HomeMy WebLinkAboutENGINEER LETTER - 21-00867 - 625 Autumn Ct - Solar Panels
55 WEST 500 SOUTH, HEBER CITY, UT 84032
T 925.787.3067 U RIGHTANGLEENG.COM
November 1, 2021
Horizon PWR
166 Valley Street
Providence, RI 02909
RE: Structural Roof Evaluation for the Rawlings Residence: 625 Autumn Court,
Rexburg, Idaho
As per your request, we have evaluated the roof structure under the proposed solar panel array. The
information used to evaluate this structure was gathered by Horizon PWR on behalf of Right Angle
Engineering. The roof structure consists of pre-manufactured trusses spaced at 24” on center. The roof
material consists of asphalt shingles. The design criteria used to analyze this structure are listed above
and included with this letter. The adopted building codes in this jurisdiction are: the 2018 International
Building Code, the 2018 International Existing Building Code, and ASCE 7-16.
International Existing Building Code (IEBC) 2018 section 806.2 indicates that alterations to an existing
building that results in less than a 5% increase in the total stress may be performed without a structural
evaluation of the existing building. As demonstrated in the attached calculations, the additional weight
of the solar panels will be less than 5% increase in the gravity loading and the stress on the existing roof
framing.
Based on our assessment we have determined that the existing roof framing will safely and adequately
support the additional loads imposed by the solar panels without reinforcement. In order for the loads
to be evenly distributed, the roof attachments should be staggered and spread evenly throughout the
panel array. Attachment points should be spaced at a maximum of 48” on center. The racking system
should be installed per the manufacture’s specifications. There should be a minimum of 65 FlashFoot2
attachment points to the roof. Each attachment should have a 5/16” or 18/8 SS lag screw with 2.5”
minimum penetration centered on each truss top chord or rafter. Waterproofing around the roof
penetrations is the responsibility of others. Right Angle Engineering assumes no responsibility for
improper installation of the solar panels.
Regards,
Robert D Smythe, P.E.
Right Angle Engineering
11/1/21
Design Criteria:
Design Wind Speed (ASD)- 115 mph
Ground Snow Load- 50 psf
Risk Category- II
Exposure category- C
2
Design Criteria:
Design Wind Speed (3 second gust) 115 mph
Exposure Category C
Risk Category 2
Mean Roof Height 30 ft
Roof Type Gable Roof
Building Type enclosed
Roof Dead Load- ASCE Table C3-1
Asphalt Shingles 2 psf
5/8" Plywood Sheathing 2 psf
Roof Framing 4 psf
Insulation 3.85 psf
Gypsum sheathing 2 psf
Solar Panel Array 3 psf
Dead Load Without Panels 13.85 psf
Dead Load With Solar panels 16.85 psf
Roof Live Load
Existing Roof Live Load 20 psf ASCE 7-16 Table 4.3-1
Roof Live Load with Solar Panels 0 psf 2018 IBC 1607.13.5.1
Roof Snow Load-ASCE 7-16
Ground Snow Load (pg) 50 psf Section 7.2
Exposure Factor (Ce) 0.9 Table 7.3-1
Thermal Factor (Ct) 1.1 Table 7.3-2
Importance Factor (Is) 1 Table 1.5-2
Flat Roof Snow Load (Pf) 35 Equation 7.3-1
Slippery surface Slope Factor (Cs) 0.57 Figure 7-2
Nonslippery Surface Slope Factor
(Cs) 1 Figure 7-2
Roof Snow Load 35 psf Equation 7.4-1
Reduced Roof Snow Load (Slippery
Surface) 20 psf Equation 7.4-1
Load Combinations - ASCE 7-16 Section 2.4.1
Without Solar Panels
With Solar
panels
D + Lr 33.8 psf 16.8 psf
D + S 48.5 psf 36.5 psf
3
Solar Array 1- Array One
Roof Slope 36 degrees
Number of panels 7
Panel Area 122.5 ft^2
Wind Calculations- ASCE 7-16
GCp Zone 1 -1 Figure 30.3-(2A-5B)
GCp Zone 2 -1.8 Figure 30.3-(2A-5B)
GCp Zone 3 -2.8 Figure 30.3-(2A-5B)
Gcpi 0.18 Table 26.13-1
Velocity Pressure (qh) 28.2 psf
qh= .00256KhKhtKdV^2 Equation 26.10-1
Kh 0.98 Table 26.10-1
Kht 1 Equation 26.8-1
Kd 0.85 Table 26.6-1
Designed wind pressure (P) psf Equation 30.8-1
P= qh(GCh) - (GChi))
Zone 1 Pressure (P) -33.3 psf
Zone 2 Pressure (P) -55.8 psf
Zone 3 Pressure (P) -84 psf
Roof Connection
Shear Capacity 396 lbs NDS 2015 Table 12K
Shear tributary area 29.8 ft^2
Pullout Capacity 266 lbs/in
Lag screw embedment 2.5 in
Total pullout capacity 951 lbs NDS 2015 Table 12.2A
Pullout max tributary area 17 ft^2
Factor of Safety 2.11
Minimum number of connections 12
Beam Stress IEBC 2018 Section 806.2
Beam Span 14 ft
Spacing 2 ft
Roof Framing type pre-manufactured trusses
Panel Orientation portrait
Number of Panels per rafter 2
Panel distance from eave 0
Without Solar
Panels
With Solar
Panels
Percent
Increase
Bending Moment 2376.5 ft-lbs 1785.6 ft-lbs 75.1% Less than 105%
Vertical Reaction (V1) 679 lbs 567.3 lbs 83.5% Less than 105%
Vertical Reaction (V2) 679 lbs 514.12 lbs 75.7% Less than 105%
4
Solar Array 2- Array Two
Roof Slope 36 degrees
Number of panels 7
Panel Area 122.5 ft^2
Wind Calculations- ASCE 7-16
GCp Zone 1 -1 Figure 30.3-(2A-5B)
GCp Zone 2 -1.2 Figure 30.3-(2A-5B)
GCp Zone 3 -1.2 Figure 30.3-(2A-5B)
Gcpi 0.18 Table 26.13-1
Velocity Pressure (qh) 28.2 psf
qh= .00256KhKhtKdV^2 Equation 26.10-1
Kh 0.98 Table 26.10-1
Kht 1 Equation 26.8-1
Kd 0.85 Table 26.6-1
Designed wind pressure (P) psf Equation 30.8-1
P= qh(GCh) - (GChi))
Zone 1 Pressure (P) -33.3 psf
Zone 2 Pressure (P) -38.9 psf
Zone 3 Pressure (P) -38.9 psf
Lag Screw Connection
Shear Capacity 396 lbs NDS 2015 Table 12K
Shear tributary area 29.8 ft^2
Pullout Capacity 266 lbs/in
Lag screw embedment 2.5 in
Total pullout capacity 951 lbs NDS 2015 Table 12.2A
Pullout max tributary area 24.4 ft^2
Factor of Safety 2.91
Minimum number of connections 11
Beam Stress IEBC 2018 Section 806.2
Beam Span 14 ft
Spacing 2 ft
Roof Framing type pre-manufactured trusses
Panel Orientation portrait
Number of Panels per rafter 2
Panel distance from eave 0
Without Solar
Panels
With Solar
Panels
Percent
Increase
Bending Moment 2376.5 ft-lbs 1810.6 ft-lbs 76.2% Less than 105%
Vertical Reaction (V1) 679 lbs 576.4 lbs 84.9% Less than 105%
Vertical Reaction (V2) 679 lbs 517.4 lbs 76.2% Less than 105%
5
Solar Array 3- Array Three
Roof Slope 36 degrees
Number of panels 16
Panel Area 280 ft^2
Wind Calculations- ASCE 7-16
GCp Zone 1 -1 Figure 30.3-(2A-5B)
GCp Zone 2 -1.2 Figure 30.3-(2A-5B)
GCp Zone 3 -1.2 Figure 30.3-(2A-5B)
Gcpi 0.18 Table 26.13-1
Velocity Pressure (qh) 28.2 psf
qh= .00256KhKhtKdV^2 Equation 26.10-1
Kh 0.98 Table 26.10-1
Kht 1 Equation 26.8-1
Kd 0.85 Table 26.6-1
Designed wind pressure (P) psf Equation 30.8-1
P= qh(GCh) - (GChi))
Zone 1 Pressure (P) -33.3 psf
Zone 2 Pressure (P) -38.9 psf
Zone 3 Pressure (P) -38.9 psf
Lag Screw Connection
Shear Capacity 396 lbs NDS 2015 Table 12K
Shear tributary area 29.8 ft^2
Pullout Capacity 266 lbs/in
Lag screw embedment 2.5 in
Total pullout capacity 951 lbs NDS 2015 Table 12.2A
Pullout max tributary area 24.4 ft^2
Factor of Safety 2.91
Minimum number of connections 26
Beam Stress IEBC 2018 Section 806.2
Beam Span 15 ft
Spacing 2 ft
Roof Framing type pre-manufactured trusses
Panel Orientation portrait
Number of Panels per rafter 2
Panel distance from eave 0
Without Solar
Panels
With Solar
Panels
Percent
Increase
Bending Moment 2728.1 ft-lbs 2052.7 ft-lbs 75.2% Less than 105%
Vertical Reaction (V1) 727.5 lbs 614.2 lbs 84.4% Less than 105%
Vertical Reaction (V2) 727.5 lbs 576.7 lbs 79.3% Less than 105%
6
Solar Array 4- Array Four
Roof Slope 36 degrees
Number of panels 10
Panel Area 175 ft^2
Wind Calculations- ASCE 7-16
GCp Zone 1 -1 Figure 30.3-(2A-5B)
GCp Zone 2 -1.2 Figure 30.3-(2A-5B)
GCp Zone 3 -1.2 Figure 30.3-(2A-5B)
Gcpi 0.18 Table 26.13-1
Velocity Pressure (qh) 28.2 psf
qh= .00256KhKhtKdV^2 Equation 26.10-1
Kh 0.98 Table 26.10-1
Kht 1 Equation 26.8-1
Kd 0.85 Table 26.6-1
Designed wind pressure (P) psf Equation 30.8-1
P= qh(GCh) - (GChi))
Zone 1 Pressure (P) -33.3 psf
Zone 2 Pressure (P) -38.9 psf
Zone 3 Pressure (P) -38.9 psf
Lag Screw Connection
Shear Capacity 396 lbs NDS 2015 Table 12K
Shear tributary area 29.8 ft^2
Pullout Capacity 266 lbs/in
Lag screw embedment 2.5 in
Total pullout capacity 951 lbs NDS 2015 Table 12.2A
Pullout max tributary area 24.4 ft^2
Factor of Safety 2.91
Minimum number of connections 16
Beam Stress IEBC 2018 Section 806.2
Beam Span 18 ft
Spacing 2 ft
Roof Framing type pre-manufactured trusses
Panel Orientation portrait
Number of Panels per rafter 3
Panel distance from eave 0
Without Solar
Panels
With Solar
Panels
Percent
Increase
Bending Moment 3928.5 ft-lbs 2829.5 ft-lbs 72% Less than 105%
Vertical Reaction (V1) 873 lbs 724.9 lbs 83% Less than 105%
Vertical Reaction (V2) 873 lbs 624.9 lbs 71.6% Less than 105%