HomeMy WebLinkAboutLOAD SHORT FORM - 22-00188 - 641 S 2470 W - New SFRCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Mar-24 11:19:13 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF5B14 Highland.rup Calc = MJ8 Front Door faces: SE SF5B14Job:Load Short Form Date:Entire House Vince ByramBy: Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com Project Information Cody PuzeyFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Information InfiltrationClgHtg SimplifiedMethod89-6Outside db (°F) Semi-tightConstruction quality7570Inside db (°F) 0Fireplaces1476Design TD (°F) H-Daily range 5050Inside humidity (%) -3162Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Goodman Mfg.Make Goodman Mfg. Trade GOODMAN Trade GOODMAN; JANITROL; AMANA DISTI... Model GMSS960603BN Cond GSX130301B AHRI ref 7365096 Coil ARUF30B14A AHRI ref 5383471 Efficiency 96.1 AFUE Efficiency 11.0 EER, 13 SEER Heating input Btuh60000 Sensible cooling Btuh27000 Heating output Btuh58000 Latent cooling Btuh0 Temperature rise °F70 Total cooling Btuh27000 Actual air flow cfm900 Actual air flow cfm900 Air flow factor cfm/Btuh0.030 Air flow factor cfm/Btuh0.070 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Room1 428 3229 2125 98 150 Room2 81 546 103 17 7 Room3 189 2351 1000 72 70 Room4 231 2826 1000 86 70 Room5 42 596 74 18 5 Room6 147 2871 1042 87 73 Room7 173 3192 1081 97 76 Room9 33 1097 69 33 5 Room10 797 12858 6281 391 442 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Mar-24 11:19:13 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 2 S:\High Country\Wrightsoft\SF5B14 Highland.rup Calc = MJ8 Front Door faces: SE Entire House d 2121 29566 12775 900 900 Other equip loads 12166 988 Equip. @ 0.94 RSM 12937 Latent cooling 0 TOTALS 2121 41732 12937 900 900 2022-Mar-24 11:19:13 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF5B14 Highland.rup Calc = MJ8 Front Door faces: SE SF5B14Job:Building Analysis Date:Entire House Vince ByramBy: Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com Project Information Cody PuzeyFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) SimplifiedMethod)H(34-Da ily ra nge (°F) Semi-tightConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing OtherCeilings Floors Infiltration Ventilation Humidification % of loadBtuhBtuh/ft²Component 26.6110924.9Walls 14.2591324.3Glazing 1.147911.4Doors 4.719721.5Ceilings 12.451934.04.0Floors 11.849171.9Infiltration 00Ducts 00Piping 16.36803Humidification 12.95364Ventilation0Adjustments 100.041732Total Cooling Walls Glazing Other Ceilings Infiltration Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 7.710650.5Walls 57.6793132.6Glazing 0.81172.8Doors 7.910900.8Ceilings 000Floors 3.34530.2Infiltration 00Ducts 7.2988Ventilation 15.42120Internal gains 00Blower 0Adjustments 100.013763Total Latent Cooling Load = 0 Btuh Overall U-va lue = 0.0 63 Btuh/ft²-°F Data entries checked. 2022-Mar-24 11:19:13 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF5B14 Highland.rup Calc = MJ8 Front Door faces: SE SF5B14Job:Component Constructions Date:Entire House Vince ByramBy: Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com Project Information Cody PuzeyFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) SimplifiedMethod)H(34-Da ily ra nge (°F) Semi-tightConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 1180.4712284.9421.00.065249ne 1810.4718824.9421.00.065381se 1340.4713934.9421.00.065282sw 1640.4717124.9421.00.065347nw 5970.4762154.9421.00.0651258all Frm wall, vnl ext, 3/8" wood shth, r-22 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 1220.4712754.9422.00.065258ne 1200.4712454.9422.00.065252se 1070.4711124.9422.00.065225sw 1200.4712454.9422.00.065252nw 4680.4748774.9422.00.065987all Partitions (none) Windows 61C: 61C; NFRC rated (SHGC=0.32); 6.67 ft head ht 0.32078ne 187323.9190524.30 53823.954724.300.32023ne 136830.4109424.300.32045sw 295730.4236624.300.32097sw 673627.7591324.300.320243all Doors metal: Door, mtl pur core type 1172.7847911.410.50.15042ne Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 10900.8419721.5250.00.0201297 Floors 22B-10cpm: Bg floor, heavy dry or light damp soil, on grade depth, r-10 edge ins, carpet flr fnsh 00344427.010.00.355128 00174927.010.00.35565 00519327.010.00.355192all Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Mar-24 11:19:13 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF5B14 Highland.rup Calc = MJ8 Front Door faces: SE SF5B14Job:Project Summary Date:Entire House Vince ByramBy: Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com Project Information Cody PuzeyFor:3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Notes: Design Information Idaho Falls, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-6 Outside db °F89Inside db °F70 Inside db °F75 Design TD °F76 Design TD °F14Daily range H Relative humidity %50Moisture difference gr/lb-31 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh29566 Structure Btuh12775 Ducts Btuh0 Ducts Btuh0Central vent (76 cfm)5364 Btuh Central vent (76 cfm)Btuh988 Outside air Outside airHumidificationBtuh6803Blower Btuh0 Piping Btuh0Equipment load Btuh41732 Use manufacturer's data n Rate/swing multiplier 0.94InfiltrationEquipment sensible load Btuh12937 Method Latent Cooling Equipment Load SizingSimplified Construction quality Semi-tight0Fireplaces Structure Btuh171 Ducts Btuh0Central vent (76 cfm)Btuh-1373 CoolingHeating Outside air21212121Area (ft²)Equipment latent load Btuh0 1909119091Volume (ft³)Air changes/hour 0.110.22 Equipment Total Load (Sen+Lat)Btuh12937 Equiv. AVF (cfm)3570 Req. total capacity at 1.00 SHR ton1.1 Heating Equipment Summary Cooling Equipment Summary Make Goodman Mfg.Make Goodman Mfg.Trade GOODMAN Trade GOODMAN; JANITROL; AMANA DISTI... Model GMSS960603BN Cond GSX130301BAHRI ref 7365096 Coil ARUF30B14A AHRI ref 5383471Efficiency96.1 AFUE Efficiency 11.0 EER, 13 SEER Heating input Btuh60000 Sensible cooling Btuh27000Heating output Btuh58000 Latent cooling Btuh0 Temperature rise °F70 Total cooling Btuh27000Actual air flow cfm900 Actual air flow cfm900 Air flow factor cfm/Btuh0.030 Air flow factor cfm/Btuh0.070Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 1.00 2022-Mar-24 11:19:13 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF5B14 Highland.rup Calc = MJ8 Front Door faces: SE SF5B14Job:AED Assessment Date:Entire House Vince ByramBy: Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com Project Information Cody PuzeyFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) )H(34-Da ily ra nge (°F) 60-We t bu lb (°F) 7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limitGlazing load (Btuh)Hour of Day 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 49.2%. House does not have adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 1195 Btuh (PFG - 1.3*AFG) Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Mar-24 11:19:13Right-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1S:\High Country\Wrightsoft\SF5B14 Highland.rup Calc = MJ8 Front Door faces: SE SF5B14Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Entire House Room1 2 Exposed wall 281.2 ft 29.3 ft 3 Room height 9.0 dft 9.0 heat/coolft 4 Room dimensions ft428.1x1.0 5 Room area 2121.2 f t²428.1 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.944.94 0.470.47 327 249 1228 118 0 0 0 0 .GG 61C61C 0.3200.320 nene 24.3224.32 23.9123.91 78 0 1905 1873 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.944.94 0.470.47 323 258 1275 122 0 0 0 0 .GG 61C61C 0.3200.320 nene 24.3224.32 23.9123.91 23 0 547 538 0 0 0 0 1 1 DD metalmetal 0.1500.150 nene 11.4011.40 2.782.78 42 42 479 117 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.944.94 0.470.47 381 381 1882 181 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.944.94 0.470.47 252 252 1245 120 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.944.94 0.470.47 327 282 1393 134 122 93 460 44 GG 61C61C 0.3200.320 swsw 24.3224.32 30.3930.39 45 0 1094 1368 28 0 689 861 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.944.94 0.470.47 323 225 1112 107 0 0 0 0 GG 61C61C 0.3200.320 swsw 24.3224.32 30.3930.39 97 0 2366 2957 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.944.94 0.470.47 347 347 1712 164 143 143 704 68 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.944.94 0.470.47 252 252 1245 120 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 1297 1297 1972 1090 428 428 651 360 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 830 128 3444 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 467 65 1749 0 115 8 212 0 6 c) AED excursion 1195 285 Envelope loss/gain 24649 10202 2716 1617 12 a)Infiltration 4917 453 513 47 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 4 920 2 460 Appliances/other 1200 0 Subtotal (lines 6 to 13)29566 12775 3229 2125 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 29566 12775 3229 2125 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 29566 12775 3229 2125 Air required (cfm)Air required (cfm)900 900 98 150 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Mar-24 11:19:13Right-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 2S:\High Country\Wrightsoft\SF5B14 Highland.rup Calc = MJ8 Front Door faces: SE SF5B14Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Room2 Room3 2 Exposed wall 6.8 ft 27.8 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft11.8x6.8 ft11.8x16.0 5 Room area 80.9 f t²189.3 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.944.94 0.470.47 0 0 0 0 0 0 0 0 .GG 61C61C 0.3200.320 nene 24.3224.32 23.9123.91 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.944.94 0.470.47 0 0 0 0 0 0 0 0 .GG 61C61C 0.3200.320 nene 24.3224.32 23.9123.91 0 0 0 0 0 0 0 0 1 1 DD metalmetal 0.1500.150 nene 11.4011.40 2.782.78 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.944.94 0.470.47 0 0 0 0 107 107 526 51 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.944.94 0.470.47 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.944.94 0.470.47 62 62 304 29 144 127 629 60 GG 61C61C 0.3200.320 swsw 24.3224.32 30.3930.39 0 0 0 0 17 0 405 507 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3200.320 swsw 24.3224.32 30.3930.39 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.944.94 0.470.47 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.944.94 0.470.47 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 81 81 123 68 189 189 288 159 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 4 1 16 0 6 c) AED excursion -5 179 Envelope loss/gain 427 92 1864 956 12 a)Infiltration 119 11 487 45 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)546 103 2351 1000 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 546 103 2351 1000 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 546 103 2351 1000 Air required (cfm)Air required (cfm)17 7 72 70 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Mar-24 11:19:13Right-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 3S:\High Country\Wrightsoft\SF5B14 Highland.rup Calc = MJ8 Front Door faces: SE SF5B14Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Room4 Room5 2 Exposed wall 30.5 ft 7.2 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft16.3x14.2 ft7.2x5.8 5 Room area 231.4 f t²41.8 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.944.94 0.470.47 128 99 490 47 0 0 0 0 .GG 61C61C 0.3200.320 nene 24.3224.32 23.9123.91 28 0 689 677 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.944.94 0.470.47 0 0 0 0 0 0 0 0 .GG 61C61C 0.3200.320 nene 24.3224.32 23.9123.91 0 0 0 0 0 0 0 0 1 1 DD metalmetal 0.1500.150 nene 11.4011.40 2.782.78 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.944.94 0.470.47 147 147 726 70 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.944.94 0.470.47 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3200.320 swsw 24.3224.32 30.3930.39 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3200.320 swsw 24.3224.32 30.3930.39 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.944.94 0.470.47 0 0 0 0 65 65 319 31 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.944.94 0.470.47 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 231 231 352 194 42 42 64 35 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 10 1 36 0 19 3 89 0 6 c) AED excursion -38 -3 Envelope loss/gain 2293 951 471 62 12 a)Infiltration 533 49 125 12 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2826 1000 596 74 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 2826 1000 596 74 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2826 1000 596 74 Air required (cfm)Air required (cfm)86 70 18 5 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Mar-24 11:19:13Right-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 4S:\High Country\Wrightsoft\SF5B14 Highland.rup Calc = MJ8 Front Door faces: SE SF5B14Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Room6 Room7 2 Exposed wall 24.3 ft 27.5 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft13.3x11.0 ft15.5x11.2 5 Room area 146.7 f t²173.1 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.944.94 0.470.47 99 74 366 35 101 76 373 36 .GG 61C61C 0.3200.320 nene 24.3224.32 23.9123.91 25 0 608 598 25 0 608 598 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.944.94 0.470.47 0 0 0 0 0 0 0 0 .GG 61C61C 0.3200.320 nene 24.3224.32 23.9123.91 0 0 0 0 0 0 0 0 1 1 DD metalmetal 0.1500.150 nene 11.4011.40 2.782.78 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.944.94 0.470.47 0 0 0 0 128 128 630 60 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.944.94 0.470.47 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3200.320 swsw 24.3224.32 30.3930.39 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3200.320 swsw 24.3224.32 30.3930.39 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.944.94 0.470.47 120 120 593 57 20 20 96 9 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.944.94 0.470.47 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 147 147 223 123 173 173 263 145 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 147 24 657 0 173 27 741 0 6 c) AED excursion -41 -42 Envelope loss/gain 2446 772 2711 806 12 a)Infiltration 426 39 481 44 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 1 230 1 230 Appliances/other 0 0 Subtotal (lines 6 to 13)2871 1042 3192 1081 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 2871 1042 3192 1081 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2871 1042 3192 1081 Air required (cfm)Air required (cfm)87 73 97 76 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Mar-24 11:19:13Right-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 5S:\High Country\Wrightsoft\SF5B14 Highland.rup Calc = MJ8 Front Door faces: SE SF5B14Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Room9 Room10 2 Exposed wall 12.3 ft 115.3 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft8.5x3.8 ft797.4x1.0 5 Room area 32.6 f t²797.4 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.944.94 0.470.47 0 0 0 0 0 0 0 0 .GG 61C61C 0.3200.320 nene 24.3224.32 23.9123.91 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.944.94 0.470.47 35 35 170 16 288 224 1104 106 .GG 61C61C 0.3200.320 nene 24.3224.32 23.9123.91 0 0 0 0 23 0 547 538 1 1 DD metalmetal 0.1500.150 nene 11.4011.40 2.782.78 0 0 0 0 42 42 479 117 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.944.94 0.470.47 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.944.94 0.470.47 77 77 378 36 176 176 867 83 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3200.320 swsw 24.3224.32 30.3930.39 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.944.94 0.470.47 0 0 0 0 323 225 1112 107 GG 61C61C 0.3200.320 swsw 24.3224.32 30.3930.39 0 0 0 0 97 0 2366 2957 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.944.94 0.470.47 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.944.94 0.470.47 0 0 0 0 252 252 1245 120 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 0 0 0 0 6 6 9 5 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 33 12 333 0 797 115 3112 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -3 863 Envelope loss/gain 881 49 10842 4895 12 a)Infiltration 216 20 2017 186 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 1200 Subtotal (lines 6 to 13)1097 69 12858 6281 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1097 69 12858 6281 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1097 69 12858 6281 Air required (cfm)Air required (cfm)33 5 391 442 Job #: SF5B14 Performed by Vince Byram for: Cody Puzey 3758 Yellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 Modern Plumbing Heating and Electric 3939 E 240 N Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Vince@modernphe.com Scale: 1 : 71 Page 1 Ri g ht-Sui t e® Un i v ersa l 2 019 19.0.13 RSU20477 2022-Mar-24 11:19:58 ...\Wrightsoft\SF5B14 Highland.rup N main Room9 Room10 88 cfm 359 cfm 88 cfm 33 cfm 88 cfm 88 cfm 88 cfm Job #: SF5B14 Performed by Vince Byram for: Cody Puzey 3758 Yellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 Modern Plumbing Heating and Electric 3939 E 240 N Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Vince@modernphe.com Scale: 1 : 71 Page 2 Ri g ht-Sui t e® Un i v ersa l 2 019 19.0.13 RSU20477 2022-Mar-24 11:19:58 ...\Wrightsoft\SF5B14 Highland.rup N 2nd story Room1 Room2Room3 Room4 Room5 Room6 Room7 Room8 6" mechanical fresh damper 80 cfm 75 cfm 87 cfm 75 cfm 17 cfm72 cfm 86 cfm 18 cfm 97 cfm 171 cfm 185 cfm 158 cfm 14x3.25 6 " 6 " 12 x 8 2-14x3.25 12 x 8 12 x 812 x 8 6 " 6 " 6 "6 " 6 " 6 " 6 " 6 " 16 x 8 6 " 14x3.25 6 " 16 x 8 14x3.25 6 " 14x3.25 6 " 2022-Mar-24 11:19:14 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF5B14 Highland.rup Calc = MJ8 Front Door faces: SE SF5B14Job:Duct System Summary Date:Entire House Vince ByramBy: Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com Project Information Cody PuzeyFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0in H2O0 Available static pressure in H2O0.70in H2O0.70 Supply / return available pressure 0.326 / 0.374 in H2O in H2O0.326 / 0.374 Lowest friction rate in/100ft0.146in/100ft0.146 Actual air flow cfm900cfm900 Total effective length (TEL)ft481 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st1165.026.5ShMt0x06.00.17075491062cRoom1 st1A170.026.8ShMt0x06.00.16575491062cRoom1-A st1130.036.0ShMt0x06.00.19688781256cRoom10 st1A150.049.2ShMt0x06.00.16388781256cRoom10-A st1175.024.5ShMt0x06.00.16388781256cRoom10-B st1A160.025.2ShMt0x06.00.17688781256cRoom10-C st1160.012.8ShMt0x06.00.18888781256cRoom10-D st1150.027.3ShMt0x06.00.184717546hRoom2 st1B170.047.8ShMt0x06.00.14970722351hRoom3 st1C190.033.7ShMt0x06.00.14670862826hRoom4 st1180.08.3ShMt0x06.00.173518596hRoom5 st1175.015.3ShMt0x06.00.17173872871hRoom6-A st1140.028.3ShMt0x06.00.19376973192hRoom7 st1B180.031.7ShMt0x06.00.1545331097hRoom9 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st1A Peak AVF 397 398 0.146 596 9.0 12x8 ShtMetl st1 st1 Peak AVF 900 900 0.146 1013 12.3 16x8 ShtMetl st1B Peak AVF 191 146 0.146 286 6.9 12x8 ShtMetl st1A st1C Peak AVF 86 70 0.146 129 5.1 12x8 ShtMetl st1B 2022-Mar-24 11:19:14 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 2 S:\High Country\Wrightsoft\SF5B14 Highland.rup Calc = MJ8 Front Door faces: SE Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb3 0x 1580 141 137.5 0.272 499 5.6 3.25x14 10x9 SJSp rt1 rb5 0x 3470 359 257.3 0.146 568 8.7 2-3.25x14 2-10x18 SJSp rt1A rb1 0x 1440 171 125.7 0.298 540 5.7 3.25x14 10x9 SJSp rt1 rb2 0x 1850 150 104.2 0.360 584 5.7 3.25x14 10x9 SJSp rt1 rb4 0x 670 80 91.5 0.409 253 4.0 3.25x14 10x9 SJSp rt1 Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 900 900 0.146 1013 12.3 16x8 ShtMetl rt1A Peak AVF 347 359 0.146 538 8.7 12x8 ShtMetl rt1