2000 International Fire Code
Plan Rev ielv
Building; Name- NEWPORT CONDOMINNMS
Building Address: 300 BLOCK OF WEST 7TII SOUTH
Stories,- 3
Type of ConstrLiction: V -S
Occupancy Classification. R-2
Plait Date: 5-22-03
Review Date: 5-29-03
d.
Z7)
Existina Floor Area: N/A
New Construction Floor Area: APPROXIMATELY 201 560 SQUARE FEET EACH
Bi7ILDING
L Required Fire Flow (Appendix B).- 3,750 GPNi/THREE HOURS
Comments: FIRE FLOW MAYBE REDUCED LF EACH BUILDING HAS A FIRE
SUPPRESSION SYSTEM THROUGHOUT.
2. Wateir Supply (Section 508, Appendix C) Required.- YES
Fire Hydrant Location, OKAY
Fire Hydrant Flows, UNKNOWN
Fire Flow Test Locatian: N/A
Fire Flow Supplied By: N/A
Other Approved Water Source- NONE
Water Supply Acceptable: SEE. COMMENTS
Fire Hydrant Location. Acceptable.- YES
-4
PQ
Water Supply Comments: PLEASE PROVIDE AN ENGINEER'S As SESSMENT
OF WATER FLOWS PRIOR TO CONSTRUCTION.
3. Fire Apparatus Access Roads (Secti'mon 5p;, Appeiidix I�) Requisred: YES
Acceptable Width.- X
Length: X
Complete Road Acceptable: YES
Comments: NONE
Surface: X
4. access Roads and Water Supply, including fire hydrants are required to be installed
and made serviceable prior to and during time of construction (Section 50 1):
Comments.- tF NOT INSTALLED PRIOR TO CONSTRUCTION ANA MADE
MENI
OPERATIONAL, A STOP WORK ORDER WILL BE ISSUED.
5. Installation of portable fire extinguishers (Section. 906) Required: YES
Location shown: NOT SHOWN
Type provided acceptable: NOT SHOWN
Comments: A/1INIMUM SIZE OF 2A10I3C REQU -RE-D TO BE ]MOUNTED IN
EACH UNIT NEAR TRE KITCHEN AREA.
6. Automat'c firs extinguishing systems (Sect-
ion 9U3) Required: SES
Type Of system being installed: NOT StIOWN
Sprinkler system monitoring (Section 907) required: YES
Comments: PLANS REQUIRED TO BE SUBMITTED TO STATE PRIOR TO
ISSUANCE OF A BUILDING PERMIT.
7. Standpipes (Section 9Q5) required: NO
Type required: Comments:
8. Ventilating hood and duct fire extinguisher system (Section 609) required: NO
Type being provided:
Automatic fuel shut -ofd required.-
Portable
equired:
Portable fire extinguisher shown:
Comments-
9. -
Fire alarm systems (Section 907) required,-
Type
equired:Type ofsystern required- Manual:.
Type, of system being provided,-
Manual:
Automatic.,
Automatisc*
Components of system shown: Smoky Deiectors: X
Manual Pull Station, Soundina Devices, -b
Do -or Holders. -
Duct Detec,iors:
Sprinkler Valve Mon'tor'in;: REQUIRED
Both: X
Both: X
Head Detectors:
Vis-ual Devices -
r
Flew Alarm
Fire Alarm System Acceptable: NO, SEE COMMENTS BELOW
10. Other corrections that are required by special occupancy or conditions: FIR -E,
ALARNI SYSTEM: PLEASE SUBMff PLANS IN ADDITION TO THE
FOLLOWING SUBMITTALS: ALARM co
OL AND TOUR -BLE
SIGNALING EQL'IPNIENT, ANNUNCIATION, POWERCONNECTION,
BATTERY CALCULATIONS, CONDUCTOR TYPE AND S[ZES, VOLTAGE
DROP CALCULATIONS, MANUFACTURERS MODEL NUMBERS, AND
LISTING INFORMATION FOR EQ
UIPNIENT, EVICES A.ND MATERIALS
AND INTERFACE CONNECTIONS. ADA UNITS SHALL HAVE ALL
RORN/STROBEUNITS. PLANS:N/IUST BE SUBMITTED PRIOR TO
CONSTRUCTION OR A STOP WORK OR -DER WILL BEMOM ISSUED.
Pians as submitted are acceptable: NO
Plans checked by: CHRIS HUSKINSON Tate: 15. him
Please furnish comments back to the pian reviewer xn the following
Written Comments: X New Plans: X
manner:
11F. 4
4
i
A
rl
I
Y
D h�t i n i 2L rz1S
a
N
�
i
I
Y
D h�t i n i 2L rz1S