Loading...
HomeMy WebLinkAboutFS APPROVAL - 21-00765 - BYUI Manwaring Center Academic Advising - RemodelBYU-Idaho Academic Advising Remodel TI – Rexburg 1 of 1 STATE FIRE MARSHAL IDAHO DEPARTMENT OF INSURANCE 700 W. State Street, 3rd Floor P.O. Box 83720 Boise, ID 83720-0043 (208) 334-4370 | www.doi.idaho.gov/sfm PLAN REVIEW FOR FIRE SPRINKLER SYSTEMS PLANS RECEIVED: February 16, 2022 APPROVED: March 8, 2022 REVIEWED BY: Javier Cervantes, ISFM Fire Plan Reviewer PROJECT: Brigham Young University-Idaho Academic Advising Remodel TI STREET ADDRESS: 525 S Center St CITY: Rexburg AHJ: Madison Fire Department SPRINKLER CONTRACTOR: 3-D Fire Protection 6312 S. Burgraff Way Idaho Falls, ID 83401 IDAHO LICENSE: FPSC-008 CONTACT NAME: Jason Blatter jason.blatter@3dfire.us PHONE NO: (208) 881-5439 SYSTEM DESIGNED BY: Jason Blatter jason.blatter@3dfire.us PHONE NO: (208) 881-5439 TYPE OF SYSTEM: NFPA 13/Wet HEAD COUNT: 64 TOTAL SYSTEMS: 1 OCCUPANCY CLASSIFICATION: Light Hazard CONSTRUCTION TYPE: Steel and Concrete AREA SQUARE FOOTAGE: 10,000 SCOPE OF WORK: Head Relocation of existing branch lines and mains PLAN REVIEW COMMENTS: Approved with the following comment 1. Working Plans per NFPA 13, 27.1.3(20) Show max length and number of bends for flexible drops on plans. Approval of shop drawings is not intended to imply waiver or modification of any requirements of the Idaho State Statutes or Rules, International Fire Code, NFPA Standards or any other applicable criteria. It is acknowledged that backflow preventer is installed per the demand of the local water purveyor. The State Fire Marshal’s Office and its personnel does not take any responsibility for the back flow device.