Loading...
HomeMy WebLinkAboutLOAD SHORT FORM - 22-00151 - 1011 Pine Brook Ln - New SFRCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-15 08:54:53 Right-Suite® Universal 2021 21.0.10 RSU28163 Page 1 ...s\Neals Heating\Merrill House\Merrill House.rup Calc = MJ8 Front Door faces: SW Merrill HomeJob:Load Short Form 01/14/2022Date:Entire House Gene MillerBy: Merrill HomePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Neals HeatingFor: Design Information InfiltrationClgHtg SimplifiedMethod90-7Outside db (°F) Semi-tightConstruction quality7570Inside db (°F) 0Fireplaces1577Design TD (°F) H-Daily range 5030Inside humidity (%) -2935Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make American Standard Make American Standard Trade AMERICAN STANDARD Trade AMERICAN STANDARD Model S9V2D120U5VS***Cond 4A7A4042L1 AHRI ref 10591649 Coil 4TXCB006DS3 AHRI ref 8736604 Efficiency 97 AFUE Efficiency 12.2 EER, 14 SEER Heating input Btuh120000 Sensible cooling Btuh38479 Heating output Btuh91530 Latent cooling Btuh0 Temperature rise °F57 Total cooling Btuh38479 Actual air flow cfm1746 Actual air flow cfm1870 Air flow factor cfm/Btuh0.028 Air flow factor cfm/Btuh0.078 Static pressure in H2O0.80 Static pressure in H2O0.80 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Crawl Space 3080 26413 1554 739 121 Rec Rm 375 6011 3554 168 277 Laundry 91 1507 744 42 58 Bedroom 3 198 3139 1872 88 146 Bath 4 51 785 590 22 46 Mud Rm 126 1755 326 49 25 Bedroom 2 207 2780 1845 78 144 Bath 3 57 1012 615 28 48 Office 165 2049 1751 57 137 Master 236 2718 1615 76 126 M Bath 168 2434 812 68 63 Room12 111 619 128 17 10 M TR 27 304 45 9 3 Kit/Din/Great Rm 1270 10908 8535 305 665 No Condenser will be installed at this time Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-15 08:54:53 Right-Suite® Universal 2021 21.0.10 RSU28163 Page 2 ...s\Neals Heating\Merrill House\Merrill House.rup Calc = MJ8 Front Door faces: SW Entire House 6159 62433 23985 1746 1870 Other equip loads 12732 2424 Equip. @ 0.95 RSM 24982 Latent cooling 0 TOTALS 6159 75165 24982 1746 1870 2022-Jan-15 08:54:53 Right-Suite® Universal 2021 21.0.10 RSU28163 Page 1 ...s\Neals Heating\Merrill House\Merrill House.rup Calc = MJ8 Front Door faces: SW Merrill HomeJob:Building Analysis 01/14/2022Date:Entire House Gene MillerBy: Merrill HomePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Neals HeatingFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5030Relative humidity (%)°N44Latitude:Outdoor:-29.435.3Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Doors Ceilings Floors Infiltration Ventilation % of loadBtuhBtuh/ft²Component 40.5304466.6Walls 10.4784323.0Glazing 5.1383929.9Doors 6.347241.5Ceilings 7.959051.91.9Floors 12.996771.9Infiltration 00Ducts 00Piping 00Humidification 16.912732Ventilation0Adjustments 100.075165Total Cooling Walls Glazing Doors Ceilings Infiltration Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 9.525100.5Walls 52.21378140.4Glazing 3.59317.3Doors 9.825930.8Ceilings 000Floors 3.79690.2Infiltration 00Ducts 9.22424Ventilation 12.13200Internal gains 00Blower 0Adjustments 100.026409Total Latent Cooling Load = 0 Btuh Overall U-value = 0.061 Btuh/ft²-°F Data entries checked. 2022-Jan-15 08:54:53 Right-Suite® Universal 2021 21.0.10 RSU28163 Page 1 ...s\Neals Heating\Merrill House\Merrill House.rup Calc = MJ8 Front Door faces: SW Merrill HomeJob:Component Constructions 01/14/2022Date:Entire House Gene MillerBy: Merrill HomePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Neals HeatingFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-29.435.3Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 14A-6: Misc. wall, 6" thk 2930.6441649.1300.119456ne 250.643559.1300.11939e 2600.6436979.1300.119405se 3110.6444159.1300.119484sw 2630.6437409.1300.119410nw 11530.64163719.1300.1191794all Frm wall, vnl ext, 3/8" wood shth, r-22 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 3290.4834064.9922.00.065683ne 130.481404.9922.00.06528e 3140.4832564.9922.00.065653se 3340.4834624.9922.00.065694sw 3680.4838114.9922.00.065765nw 13580.48140744.9922.00.0652823all Partitions 342135.6220923.000.30096ne 324742.7174923.000.30076se 661542.7356323.000.300155sw 49935.632223.000.30014nw 1378140.4784323.000.300341all 3057.25125629.900.39042ne 3057.25125629.900.39042e 1577.2564629.900.39022sw 1657.2568129.900.39023nw 9317.25383929.900.390128all (none) Windows 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/4" gap, 1/8" thk: 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.35); foreground = new concrete (0.32); 6.67 ft head ht Doors 11D0: Door, wd sc type Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 25930.8447241.5350.00.0203080 2022-Jan-15 08:54:53 Rig ht-Su ite® U niv er sal 20 21 21 .0.10 RSU2 8163 Page 2 ...s\Neals Heating\Merrill House\Merrill House.rup Calc = MJ8 Front Door faces: SW Floors Bg floor, light dry soil, 5' depth, Dirt Floor w/plastic covering 1.9200.0253080 005905 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-15 08:54:53 Right-Suite® Universal 2021 21.0.10 RSU28163 Page 1 ...s\Neals Heating\Merrill House\Merrill House.rup Calc = MJ8 Front Door faces: SW Merrill HomeJob:Project Summary 01/14/2022Date:Entire House Gene MillerBy: Merrill HomePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Neals HeatingFor: Oversized equipment is at the Homeowners request.Notes: Design Information Idaho Falls Rgnl, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-7 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F77 Design TD °F15Daily range H Relative humidity %50Moisture difference gr/lb-29 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh62433 Structure Btuh23985 Ducts Btuh0 Ducts Btuh0Central vent (180 cfm)12732 Btuh Central vent (180 cfm)Btuh2424 Outside air Outside airHumidificationBtuh0Blower Btuh0 Piping Btuh0Equipment load Btuh75165 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh24982 Method Latent Cooling Equipment Load SizingSimplified Construction quality Semi-tight0Fireplaces Structure Btuh-1205 Ducts Btuh0Central vent (180 cfm)Btuh-3013 CoolingHeating Outside air61596159Area (ft²)Equipment latent load Btuh0 4311543115Volume (ft³)Air changes/hour 0.100.19 Equipment Total Load (Sen+Lat)Btuh24982 Equiv. AVF (cfm)72137 Req. total capacity at 1.00 SHR ton2.1 Heating Equipment Summary Cooling Equipment Summary Make American Standard Make American StandardTradeAMERICAN STANDARD Trade AMERICAN STANDARD Model S9V2D120U5VS***Cond 4A7A4042L1AHRI ref 10591649 Coil 4TXCB006DS3 AHRI ref 8736604Efficiency97 AFUE Efficiency 12.2 EER, 14 SEER Heating input Btuh120000 Sensible cooling Btuh38479Heating output Btuh91530 Latent cooling Btuh0 Temperature rise °F57 Total cooling Btuh38479Actual air flow cfm1746 Actual air flow cfm1870 Air flow factor cfm/Btuh0.028 Air flow factor cfm/Btuh0.078Static pressure in H2O0.80 Static pressure in H2O0.80 Space thermostat Load sensible heat ratio 1.00 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-15 08:54:53Right-Su ite® U niv er sal 20 21 21 .0.10 RSU2 8163 Page 1...s\Neals Heating\Merrill House\Merrill House.rup Calc = MJ8 Front Door faces: SW Merrill HomeJob:Right-J® W or ksheet 01/14/2022Date:Entire House Gene MillerBy:Merrill HomePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Entire House Crawl Space 2 Exposed wall 726.5 ft 363.3 ft 3 Room height 7.0 ft 5.0 heat/coolft 4 Room dimensions ft3079.6x1.0 5 Room area 6159.3 f t²3079.6 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 14A-614A-6 0.1190.119 nene 9.139.13 0.640.64 456 456 4164 293 456 456 4164 293 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.994.99 0.480.48 821 683 3406 329 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nene 23.0123.01 35.6335.63 96 0 2209 3421 0 0 0 0 .DD 11D011D0 0.3900.390 nene 29.9129.91 7.257.25 42 42 1256 305 0 0 0 0 1 1 WW 14A-614A-6 0.1190.119 ee 9.139.13 0.640.64 39 39 355 25 39 39 355 25 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.994.99 0.480.48 70 28 140 13 0 0 0 0 DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 42 42 1256 305 0 0 0 0 WW 14A-614A-6 0.1190.119 sese 9.139.13 0.640.64 405 405 3697 260 405 405 3697 260 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.994.99 0.480.48 729 653 3256 314 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 sese 23.0123.01 42.7242.72 76 0 1749 3247 0 0 0 0 WW 14A-614A-6 0.1190.119 swsw 9.139.13 0.640.64 484 484 4415 311 484 484 4415 311 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.994.99 0.480.48 871 694 3462 334 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 swsw 23.0123.01 42.7242.72 155 0 3563 6615 0 0 0 0 DD 11D011D0 0.3900.390 swsw 29.9129.91 7.257.25 22 22 646 157 0 0 0 0 WW 14A-614A-6 0.1190.119 nwnw 9.139.13 0.640.64 433 410 3740 263 433 410 3740 263 DD 11D011D0 0.3900.390 nwnw 29.9129.91 7.257.25 23 23 681 165 23 23 681 165 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.994.99 0.480.48 779 765 3811 368 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nwnw 23.0123.01 35.6335.63 14 0 322 499 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 3080 3080 4724 2593 0 0 0 0 FF Bg floor, light dry 0.025Bg floor, light dry 0.025 --1.921.92 0.000.00 3080 3080 5905 0 3080 3080 5905 0 6 c) AED excursion 0 -110 Envelope loss/gain 52756 19815 22957 1208 12 a)Infiltration 9677 969 3456 346 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 3200 0 Subtotal (lines 6 to 13)62433 23985 26413 1554 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 62433 23985 26413 1554 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 62433 23985 26413 1554 Air required (cfm)Air required (cfm)1746 1870 739 121 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-15 08:54:53Right-Su ite® U niv er sal 20 21 21 .0.10 RSU2 8163 Page 2...s\Neals Heating\Merrill House\Merrill House.rup Calc = MJ8 Front Door faces: SW Merrill HomeJob:Right-J® W or ksheet 01/14/2022Date:Entire House Gene MillerBy:Merrill HomePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Rec Rm Laundry 2 Exposed wall 66.8 ft 18.0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft15.0x25.0 ft90.6x1.0 5 Room area 375.0 f t²90.6 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 14A-614A-6 0.1190.119 nene 9.139.13 0.640.64 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.994.99 0.480.48 225 189 942 91 95 95 471 45 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nene 23.0123.01 35.6335.63 36 0 828 1283 0 0 0 0 .DD 11D011D0 0.3900.390 nene 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 1 1 WW 14A-614A-6 0.1190.119 ee 9.139.13 0.640.64 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 14A-614A-6 0.1190.119 sese 9.139.13 0.640.64 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.994.99 0.480.48 135 99 494 48 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 sese 23.0123.01 42.7242.72 36 0 828 1538 0 0 0 0 WW 14A-614A-6 0.1190.119 swsw 9.139.13 0.640.64 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.994.99 0.480.48 106 106 527 51 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 swsw 23.0123.01 42.7242.72 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 swsw 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 14A-614A-6 0.1190.119 nwnw 9.139.13 0.640.64 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 nwnw 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.994.99 0.480.48 135 135 673 65 68 54 267 26 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nwnw 23.0123.01 35.6335.63 0 0 0 0 14 0 322 499 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 375 375 575 316 91 91 139 76 FF Bg floor, light dry 0.025Bg floor, light dry 0.025 --1.921.92 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -252 67 Envelope loss/gain 4868 3139 1199 713 12 a)Infiltration 1143 115 308 31 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 300 0 Subtotal (lines 6 to 13)6011 3554 1507 744 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 6011 3554 1507 744 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 6011 3554 1507 744 Air required (cfm)Air required (cfm)168 277 42 58 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-15 08:54:53Right-Su ite® U niv er sal 20 21 21 .0.10 RSU2 8163 Page 3...s\Neals Heating\Merrill House\Merrill House.rup Calc = MJ8 Front Door faces: SW Merrill HomeJob:Right-J® W or ksheet 01/14/2022Date:Entire House Gene MillerBy:Merrill HomePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Bedroom 3 Bath 4 2 Exposed wall 37.0 ft 8.5 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft198.2x1.0 ft6.0x8.5 5 Room area 198.2 f t²51.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 14A-614A-6 0.1190.119 nene 9.139.13 0.640.64 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.994.99 0.480.48 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nene 23.0123.01 35.6335.63 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nene 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 1 1 WW 14A-614A-6 0.1190.119 ee 9.139.13 0.640.64 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 14A-614A-6 0.1190.119 sese 9.139.13 0.640.64 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.994.99 0.480.48 72 72 359 35 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 sese 23.0123.01 42.7242.72 0 0 0 0 0 0 0 0 WW 14A-614A-6 0.1190.119 swsw 9.139.13 0.640.64 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.994.99 0.480.48 135 105 523 51 77 67 332 32 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 swsw 23.0123.01 42.7242.72 30 0 690 1282 10 0 230 427 DD 11D011D0 0.3900.390 swsw 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 14A-614A-6 0.1190.119 nwnw 9.139.13 0.640.64 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 nwnw 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.994.99 0.480.48 126 126 628 61 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nwnw 23.0123.01 35.6335.63 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 198 198 304 167 51 51 78 43 FF Bg floor, light dry 0.025Bg floor, light dry 0.025 --1.921.92 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 214 74 Envelope loss/gain 2505 1808 640 576 12 a)Infiltration 634 63 146 15 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)3139 1872 785 590 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 3139 1872 785 590 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 3139 1872 785 590 Air required (cfm)Air required (cfm)88 146 22 46 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-15 08:54:53Right-Su ite® U niv er sal 20 21 21 .0.10 RSU2 8163 Page 4...s\Neals Heating\Merrill House\Merrill House.rup Calc = MJ8 Front Door faces: SW Merrill HomeJob:Right-J® W or ksheet 01/14/2022Date:Entire House Gene MillerBy:Merrill HomePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Mud Rm Bedroom 2 2 Exposed wall 16.8 ft 31.0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft7.5x16.8 ft207.0x1.0 5 Room area 125.6 f t²207.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 14A-614A-6 0.1190.119 nene 9.139.13 0.640.64 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.994.99 0.480.48 151 130 647 62 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nene 23.0123.01 35.6335.63 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nene 29.9129.91 7.257.25 21 21 628 152 0 0 0 0 1 1 WW 14A-614A-6 0.1190.119 ee 9.139.13 0.640.64 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 14A-614A-6 0.1190.119 sese 9.139.13 0.640.64 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.994.99 0.480.48 0 0 0 0 63 63 314 30 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 sese 23.0123.01 42.7242.72 0 0 0 0 0 0 0 0 WW 14A-614A-6 0.1190.119 swsw 9.139.13 0.640.64 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.994.99 0.480.48 0 0 0 0 153 123 613 59 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 swsw 23.0123.01 42.7242.72 0 0 0 0 30 0 690 1282 DD 11D011D0 0.3900.390 swsw 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 14A-614A-6 0.1190.119 nwnw 9.139.13 0.640.64 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 nwnw 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.994.99 0.480.48 0 0 0 0 63 63 314 30 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nwnw 23.0123.01 35.6335.63 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 126 126 193 106 207 207 318 174 FF Bg floor, light dry 0.025Bg floor, light dry 0.025 --1.921.92 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -23 216 Envelope loss/gain 1468 297 2249 1792 12 a)Infiltration 287 29 531 53 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1755 326 2780 1845 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1755 326 2780 1845 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1755 326 2780 1845 Air required (cfm)Air required (cfm)49 25 78 144 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-15 08:54:53Right-Su ite® U niv er sal 20 21 21 .0.10 RSU2 8163 Page 5...s\Neals Heating\Merrill House\Merrill House.rup Calc = MJ8 Front Door faces: SW Merrill HomeJob:Right-J® W or ksheet 01/14/2022Date:Entire House Gene MillerBy:Merrill HomePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Bath 3 Office 2 Exposed wall 12.0 ft 20.3 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft6.0x9.5 ft164.9x1.0 5 Room area 57.0 f t²164.9 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 14A-614A-6 0.1190.119 nene 9.139.13 0.640.64 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.994.99 0.480.48 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nene 23.0123.01 35.6335.63 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nene 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 1 1 WW 14A-614A-6 0.1190.119 ee 9.139.13 0.640.64 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 14A-614A-6 0.1190.119 sese 9.139.13 0.640.64 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.994.99 0.480.48 23 23 112 11 23 23 112 11 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 sese 23.0123.01 42.7242.72 0 0 0 0 0 0 0 0 WW 14A-614A-6 0.1190.119 swsw 9.139.13 0.640.64 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.994.99 0.480.48 86 76 376 36 115 85 423 41 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 swsw 23.0123.01 42.7242.72 10 0 230 427 30 0 690 1282 DD 11D011D0 0.3900.390 swsw 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 14A-614A-6 0.1190.119 nwnw 9.139.13 0.640.64 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 nwnw 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.994.99 0.480.48 0 0 0 0 45 45 224 22 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nwnw 23.0123.01 35.6335.63 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 57 57 87 48 165 165 253 139 FF Bg floor, light dry 0.025Bg floor, light dry 0.025 --1.921.92 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 72 223 Envelope loss/gain 806 594 1702 1716 12 a)Infiltration 205 21 347 35 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1012 615 2049 1751 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1012 615 2049 1751 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1012 615 2049 1751 Air required (cfm)Air required (cfm)28 48 57 137 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-15 08:54:53Right-Su ite® U niv er sal 20 21 21 .0.10 RSU2 8163 Page 6...s\Neals Heating\Merrill House\Merrill House.rup Calc = MJ8 Front Door faces: SW Merrill HomeJob:Right-J® W or ksheet 01/14/2022Date:Entire House Gene MillerBy:Merrill HomePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Master M Bath 2 Exposed wall 30.8 ft 23.8 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft16.3x14.5 ft167.9x1.0 5 Room area 235.6 f t²167.9 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 14A-614A-6 0.1190.119 nene 9.139.13 0.640.64 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.994.99 0.480.48 0 0 0 0 77 56 277 27 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nene 23.0123.01 35.6335.63 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nene 29.9129.91 7.257.25 0 0 0 0 21 21 628 152 1 1 WW 14A-614A-6 0.1190.119 ee 9.139.13 0.640.64 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 14A-614A-6 0.1190.119 sese 9.139.13 0.640.64 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.994.99 0.480.48 146 146 729 70 137 127 634 61 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 sese 23.0123.01 42.7242.72 0 0 0 0 10 0 230 427 WW 14A-614A-6 0.1190.119 swsw 9.139.13 0.640.64 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.994.99 0.480.48 131 106 526 51 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 swsw 23.0123.01 42.7242.72 25 0 575 1068 0 0 0 0 DD 11D011D0 0.3900.390 swsw 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 14A-614A-6 0.1190.119 nwnw 9.139.13 0.640.64 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 nwnw 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nwnw 23.0123.01 35.6335.63 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 236 236 361 198 168 168 258 141 FF Bg floor, light dry 0.025Bg floor, light dry 0.025 --1.921.92 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 174 -37 Envelope loss/gain 2192 1562 2027 771 12 a)Infiltration 527 53 407 41 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2718 1615 2434 812 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 2718 1615 2434 812 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2718 1615 2434 812 Air required (cfm)Air required (cfm)76 126 68 63 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-15 08:54:53Right-Su ite® U niv er sal 20 21 21 .0.10 RSU2 8163 Page 7...s\Neals Heating\Merrill House\Merrill House.rup Calc = MJ8 Front Door faces: SW Merrill HomeJob:Right-J® W or ksheet 01/14/2022Date:Entire House Gene MillerBy:Merrill HomePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Room12 M TR 2 Exposed wall 7.3 ft 4.3 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft15.3x7.3 ft6.3x4.3 5 Room area 110.6 f t²26.6 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 14A-614A-6 0.1190.119 nene 9.139.13 0.640.64 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.994.99 0.480.48 65 65 325 31 38 38 191 18 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nene 23.0123.01 35.6335.63 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nene 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 1 1 WW 14A-614A-6 0.1190.119 ee 9.139.13 0.640.64 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 14A-614A-6 0.1190.119 sese 9.139.13 0.640.64 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 sese 23.0123.01 42.7242.72 0 0 0 0 0 0 0 0 WW 14A-614A-6 0.1190.119 swsw 9.139.13 0.640.64 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 swsw 23.0123.01 42.7242.72 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 swsw 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 14A-614A-6 0.1190.119 nwnw 9.139.13 0.640.64 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 nwnw 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nwnw 23.0123.01 35.6335.63 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 111 111 170 93 27 27 41 22 FF Bg floor, light dry 0.025Bg floor, light dry 0.025 --1.921.92 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -9 -3 Envelope loss/gain 495 115 231 38 12 a)Infiltration 124 12 73 7 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)619 128 304 45 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 619 128 304 45 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 619 128 304 45 Air required (cfm)Air required (cfm)17 10 9 3 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-15 08:54:53Right-Su ite® U niv er sal 20 21 21 .0.10 RSU2 8163 Page 8...s\Neals Heating\Merrill House\Merrill House.rup Calc = MJ8 Front Door faces: SW Merrill HomeJob:Right-J® W or ksheet 01/14/2022Date:Entire House Gene MillerBy:Merrill HomePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Kit/Din/Great Rm 2 Exposed wall 87.0 ft 3 Room height 9.0 heat/coolft 4 Room dimensions ft1269.8x1.0 5 Room area 1269.8 f t² Ty Construction U-value Or HTM Area (f t²)Load Area Load number (Bt uh/f t²-°F)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 14A-6 0.119 ne 9.13 0.64 0 0 0 0 .W Frm wall, vnl ext, 3 0.065 ne 4.99 0.48 171 111 553 53 .G 2 glazing, clr low-e 0.300 ne 23.01 35.63 60 0 1381 2138 .D 11D0 0.390 ne 29.91 7.25 0 0 0 0 1 1 W 14A-6 0.119 e 9.13 0.64 0 0 0 0 W Frm wall, vnl ext, 3 0.065 e 4.99 0.48 70 28 140 13 D 11D0 0.390 e 29.91 7.25 42 42 1256 305 W 14A-6 0.119 se 9.13 0.64 0 0 0 0 W Frm wall, vnl ext, 3 0.065 se 4.99 0.48 131 101 501 48 G 2 glazing, clr low-e 0.300 se 23.01 42.72 30 0 690 1282 W 14A-6 0.119 sw 9.13 0.64 0 0 0 0 W Frm wall, vnl ext, 3 0.065 sw 4.99 0.48 70 28 141 14 G 2 glazing, clr low-e 0.300 sw 23.01 42.72 20 0 456 847 D 11D0 0.390 sw 29.91 7.25 22 22 646 157 W 14A-6 0.119 nw 9.13 0.64 0 0 0 0 D 11D0 0.390 nw 29.91 7.25 0 0 0 0 W Frm wall, vnl ext, 3 0.065 nw 4.99 0.48 342 342 1705 165 G 2 glazing, clr low-e 0.300 nw 23.01 35.63 0 0 0 0 C 16B-50ad 0.020 -1.53 0.84 1270 1270 1948 1069 F Bg floor, light dry 0.025 -1.92 0.00 0 0 0 0 6 c) AED excursion -605 Envelope loss/gain 9417 5486 12 a)Infiltration 1490 149 b)Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 2900 Subtotal (lines 6 to 13)10908 8535 Less external load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 10908 8535 15 Duct loads -0%0%0 0 Total room load 10908 8535 Air required (cfm)305 665 Job #: Merrill Home Performed by Gene Miller for: Neals Heating Mechanical Compliance Solutions 4181 Aschli lane Idaho Falls, ID 83406 Phone: 208-881-3243 gene.mechcompliancesolutions@gmail.com Scale: 1 : 142 Page 1 Ri ght -S uite® Uni ve rsal 2021 21.0.10 RSU28163 2022-Jan-15 08:55:09 ...\Merrill House\Merrill House.rup N Crawl Space Crawl Space 185 cfm 185 cfm 185 cfm 6 " 6 "2-14x3.25 6 " 6 " 6 " 3-14x3.25 8 " 2-14x3.25 6 " 14x3.25 6 " 6 " 6 " 6 " 8 " 8 " 6 " 6 " 8 " 6 " 6 " 28 x 12 6 " 28 x 12 10 x 8 6 " 3-14x3.25 6 " 6 " 2-14x3.25 6 " 6 " 6 " 26 x 8 14x3.25 5-14x3.25 28 x 10 28 x 8 18 x 8 8 x 8 26 x 10 26 x 8 20 x 8 6 " 6 " 14 x 8 12 x 8 8 x 8 Fresh air will be supplied with a pipe and damper attached to the return 185 cfm Job #: Merrill Home Performed by Gene Miller for: Neals Heating Mechanical Compliance Solutions 4181 Aschli lane Idaho Falls, ID 83406 Phone: 208-881-3243 gene.mechcompliancesolutions@gmail.com Scale: 1 : 142 Page 2 Ri ght -S uite® Uni ve rsal 2021 21.0.10 RSU28163 2022-Jan-15 08:55:09 ...\Merrill House\Merrill House.rup N Main Rec Rm Laundry Bedroom 3 Bath 4 Mud Rm Bedroom 2 Bath 3 Office Master M BathRoom12 M TR Kit/Din/Great Rm 92 cfm 95 cfm 95 cfm 95 cfm Bath 2 95 cfm 49 cfm 137 cfm 68 cfm 9 cfm 17 cfm 331 cfm 203 cfm 168 cfm46 cfm 58 cfm 48 cfm 192 cfm 442 cfm 277 cfm 72 cfm 72 cfm73 cfm 73 cfm 95 cfm 92 cfm 95 cfm 95 cfm 137 cfm 63 cfm 63 cfm 92 cfm 739 cfm 2022-Jan-15 08:54:54 Rig ht-Su ite® U niv er sal 20 21 21 .0.10 RSU2 8163 Page 1 ...s\Neals Heating\Merrill House\Merrill House.rup Calc = MJ8 Front Door faces: SW Merrill HomeJob:Duct System Summary 01/14/2022Date:Entire House Gene MillerBy: Merrill HomePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Neals HeatingFor: CoolingHeating External static pressure in H2O0.80in H2O0.80 Pressure losses in H2O0.37in H2O0.37 Available static pressure in H2O0.43in H2O0.43 Supply / return available pressure 0.279 / 0.151 in H2O in H2O0.279 / 0.151 Lowest friction rate in/100ft0.043in/100ft0.043 Actual air flow cfm1870cfm1746 Total effective length (TEL)ft1005 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st1B190.031.8ShMt0x06.00.1264828615cBath 3 st2130.025.8ShMt0x06.00.1794622590cBath 4 st2130.023.3ShMt0x06.00.1827239922cBedroom 2 st1130.029.3ShMt0x06.00.1757239922cBedroom 2-A st2A160.050.5ShMt0x06.00.1337344936cBedroom 3 st2A180.044.3ShMt0x06.00.1247344936cBedroom 3-A st2A125.039.5ShMt0x08.00.170301856603hCrawl Space st1A150.026.0ShMt0x08.00.158301856603hCrawl Space-B st1E525.051.0ShMt8x88.50.048301856603hCrawl Space-C st1160.048.3ShMt0x08.00.134301856603hCrawl Space-D st1B180.029.3ShMt0x06.00.13395441219cKit/Din/Great Rm st1C200.039.5ShMt0x06.00.11695441219cKit/Din/Great Rm-A st1A170.030.5ShMt0x06.00.13995441219cKit/Din/Great Rm-B st1150.012.5ShMt0x06.00.17295441219cKit/Din/Great Rm-C st1C210.034.5ShMt0x06.00.11495441219cKit/Din/Great Rm-D st1A180.038.0ShMt0x06.00.12895441219cKit/Din/Great Rm-E st1B170.034.8ShMt0x06.00.13695441219cKit/Din/Great Rm-F st2A170.031.5ShMt0x06.00.1385842744cLaundry st1E520.058.5ShMt0x06.00.04863682434hM Bath st1D435.052.5ShMt0x06.00.05739304hM TR st1D370.061.0ShMt0x06.00.0656338807cMaster st1E585.066.8ShMt0x06.00.0436338807cMaster-A st2140.020.0ShMt0x06.00.17425491755hMud Rm st1C220.053.0ShMt0x08.00.102137571751cOffice st1140.050.5ShMt0x06.00.14692561185cRec Rm st1A160.053.8ShMt0x06.00.13092561185cRec Rm-A 95.046.8ShMt0x06.00.19792561185cRec Rm-B st1D305.049.5ShMt0x06.00.0791017619hRoom12 2022-Jan-15 08:54:54 Rig ht-Su ite® U niv er sal 20 21 21 .0.10 RSU2 8163 Page 2 ...s\Neals Heating\Merrill House\Merrill House.rup Calc = MJ8 Front Door faces: SW Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st1E Peak AVF 291 157 0.043 436 8.0 12x8 ShtMetl st1D st1D Peak AVF 355 233 0.043 456 11.1 14x8 ShtMetl st1C st1A Peak AVF 942 1110 0.043 615 17.0 26x10 ShtMetl st1 st1 Peak AVF 1265 1400 0.043 600 19.1 28x12 ShtMetl st1B Peak AVF 614 798 0.043 552 15.0 26x8 ShtMetl st1A st2A Peak AVF 315 234 0.124 708 8.6 8x8 ShtMetl st2 st2 Peak AVF 424 378 0.124 764 9.6 10x8 ShtMetl st1C Peak AVF 499 560 0.043 504 13.1 20x8 ShtMetl st1B Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb9 0x 7390 121 218.3 0.069 468 13.2 5-3.25x14 5-10x46 SJSp rt2 rb2 0x 1530 331 269.3 0.056 349 10.2 3-3.25x14 3-10x27 SJSp rt1C rb3 0x 1700 203 344.3 0.044 321 9.0 2-3.25x14 2-10x18 SJSp rt1C rb4 0x 870 168 353.0 0.043 266 8.4 2-3.25x14 2-10x18 SJSp rt2A rb5 0x 1060 192 115.0 0.131 607 7.0 3.25x14 10x9 SJSp rt1 rb6 0x 2660 442 144.8 0.104 466 10.1 3-3.25x14 3-10x27 SJSp rt1A rb7 0x 1680 277 116.3 0.130 438 8.1 2-3.25x14 2-10x18 SJSp rt1 rb8 0x 570 137 189.0 0.080 432 6.8 3.25x14 10x9 SJSp rt1B Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt2 Peak AVF 826 289 0.043 572 15.2 26x8 ShtMetl rt2A Peak AVF 87 168 0.043 378 8.4 8x8 ShtMetl rt2 rt1 Peak AVF 920 1581 0.044 677 19.1 28x12 ShtMetl rt1A Peak AVF 646 1112 0.044 572 17.0 28x10 ShtMetl rt1 rt1C Peak AVF 323 534 0.044 534 12.9 18x8 ShtMetl rt1B rt1B Peak AVF 380 670 0.044 431 17.0 28x8 ShtMetl rt1A