Loading...
HomeMy WebLinkAboutLOAD SHORT FORM - 22-00138 - 739 S 2470 W - New SFRCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Mar-07 15:34:42 Right-Suite® Universal 2019 19.0.13 RSU20477 Page 1 S:\High Country\Wrightsoft\SF4B14 magnolia.rup Calc = MJ8 Front Door faces: S SF4B14Job:Load Short Form Date:Entire House Vince ByramBy: fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com Project Information Cody Puzey, Karthcner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Information InfiltrationClgHtg SimplifiedMethod89-6Outside db (°F) Semi-tightConstruction quality7570Inside db (°F) 0Fireplaces1476Design TD (°F) H-Daily range 5050Inside humidity (%) -3162Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Lennox Make Lennox Trade LENNOX Trade LENNOX Model ML195UH045XP24B-*Cond 13ACXN018-230A** AHRI ref 4805337 Coil C35-18/24B*++TDR AHRI ref 201757243 Efficiency 95 AFUE Efficiency 10.7 EER, 13 SEER Heating input Btuh44000 Sensible cooling Btuh17500 Heating output Btuh41000 Latent cooling Btuh0 Temperature rise °F63 Total cooling Btuh17500 Actual air flow cfm700 Actual air flow cfm700 Air flow factor cfm/Btuh0.020 Air flow factor cfm/Btuh0.047 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Room1 253 3293 1619 65 76 Room3 109 1828 660 36 31 Room4 814 10126 5756 199 270 Room6 36 448 35 9 2 Room7 144 2197 710 43 33 Room8 78 762 60 15 3 Room9 146 2381 753 47 35 Room10 204 3910 871 77 41 Room11 544 4019 1179 79 55 Room12 53 81 42 2 2 Room14 138 1319 652 26 31 Room15 40 443 66 9 3 Room16 149 2322 1256 46 59 Room17 151 2335 1258 46 59 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Mar-07 15:34:42 Right-Suite® Universal 2019 19.0.13 RSU20477 Page 2 S:\High Country\Wrightsoft\SF4B14 magnolia.rup Calc = MJ8 Front Door faces: S Room5 51 226 13 4 1 Entire House d 2910 35691 14929 700 700 Other equip loads 7358 1355 Equip. @ 0.94 RSM 15308 Latent cooling 0 TOTALS 2910 43049 15308 700 700 2022-Mar-07 15:34:42 Right-Suite® Universal 2019 19.0.13 RSU20477 Page 1S:\High Country\Wrightsoft\SF4B14 magnolia.rup Calc = MJ8 Front Door faces: S SF4B14Job:Building Analysis Date:Entire House Vince ByramBy: fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com Project Information Cody Puzey, Karthcner HomesFor:3758 Yellowstones Hwy, Idaho Falls, Id 83401Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation:5050Relative humidity (%)°N44Latitude:Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F)SimplifiedMethod)H(34-Daily range (°F) Semi-tightConstruction quality60-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing DoorsCeilings Floors Infiltration Ventilation % of loadBtuhBtuh/ft²Component 31.5135674.9Walls 20.1863223.9Glazing 2.292622.0Doors 6.126311.5Ceilings 7.431891.81.8Floors 15.767452.1Infiltration 00Ducts00Piping00Humidification17.17358Ventilation0Adjustments100.043049Total Cooling Walls Glazing Other Ceilings InfiltrationVentilation % of loadBtuhBtuh/ft²Component 8.013030.5Walls 69.51132631.3Glazing 1.42255.4Doors 8.914540.8Ceilings 000Floors3.86210.2Infiltration 00Ducts8.31355Ventilation00Internal gains 00Blower0Adjustments100.016285Total Latent Cooling Load = 0 BtuhOverall U-value = 0.057 Btuh/ft²-°F Data entries checked. 2022-Mar-07 15:34:42Right-Suite® Universal 2019 19.0.13 RSU20477 Page 1S:\High Country\Wrightsoft\SF4B14 magnolia.rup Calc = MJ8 Front Door faces: S SF4B14Job:Component Constructions Date:Entire House Vince ByramBy: fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com Project Information Cody Puzey, Karthcner HomesFor:3758 Yellowstones Hwy, Idaho Falls, Id 83401Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F) SimplifiedMethod)H(34-Daily range (°F) Semi-tightConstruction quality60-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Frm wall, vnl ext, 3/8" wood shth, r-22 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 3360.4734984.9422.00.065708ne 3390.4735274.9422.00.065714se 2830.4729474.9422.00.065597sw 3450.4735964.9422.00.065728nw 13030.47135674.9422.00.0652746all Partitions (none) Windows 61C: 61C; 6.67 ft head ht 112023.6122725.800.34048ne 44829.938825.800.34015se 149329.9129225.800.34050sw 35423.638825.800.34015nw 341526.8329525.800.340128all 61C: 61C; NFRC rated (SHGC=0.33); 6.67 ft head ht 0.30035ne 84824.279822.80 158030.9116522.800.30051se 408230.9301022.800.300132sw 38824.236522.800.30016nw 689729.5533722.800.300234all Doors 11P0: Door, mtl pur core type 1135.3646322.010.50.29021ne 1135.3646322.010.50.29021nw 2255.3692622.010.50.29042all Ceilings16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 14540.8426311.5250.00.0201731 Floors21A-32c: Bg floor, heavy dry or light damp soil, 8' depth, carpet flr fnsh 022571.5200.0201485 0 2022-Mar-07 15:34:42Right-Suite® Universal 2019 19.0.13 RSU20477 Page 2S:\High Country\Wrightsoft\SF4B14 magnolia.rup Calc = MJ8 Front Door faces: S 22B-10cpm: Bg floor, heavy dry or light damp soil, on grade depth, r-10 edge ins, carpet flr fnsh 0093227.010.00.35535 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Mar-07 15:34:42Right-Suite® Universal 2019 19.0.13 RSU20477 Page 1S:\High Country\Wrightsoft\SF4B14 magnolia.rup Calc = MJ8 Front Door faces: S SF4B14Job:Project Summary Date:Entire House Vince ByramBy: fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com Project Information Cody Puzey, Karthcner HomesFor:3758 Yellowstones Hwy, Idaho Falls, Id 83401Phone: 208-529-2116 Notes: Design Information Idaho Falls, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-6 Outside db °F89Inside db °F70 Inside db °F75Design TD °F76 Design TD °F14Daily range HRelative humidity %50Moisture difference gr/lb-31 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh35691 Structure Btuh14929DuctsBtuh0DuctsBtuh0Central vent (105 cfm)7358 Btuh Central vent (105 cfm)Btuh1355Outside air Outside airHumidificationBtuh0Blower Btuh0PipingBtuh0Equipment load Btuh43049 Use manufacturer's data nRate/swing multiplier 0.94InfiltrationEquipment sensible load Btuh15308 Method Latent Cooling Equipment Load SizingSimplifiedConstruction quality Semi-tight0Fireplaces Structure Btuh-864Ducts Btuh0Central vent (105 cfm)Btuh-1884CoolingHeatingOutside air29102910Area (ft²)Equipment latent load Btuh02619226192Volume (ft³)Air changes/hour 0.110.22 Equipment Total Load (Sen+Lat)Btuh15308Equiv. AVF (cfm)4896 Req. total capacity at 1.00 SHR ton1.3 Heating Equipment Summary Cooling Equipment Summary Make Lennox Make LennoxTradeLENNOXTradeLENNOXModelML195UH045XP24B-*Cond 13ACXN018-230A**AHRI ref 4805337 Coil C35-18/24B*++TDRAHRI ref 201757243Efficiency95 AFUE Efficiency 10.7 EER, 13 SEERHeating input Btuh44000 Sensible cooling Btuh17500Heating output Btuh41000 Latent cooling Btuh0Temperature rise °F63 Total cooling Btuh17500Actual air flow cfm700 Actual air flow cfm700Air flow factor cfm/Btuh0.020 Air flow factor cfm/Btuh0.047Static pressure in H2O0.70 Static pressure in H2O0.70Space thermostat Load sensible heat ratio 1.00 2022-Mar-07 15:34:42 Right-Suite® Universal 2019 19.0.13 RSU20477 Page 1 S:\High Country\Wrightsoft\SF4B14 magnolia.rup Calc = MJ8 Front Door faces: S SF4B14Job:AED Assessment Date:Entire House Vince ByramBy: fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com Project Information Cody Puzey, Karthcner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F))H(34-Daily range (°F) 60-Wet bulb (°F)7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limit Gla z i n g l o a d ( B t u h ) Hour of Day 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 40.2%. House does not have adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 1013 Btuh (PFG - 1.3*AFG) Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Mar-07 15:34:42Right-Suite® Universal 2019 19.0.13 RSU20477 Page 1S:\High Country\Wrightsoft\SF4B14 magnolia.rup Calc = MJ8 Front Door faces: S SF4B14Job:Right-J® Worksheet Date:Entire House Vince ByramBy:fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Entire House Room1 2 Exposed wall 350.0 ft 31.3 ft3Room height 9.0 dft 9.0 heat/coolft 4 Room dimensions ft252.6x1.0 5 Room area 2910.2 ft²252.6 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.944.94 0.470.47 812 708 3498 336 0 0 0 0.GG 61C61C 0.3400.340 nene 25.8425.84 23.5823.58 48 0 1227 1120 0 0 0 0.GG 61C61C 0.3000.300 nene 22.8022.80 24.2424.24 35 0 798 848 0 0 0 0 .DD 11P011P0 0.2900.290 nene 22.0422.04 5.365.36 21 21 463 113 0 0 0 0 11 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.944.94 0.470.47 780 714 3527 339 0 0 0 0 GG 61C61C 0.3400.340 sese 25.8425.84 29.8629.86 15 0 388 448 0 0 0 0 GG 61C61C 0.3000.300 sese 22.8022.80 30.9230.92 51 0 1165 1580 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.944.94 0.470.47 779 597 2947 283 155 125 615 59 GG 61C61C 0.3400.340 swsw 25.8425.84 29.8629.86 50 0 1292 1493 0 0 0 0GG61C61C0.3000.300 swsw 22.8022.80 30.9230.92 132 0 3010 4082 30 0 684 928 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.944.94 0.470.47 780 728 3596 345 128 128 630 60GG61C61C0.3400.340 nwnw 25.8425.84 23.5823.58 15 0 388 354 0 0 0 0GG61C61C0.3000.300 nwnw 22.8022.80 24.2424.24 16 0 365 388 0 0 0 0 DD 11P011P0 0.2900.290 nwnw 22.0422.04 5.365.36 21 21 463 113 0 0 0 0CC16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 1731 1731 2631 1454 247 247 376 208 FF 21A-32c21A-32c 0.0200.020 --1.521.52 0.000.00 1485 1485 2257 0 253 253 384 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 291 35 932 0 0 0 0 0 6 c) AED excursion 1013 308 Envelope loss/gain 28945 14308 2689 1563 12 a)Infiltration 6745 621 604 56 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)35691 14929 3293 1619 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal356911492932931619 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 35691 14929 3293 1619 Air required (cfm)Air required (cfm)700 700 65 76 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Mar-07 15:34:42Right-Suite® Universal 2019 19.0.13 RSU20477 Page 2S:\High Country\Wrightsoft\SF4B14 magnolia.rup Calc = MJ8 Front Door faces: S SF4B14Job:Right-J® Worksheet Date:Entire House Vince ByramBy:fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Room3 Room4 2 Exposed wall 21.0 ft 81.8 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft9.5x11.5 ft814.3x1.0 5 Room area 109.3 ft²814.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.944.94 0.470.47 104 104 511 49 90 59 291 28.GG 61C61C 0.3400.340 nene 25.8425.84 23.5823.58 0 0 0 0 0 0 0 0.GG 61C61C 0.3000.300 nene 22.8022.80 24.2424.24 0 0 0 0 10 0 228 242 .DD 11P011P0 0.2900.290 nene 22.0422.04 5.365.36 0 0 0 0 21 21 463 113 11 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.944.94 0.470.47 0 0 0 0 275 223 1104 106 GG 61C61C 0.3400.340 sese 25.8425.84 29.8629.86 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 sese 22.8022.80 30.9230.92 0 0 0 0 51 0 1165 1580WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.944.94 0.470.47 0 0 0 0 252 150 741 71 GG 61C61C 0.3400.340 swsw 25.8425.84 29.8629.86 0 0 0 0 0 0 0 0GG61C61C0.3000.300 swsw 22.8022.80 30.9230.92 0 0 0 0 102 0 2326 3154 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.944.94 0.470.47 86 70 343 33 120 99 489 47GG61C61C0.3400.340 nwnw 25.8425.84 23.5823.58 0 0 0 0 0 0 0 0GG61C61C0.3000.300 nwnw 22.8022.80 24.2424.24 16 0 365 388 0 0 0 0 DD 11P011P0 0.2900.290 nwnw 22.0422.04 5.365.36 0 0 0 0 21 21 463 113CC16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 25 25 38 21 28 28 42 23 FF 21A-32c21A-32c 0.0200.020 --1.521.52 0.000.00 109 109 166 0 814 814 1238 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 132 134 Envelope loss/gain 1423 622 8549 5611 12 a)Infiltration 405 37 1577 145 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1828 660 10126 5756 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal1828660101265756 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1828 660 10126 5756 Air required (cfm)Air required (cfm)36 31 199 270 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Mar-07 15:34:42Right-Suite® Universal 2019 19.0.13 RSU20477 Page 3S:\High Country\Wrightsoft\SF4B14 magnolia.rup Calc = MJ8 Front Door faces: S SF4B14Job:Right-J® Worksheet Date:Entire House Vince ByramBy:fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Room6 Room7 2 Exposed wall 6.2 ft 24.0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft6.2x5.8 ft12.7x11.3 5 Room area 36.0 ft²143.6 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.944.94 0.470.47 0 0 0 0 102 77 380 37.GG 61C61C 0.3400.340 nene 25.8425.84 23.5823.58 0 0 0 0 0 0 0 0.GG 61C61C 0.3000.300 nene 22.8022.80 24.2424.24 0 0 0 0 25 0 570 606 .DD 11P011P0 0.2900.290 nene 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 11 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.944.94 0.470.47 0 0 0 0 114 114 563 54 GG 61C61C 0.3400.340 sese 25.8425.84 29.8629.86 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 sese 22.8022.80 30.9230.92 0 0 0 0 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3400.340 swsw 25.8425.84 29.8629.86 0 0 0 0 0 0 0 0GG61C61C0.3000.300 swsw 22.8022.80 30.9230.92 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.944.94 0.470.47 56 56 274 26 0 0 0 0GG61C61C0.3400.340 nwnw 25.8425.84 23.5823.58 0 0 0 0 0 0 0 0GG61C61C0.3000.300 nwnw 22.8022.80 24.2424.24 0 0 0 0 0 0 0 0 DD 11P011P0 0.2900.290 nwnw 22.0422.04 5.365.36 0 0 0 0 0 0 0 0CC16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 0 0 0 0 2 2 3 2 FF 21A-32c21A-32c 0.0200.020 --1.521.52 0.000.00 36 36 55 0 144 144 218 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -2 -31 Envelope loss/gain 329 24 1735 668 12 a)Infiltration 119 11 463 43 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)448 35 2197 710 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal448352197710 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 448 35 2197 710 Air required (cfm)Air required (cfm)9 2 43 33 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Mar-07 15:34:42Right-Suite® Universal 2019 19.0.13 RSU20477 Page 4S:\High Country\Wrightsoft\SF4B14 magnolia.rup Calc = MJ8 Front Door faces: S SF4B14Job:Right-J® Worksheet Date:Entire House Vince ByramBy:fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Room8 Room9 2 Exposed wall 10.0 ft 26.5 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft7.8x10.0 ft12.7x11.5 5 Room area 78.3 ft²145.7 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.944.94 0.470.47 90 90 445 43 104 81 400 38.GG 61C61C 0.3400.340 nene 25.8425.84 23.5823.58 0 0 0 0 23 0 581 531.GG 61C61C 0.3000.300 nene 22.8022.80 24.2424.24 0 0 0 0 0 0 0 0 .DD 11P011P0 0.2900.290 nene 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 11 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.944.94 0.470.47 0 0 0 0 114 114 563 54 GG 61C61C 0.3400.340 sese 25.8425.84 29.8629.86 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 sese 22.8022.80 30.9230.92 0 0 0 0 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3400.340 swsw 25.8425.84 29.8629.86 0 0 0 0 0 0 0 0GG61C61C0.3000.300 swsw 22.8022.80 30.9230.92 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.944.94 0.470.47 0 0 0 0 21 21 104 10GG61C61C0.3400.340 nwnw 25.8425.84 23.5823.58 0 0 0 0 0 0 0 0GG61C61C0.3000.300 nwnw 22.8022.80 24.2424.24 0 0 0 0 0 0 0 0 DD 11P011P0 0.2900.290 nwnw 22.0422.04 5.365.36 0 0 0 0 0 0 0 0CC16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 4 4 6 3 146 146 221 122 FF 21A-32c21A-32c 0.0200.020 --1.521.52 0.000.00 78 78 119 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -4 -50 Envelope loss/gain 570 42 1870 706 12 a)Infiltration 193 18 511 47 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)762 60 2381 753 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal762602381753 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 762 60 2381 753 Air required (cfm)Air required (cfm)15 3 47 35 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Mar-07 15:34:42Right-Suite® Universal 2019 19.0.13 RSU20477 Page 5S:\High Country\Wrightsoft\SF4B14 magnolia.rup Calc = MJ8 Front Door faces: S SF4B14Job:Right-J® Worksheet Date:Entire House Vince ByramBy:fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Room10 Room11 2 Exposed wall 42.2 ft 36.7 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft15.5x13.2 ft544.2x1.0 5 Room area 204.1 ft²544.2 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.944.94 0.470.47 119 119 585 56 183 158 781 75.GG 61C61C 0.3400.340 nene 25.8425.84 23.5823.58 0 0 0 0 25 0 646 590.GG 61C61C 0.3000.300 nene 22.8022.80 24.2424.24 0 0 0 0 0 0 0 0 .DD 11P011P0 0.2900.290 nene 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 11 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.944.94 0.470.47 3 3 15 1 66 66 326 31 GG 61C61C 0.3400.340 sese 25.8425.84 29.8629.86 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 sese 22.8022.80 30.9230.92 0 0 0 0 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.944.94 0.470.47 119 119 585 56 0 0 0 0 GG 61C61C 0.3400.340 swsw 25.8425.84 29.8629.86 0 0 0 0 0 0 0 0GG61C61C0.3000.300 swsw 22.8022.80 30.9230.92 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.944.94 0.470.47 140 125 615 59 81 81 400 38GG61C61C0.3400.340 nwnw 25.8425.84 23.5823.58 15 0 388 354 0 0 0 0GG61C61C0.3000.300 nwnw 22.8022.80 24.2424.24 0 0 0 0 0 0 0 0 DD 11P011P0 0.2900.290 nwnw 22.0422.04 5.365.36 0 0 0 0 0 0 0 0CC16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 204 204 310 171 544 544 827 457 FF 21A-32c21A-32c 0.0200.020 --1.521.52 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 108 22 599 0 183 12 333 0 6 c) AED excursion 98 -78 Envelope loss/gain 3098 796 3313 1114 12 a)Infiltration 813 75 707 65 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)3910 871 4019 1179 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal391087140191179 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 3910 871 4019 1179 Air required (cfm)Air required (cfm)77 41 79 55 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Mar-07 15:34:42Right-Suite® Universal 2019 19.0.13 RSU20477 Page 6S:\High Country\Wrightsoft\SF4B14 magnolia.rup Calc = MJ8 Front Door faces: S SF4B14Job:Right-J® Worksheet Date:Entire House Vince ByramBy:fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Room12 Room14 2 Exposed wall 0 ft 12.5 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft6.7x8.0 ft12.5x11.0 5 Room area 53.3 ft²137.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.944.94 0.470.47 0 0 0 0 0 0 0 0.GG 61C61C 0.3400.340 nene 25.8425.84 23.5823.58 0 0 0 0 0 0 0 0.GG 61C61C 0.3000.300 nene 22.8022.80 24.2424.24 0 0 0 0 0 0 0 0 .DD 11P011P0 0.2900.290 nene 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 11 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.944.94 0.470.47 0 0 0 0 113 98 482 46 GG 61C61C 0.3400.340 sese 25.8425.84 29.8629.86 0 0 0 0 15 0 388 448 GG 61C61C 0.3000.300 sese 22.8022.80 30.9230.92 0 0 0 0 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3400.340 swsw 25.8425.84 29.8629.86 0 0 0 0 0 0 0 0GG61C61C0.3000.300 swsw 22.8022.80 30.9230.92 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.944.94 0.470.47 0 0 0 0 0 0 0 0GG61C61C0.3400.340 nwnw 25.8425.84 23.5823.58 0 0 0 0 0 0 0 0GG61C61C0.3000.300 nwnw 22.8022.80 24.2424.24 0 0 0 0 0 0 0 0 DD 11P011P0 0.2900.290 nwnw 22.0422.04 5.365.36 0 0 0 0 0 0 0 0CC16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 53 53 81 45 138 138 209 115 FF 21A-32c21A-32c 0.0200.020 --1.521.52 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -3 20 Envelope loss/gain 81 42 1078 630 12 a)Infiltration 0 0 241 22 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)81 42 1319 652 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal81421319652 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 81 42 1319 652 Air required (cfm)Air required (cfm)2 2 26 31 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Mar-07 15:34:42Right-Suite® Universal 2019 19.0.13 RSU20477 Page 7S:\High Country\Wrightsoft\SF4B14 magnolia.rup Calc = MJ8 Front Door faces: S SF4B14Job:Right-J® Worksheet Date:Entire House Vince ByramBy:fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Room15 Room16 2 Exposed wall 6.0 ft 24.7 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft6.0x6.7 ft10.7x14.0 5 Room area 40.0 ft²149.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.944.94 0.470.47 0 0 0 0 0 0 0 0.GG 61C61C 0.3400.340 nene 25.8425.84 23.5823.58 0 0 0 0 0 0 0 0.GG 61C61C 0.3000.300 nene 22.8022.80 24.2424.24 0 0 0 0 0 0 0 0 .DD 11P011P0 0.2900.290 nene 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 11 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3400.340 sese 25.8425.84 29.8629.86 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 sese 22.8022.80 30.9230.92 0 0 0 0 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.944.94 0.470.47 0 0 0 0 126 101 499 48 GG 61C61C 0.3400.340 swsw 25.8425.84 29.8629.86 0 0 0 0 25 0 646 747GG61C61C0.3000.300 swsw 22.8022.80 30.9230.92 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.944.94 0.470.47 54 54 267 26 96 96 474 46GG61C61C0.3400.340 nwnw 25.8425.84 23.5823.58 0 0 0 0 0 0 0 0GG61C61C0.3000.300 nwnw 22.8022.80 24.2424.24 0 0 0 0 0 0 0 0 DD 11P011P0 0.2900.290 nwnw 22.0422.04 5.365.36 0 0 0 0 0 0 0 0CC16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 40 40 61 34 149 149 227 125 FF 21A-32c21A-32c 0.0200.020 --1.521.52 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -4 247 Envelope loss/gain 328 55 1846 1212 12 a)Infiltration 116 11 475 44 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)443 66 2322 1256 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal4436623221256 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 443 66 2322 1256 Air required (cfm)Air required (cfm)9 3 46 59 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Mar-07 15:34:42Right-Suite® Universal 2019 19.0.13 RSU20477 Page 8S:\High Country\Wrightsoft\SF4B14 magnolia.rup Calc = MJ8 Front Door faces: S SF4B14Job:Right-J® Worksheet Date:Entire House Vince ByramBy:fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Room17 Room5 2 Exposed wall 24.8 ft 2.3 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft10.7x14.2 ft7.8x6.5 5 Room area 151.1 ft²50.9 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.944.94 0.470.47 0 0 0 0 21 21 104 10.GG 61C61C 0.3400.340 nene 25.8425.84 23.5823.58 0 0 0 0 0 0 0 0.GG 61C61C 0.3000.300 nene 22.8022.80 24.2424.24 0 0 0 0 0 0 0 0 .DD 11P011P0 0.2900.290 nene 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 11 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.944.94 0.470.47 96 96 474 46 0 0 0 0 GG 61C61C 0.3400.340 sese 25.8425.84 29.8629.86 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 sese 22.8022.80 30.9230.92 0 0 0 0 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.944.94 0.470.47 128 103 506 49 0 0 0 0 GG 61C61C 0.3400.340 swsw 25.8425.84 29.8629.86 25 0 646 747 0 0 0 0GG61C61C0.3000.300 swsw 22.8022.80 30.9230.92 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.944.94 0.470.47 0 0 0 0 0 0 0 0GG61C61C0.3400.340 nwnw 25.8425.84 23.5823.58 0 0 0 0 0 0 0 0GG61C61C0.3000.300 nwnw 22.8022.80 24.2424.24 0 0 0 0 0 0 0 0 DD 11P011P0 0.2900.290 nwnw 22.0422.04 5.365.36 0 0 0 0 0 0 0 0CC16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 151 151 230 127 0 0 0 0 FF 21A-32c21A-32c 0.0200.020 --1.521.52 0.000.00 0 0 0 0 51 51 77 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 247 -1 Envelope loss/gain 1856 1214 181 9 12 a)Infiltration 479 44 45 4 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2335 1258 226 13 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal2335125822613 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2335 1258 226 13 Air required (cfm)Air required (cfm)46 59 4 1 Job #: SF4B14 Performed by Vince Byram for: Cody Puzey 3758 Yellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 Modern Plumbing Heating and Electric 3939 E 240 N Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Vince@modernphe.com Scale: 1 : 90 Page 1 Right-Suite® Universal 2019 19.0.13 RSU20477 2022-Mar-07 15:34:58 ...\Wrightsoft\SF4B14 magnolia.rup N main Room1 Room3 Room4 Room5 Room6 Room7 Room8 6" mechanical fresh air damper 38 cfm38 cfm 36 cfm 67 cfm 67 cfm 107 cfm275 cfm 14x3.25 14x3.25 14x3.25 12 x 8 12 x 8 14x3.25 12 x 8 14x3.25 14x3.25 14x3.25 14x3.25 43 cfm 12 x 8 12 x 8 14x3.25 4 cfm 6 " 67 cfm 6 " 6 " 6 " 6 " 6 " 12 x 86 " 6 " 15 cfm 6 " 6 "12 x 8 6 "6 " 43 cfm 67 cfm 9 cfm 6 "6 "6 " 12 x 8 6 " 6 " 6 " 12 x 8 6 " 6 "6 " 12 x 8 Job #: SF4B14 Performed by Vince Byram for: Cody Puzey 3758 Yellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 Modern Plumbing Heating and Electric 3939 E 240 N Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Vince@modernphe.com Scale: 1 : 90 Page 2 Right-Suite® Universal 2019 19.0.13 RSU20477 2022-Mar-07 15:34:58 ...\Wrightsoft\SF4B14 magnolia.rup N 2nd story Room9 Room10 Room11 Room12 Room13 Room14 Room15 Room16Room17 47 cfm 59 cfm 9 cfm 2 cfm 89 cfm 59 cfm 59 cfm 77 cfm 38 cfm 31 cfm 47 cfm 38 cfm 31 cfm 39 cfm 39 cfm 59 cfm 2022-Mar-07 15:34:43 Right-Suite® Universal 2019 19.0.13 RSU20477 Page 1 S:\High Country\Wrightsoft\SF4B14 magnolia.rup Calc = MJ8 Front Door faces: S SF4B14Job:Duct System Summary Date:Entire House Vince ByramBy: fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com Project Information Cody Puzey, Karthcner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0.34in H2O0.34 Available static pressure in H2O0.36in H2O0.36 Supply / return available pressure 0.201 / 0.159 in H2O in H2O0.201 / 0.159 Lowest friction rate in/100ft0.054in/100ft0.054 Actual air flow cfm700cfm700 Total effective length (TEL)ft669 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st1150.022.0ShMt0x06.00.1173832809cRoom1 st1185.033.0ShMt0x06.00.0923832809cRoom1-A st1A230.019.0ShMt0x06.00.08120381955hRoom10 st1185.029.0ShMt0x06.00.09420381955hRoom10-A st2270.030.5ShMt0x06.00.06728392010hRoom11 95.020.5ShMt0x06.00.17428392010hRoom11-A st2295.011.0ShMt0x06.00.0662242cRoom12 st2B345.029.0ShMt0x06.00.0543126652cRoom14 st2225.08.0ShMt0x06.00.08639443hRoom15 st2305.020.0ShMt0x06.00.06259461256cRoom16 st2260.035.5ShMt0x06.00.06859461258cRoom17 st1195.019.5ShMt0x06.00.09431361828hRoom3 st2305.019.8ShMt0x06.00.06267501439cRoom4 st2B335.028.0ShMt0x06.00.05567501439cRoom4-A st2A280.037.5ShMt0x06.00.06367501439cRoom4-B st2290.030.0ShMt0x06.00.06367501439cRoom4-C st2160.03.5ShMt0x06.00.12314226hRoom5 st2280.024.0ShMt0x06.00.06629448hRoom6 st2A280.044.5ShMt0x06.00.06233432197hRoom7 st1150.07.5ShMt0x06.00.128315762hRoom8 st2A290.043.5ShMt0x06.00.06035472381hRoom9 2022-Mar-07 15:34:43 Right-Suite® Universal 2019 19.0.13 RSU20477 Page 2 S:\High Country\Wrightsoft\SF4B14 magnolia.rup Calc = MJ8 Front Door faces: S Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st2 Peak AVF 469 522 0.054 783 12.2 12x8 ShtMetl st2A Peak AVF 215 234 0.054 351 9.1 12x8 ShtMetl st2 st1A Peak AVF 38 20 0.081 58 4.3 12x8 ShtMetl st1 st1 Peak AVF 192 150 0.081 288 7.8 12x8 ShtMetl st2B Peak AVF 76 98 0.054 147 6.6 12x8 ShtMetl st2A Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb9 0x 430 33 294.5 0.054 136 4.8 3.25x14 10x9 SJSp rt1B rb3 0x 470 35 170.2 0.093 148 4.4 3.25x14 10x9 SJSp rt1A rb6 0x 460 59 109.0 0.145 186 4.4 3.25x14 10x9 SJSp rt1 rb5 0x 460 59 120.3 0.132 187 4.5 3.25x14 10x9 SJSp rt1 rb2 0x 890 60 90.0 0.176 282 5.0 3.25x14 10x9 SJSp rt1 rb4 0x 260 31 186.7 0.085 97 3.9 3.25x14 10x9 SJSp rt1A rb7 0x 770 41 229.0 0.069 243 5.7 3.25x14 10x9 SJSp rt2A rb8 0x 1000 107 166.0 0.096 338 6.0 3.25x14 10x9 SJSp rt2 rb10 0x 2270 275 62.3 0.254 870 7.0 3.25x14 10x9 SJSp Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1B Peak AVF 43 33 0.054 65 4.8 12x8 ShtMetl rt1A rt1A Peak AVF 116 99 0.054 173 7.0 12x8 ShtMetl rt1 rt1 Peak AVF 296 277 0.054 444 9.9 12x8 ShtMetl rt2A Peak AVF 77 41 0.069 115 5.7 12x8 ShtMetl rt2 rt2 Peak AVF 177 148 0.069 266 7.8 12x8 ShtMetl