 0 0 20.9 0 1 0 9.09
Roof
DL 10.1 psf (see Gravity load roof DL)
S 20.9 psf
W
E
LL 0 psf
RLL 0 psf (see Gravity load LL with PV arrays)
U 45.56 psf
beam spacing 2 ft o.c.
uniform load 91.12 plf
span 11 ft
Mu = w(l^2)/8 1378.19 lb-ft
Number of joists 1
Flexure design
Cr 1.15 (2015 NDS Supp, p32)
Timber grade DFL#2 (2015 NDS Supp, table 4A)
Fb 900 psi (set SPF#2 as default)
Kf 2.54 (2015 NDS, table 2.3.5)
bending fact.0.85 (2015 NDS, table 2.3.6)
dimension
Cf (table 4A,
NDS supp
2015, p32)
S in^3
(table1B,
NDS supp
2015)
Fbu =
Mu/S
(psf)Fbu (psi)
moment of
inertia in^4
(table 1B,
NDS supp)
2x6 1.3 7.56 315014.9 2187.603 20.8
purlin size
λ (Table N3,
NDS 2015
p184)F'bn (psi) Fbu Fbu < F'bn
2x6 0.8 2323.9476 2187.603 Works
Design for deflection
we going to assume these calculations for U1 only since its clearly higher
we use the following equation to calculation max deflection, minimum interia, and deflection
service load combination:D+S
U 31 lb
Uniform load 62 plf
*convert all the units in the equaion to inch
max def. (ft)
E psi(Table
4A)w (plf)l (ft)
I (min)
(in^4)
Imin<
Ipurlin
0.055 1600000 62 11 19.34109 Works
Design for Shear
fvu = 1.5V/A V is shear Vu, and A cross sectional area of purlin found in table 1B
uniform load 91.12 plf
Vu 501.16 lb Vu = wl/2
Framing cross section 8.25 in^2
fvu 91.12 psi
Fv 180 psi (for DFL#2)
F'vn 311.04 psi
F'vn > fvu Works
Beam works