LOAD SHORT FORM - 21-00733 - 266 Mohawk Ave - Mechanical
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-16 10:57:07 Right-Suite® Universal 2021 21.0.10 RSU28163 Page 1 ...s\Dougs Const. Repair\Dan Highland\Highland.rup Calc = MJ8 Front Door faces: W HighlandJob:Load Short Form 01/15/2022Date:Entire House Gene MillerBy: 266 MowhawkPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Dougs Construction RepairFor: 418 N 4014 E Suite #4, Rigby, Id 83442 Phone: 208-356-9331 Design Information InfiltrationClgHtg SimplifiedMethod90-7Outside db (°F) Semi-tightConstruction quality7570Inside db (°F) 0Fireplaces1577Design TD (°F) H-Daily range 5030Inside humidity (%) -2935Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Goodman Mfg.Make Goodman Mfg. Trade GOODMAN Trade GOODMAN Model GMES960603BUA Cond GSX130241E* AHRI ref 204271258 Coil D(A,C,E)30A34++TDR AHRI ref 206229898 Efficiency 96.1 AFUE Efficiency 10.8 EER, 13.5 SEER Heating input Btuh60000 Sensible cooling Btuh19740 Heating output Btuh46980 Latent cooling Btuh0 Temperature rise °F48 Total cooling Btuh19740 Actual air flow cfm1070 Actual air flow cfm1170 Air flow factor cfm/Btuh0.035 Air flow factor cfm/Btuh0.068 Static pressure in H2O0.90 Static pressure in H2O0.90 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Storage Utility 443 0 0 0 0 Bedroom 3 229 3628 1441 129 97 Bedroom 4 151 2366 1635 84 110 Living Rm 602 7910 3583 280 242 B Bath 36 130 18 5 1 Master 176 2834 1918 100 130 Bath 48 481 95 17 6 Room8 23 0 0 0 0 Bedroom 2 169 2391 1513 85 102 Kit/Din/Great Rm 1045 10446 7125 370 481 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-16 10:57:07 Right-Suite® Universal 2021 21.0.10 RSU28163 Page 2 ...s\Dougs Const. Repair\Dan Highland\Highland.rup Calc = MJ8 Front Door faces: W Entire House 2923 30187 17328 1070 1170 Other equip loads 6080 1157 Equip. @ 0.95 RSM 17487 Latent cooling 0 TOTALS 2923 36266 17487 1070 1170 2022-Jan-16 10:57:07 Right-Suite® Universal 2021 21.0.10 RSU28163 Page 1...s\Dougs Const. Repair\Dan Highland\Highland.rup Calc = MJ8 Front Door faces: W HighlandJob:Building Analysis 01/15/2022Date:Entire House Gene MillerBy: 266 MowhawkPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Dougs Construction RepairFor:418 N 4014 E Suite #4, Rigby, Id 83442Phone: 208-356-9331 Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation:5030Relative humidity (%)°N44Latitude:Outdoor:-29.435.3Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F)SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Doors Ceilings Floors Infiltration Ventilation % of loadBtuhBtuh/ft²Component 38.4139255.1Walls 10.8393523.0Glazing 2.9104729.9Doors 8.029142.0Ceilings 7.727941.91.9Floors 15.455732.3Infiltration 00Ducts00Piping00Humidification16.86080Ventilation0Adjustments100.036266Total Cooling Walls Glazing OtherCeilings FloorsInfiltration Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 7.614030.5Walls 43.6806047.1Glazing 1.42547.3Doors 8.715991.1Ceilings 2.95320.4Floors 2.95300.2Infiltration 00Ducts6.31157Ventilation26.84950Internal gains 00Blower0Adjustments100.018485Total Latent Cooling Load = 0 BtuhOverall U-value = 0.055 Btuh/ft²-°F ERROR: negative wall area in Bedroom 4 - check windows. 2022-Jan-16 10:57:07Right-Suite® Universal 2021 21.0.10 RSU28163 Page 1...s\Dougs Const. Repair\Dan Highland\Highland.rup Calc = MJ8 Front Door faces: W HighlandJob:Component Constructions 01/15/2022Date:Entire House Gene MillerBy: 266 MowhawkPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Dougs Construction RepairFor:418 N 4014 E Suite #4, Rigby, Id 83442Phone: 208-356-9331 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5030Relative humidity (%)°N44Latitude:Outdoor:-29.435.3Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12E-0sw: Frm wall, vnl ext, 3/8" wood shth, r-19 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 3720.6530045.2219.00.068576n 2280.6518385.2219.00.068353e 1860.6515025.2219.00.068288s 5710.6546115.2219.00.068884w 13570.65109555.2219.00.0682101all 15B13-0wc-6: Bg wall, light dry soil, 2"x4" wood int frm, concrete wall, r-13 cav ins, 10" thk, 1/2" gypsum board int fnsh 260.0620494.8013.00.053427e 200.0714164.9213.00.053288s 460.0729694.6013.00.053646all Partitions (none) Windows1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.35); foreground = new concrete (0.32); 6.67 ft head ht 377147.1184123.000.30080e 108447.152923.000.30023e 75447.136823.000.30016w 245147.1119723.000.30052w 806047.1393523.000.300171all Doors 11D0: Door, wd sc type 1277.2552329.900.39018e 1277.2552329.900.39018w 2547.25104729.900.39035all Ceilings 16B-38ad: Attic ceiling, asphalt shingles roof mat, r-38 ceil ins, 1/2" gypsum board int fnsh 15991.0929141.9938.00.0261461 Floors19A-38cvtp: Flr floor, frm flr, 10" thkns, r-38 cav ins, leaky crwl ovr 0.3627941.9138.00.0291461 532 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-16 10:57:07Right-Suite® Universal 2021 21.0.10 RSU28163 Page 1...s\Dougs Const. Repair\Dan Highland\Highland.rup Calc = MJ8 Front Door faces: W HighlandJob:Project Summary 01/15/2022Date:Entire House Gene MillerBy: 266 MowhawkPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Dougs Construction RepairFor:418 N 4014 E Suite #4, Rigby, Id 83442Phone: 208-356-9331 INFORMATION CONTAINED WITHIN THE REPORT IS PER THE RESCHECK COMPLIANCE CERTIFICATE. IF ANY OF THESE VALUES SHOULD CHANGE, THIS REPORT WILL BE NULL AND VOID. OVERSIZED EQUIPMENT IS AT OWNERS REQUEST. Notes: Design Information Idaho Falls Rgnl, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-7 Outside db °F90Inside db °F70 Inside db °F75Design TD °F77 Design TD °F15Daily range HRelative humidity %50Moisture difference gr/lb-29 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh30187 Structure Btuh17328DuctsBtuh0DuctsBtuh0Central vent (86 cfm)6080 Btuh Central vent (86 cfm)Btuh1157Outside air Outside airHumidificationBtuh0Blower Btuh0PipingBtuh0Equipment load Btuh36266 Use manufacturer's data nRate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh17487 Method Latent Cooling Equipment Load SizingSimplifiedConstruction quality Semi-tight0Fireplaces Structure Btuh341DuctsBtuh0Central vent (86 cfm)Btuh-1439CoolingHeatingOutside air29232923Area (ft²)Equipment latent load Btuh02144421444Volume (ft³)Air changes/hour 0.110.22 Equipment Total Load (Sen+Lat)Btuh17487Equiv. AVF (cfm)3979 Req. total capacity at 1.00 SHR ton1.5 Heating Equipment Summary Cooling Equipment Summary Make Goodman Mfg.Make Goodman Mfg.Trade GOODMAN Trade GOODMANModelGMES960603BUACondGSX130241E*AHRI ref 204271258 Coil D(A,C,E)30A34++TDRAHRI ref 206229898Efficiency96.1 AFUE Efficiency 10.8 EER, 13.5 SEERHeating input Btuh60000 Sensible cooling Btuh19740Heating output Btuh46980 Latent cooling Btuh0Temperature rise °F48 Total cooling Btuh19740Actual air flow cfm1070 Actual air flow cfm1170Air flow factor cfm/Btuh0.035 Air flow factor cfm/Btuh0.068Static pressure in H2O0.90 Static pressure in H2O0.90Space thermostat Load sensible heat ratio 1.00 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-16 10:57:07Right-Suite® Universal 2021 21.0.10 RSU28163 Page 1...s\Dougs Const. Repair\Dan Highland\Highland.rup Calc = MJ8 Front Door faces: W HighlandJob:Right-J® Worksheet 01/15/2022Date:Entire House Gene MillerBy:266 MowhawkPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Entire House Storage Utility 2 Exposed wall 328.0 ft 47.3 ft3Room height 9.0 ft 9.0 heat/coolft 4 Room dimensions ft443.0x1.0 5 Room area 2922.5 ft²443.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12E-0sw12E-0sw 0.0680.068 nn 5.225.22 0.650.65 576 576 3004 372 0 0 0 0.WW 12E-0sw12E-0sw 0.0680.068 ee 5.225.22 0.650.65 450 353 1838 228 0 0 0 0.GG 1D-c2ov1D-c2ov 0.3000.300 ee 23.0123.01 47.1347.13 80 0 1841 3771 0 0 0 0 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 18 18 523 127 0 0 0 0 11 WW 15B13-0wc-615B13-0wc-6 0.0930.093 ee 4.804.80 0.060.06 450 427 2049 26 333 330 1616 22 GG 1D-c2ov1D-c2ov 0.3000.300 ee 23.0123.01 47.1347.13 23 0 529 1084 3 0 69 141 WW 12E-0sw12E-0sw 0.0680.068 ss 5.225.22 0.650.65 288 288 1502 186 0 0 0 0WW15B13-0wc-615B13-0wc-6 0.0930.093 ss 4.924.92 0.070.07 288 288 1416 20 92 92 454 6 WW 12E-0sw12E-0sw 0.0680.068 ww 5.225.22 0.650.65 900 884 4611 571 0 0 0 0GG1D-c2ov1D-c2ov 0.3000.300 ww 23.0123.01 47.1347.13 16 0 368 754 0 0 0 0 WW 15B13-0wc-615B13-0wc-6 0.0930.093 ww 7.137.13 0.000.00 0 -70 -496 0 0 0 0 0GG1D-c2ov1D-c2ov 0.3000.300 ww 23.0123.01 47.1347.13 52 0 1197 2451 0 0 0 0DD11D011D00.3900.390 ww 29.9129.91 7.257.25 18 18 523 127 0 0 0 0 CC 16B-38ad16B-38ad 0.0260.026 --1.991.99 1.091.09 1461 1461 2914 1599 0 0 0 0FF19A-38cvtp19A-38cvtp 0.0290.029 --1.911.91 0.360.36 1461 1461 2794 532 443 443 847 161 6 c) AED excursion 0 -20 Envelope loss/gain 24614 11847 2986 312 12 a)Infiltration 5573 530 272 26 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 5 1150 0 0 Appliances/other 3800 0 Subtotal (lines 6 to 13)30187 17328 3258 338 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution00-3258 -33814Subtotal301871732800 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 30187 17328 0 0 Air required (cfm)Air required (cfm)1070 1170 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-16 10:57:07Right-Suite® Universal 2021 21.0.10 RSU28163 Page 2...s\Dougs Const. Repair\Dan Highland\Highland.rup Calc = MJ8 Front Door faces: W HighlandJob:Right-J® Worksheet 01/15/2022Date:Entire House Gene MillerBy:266 MowhawkPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Bedroom 3 Bedroom 4 2 Exposed wall 35.8 ft 26.0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft229.0x1.0 ft151.0x1.0 5 Room area 229.0 ft²151.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12E-0sw12E-0sw 0.0680.068 nn 5.225.22 0.650.65 171 171 892 110 117 117 610 76.WW 12E-0sw12E-0sw 0.0680.068 ee 5.225.22 0.650.65 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.3000.300 ee 23.0123.01 47.1347.13 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 11 WW 15B13-0wc-615B13-0wc-6 0.0930.093 ee 4.804.80 0.060.06 117 97 433 3 0 0 0 0 GG 1D-c2ov1D-c2ov 0.3000.300 ee 23.0123.01 47.1347.13 20 0 460 943 0 0 0 0 WW 12E-0sw12E-0sw 0.0680.068 ss 5.225.22 0.650.65 0 0 0 0 0 0 0 0WW15B13-0wc-615B13-0wc-6 0.0930.093 ss 4.924.92 0.070.07 34 34 166 2 0 0 0 0 WW 12E-0sw12E-0sw 0.0680.068 ww 5.225.22 0.650.65 0 0 0 0 117 117 610 76GG1D-c2ov1D-c2ov 0.3000.300 ww 23.0123.01 47.1347.13 0 0 0 0 0 0 0 0 WW 15B13-0wc-615B13-0wc-6 0.0930.093 ww 7.137.13 0.000.00 0 0 0 0 0 -20 -143 0GG1D-c2ov1D-c2ov 0.3000.300 ww 23.0123.01 47.1347.13 0 0 0 0 20 0 460 943DD11D011D00.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 CC 16B-38ad16B-38ad 0.0260.026 --1.991.99 1.091.09 0 0 0 0 0 0 0 0FF19A-38cvtp19A-38cvtp 0.0290.029 --1.911.91 0.360.36 229 229 438 83 151 151 289 55 6 c) AED excursion -55 205 Envelope loss/gain 2389 1087 1827 1354 12 a)Infiltration 490 47 539 51 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 1 230 1 230 Appliances/other 0 0 Subtotal (lines 6 to 13)2879 1364 2366 1635 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution749780014Subtotal3628144123661635 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 3628 1441 2366 1635 Air required (cfm)Air required (cfm)129 97 84 110 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-16 10:57:07Right-Suite® Universal 2021 21.0.10 RSU28163 Page 3...s\Dougs Const. Repair\Dan Highland\Highland.rup Calc = MJ8 Front Door faces: W HighlandJob:Right-J® Worksheet 01/15/2022Date:Entire House Gene MillerBy:266 MowhawkPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Living Rm B Bath 2 Exposed wall 55.0 ft 0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft602.3x1.0 ft6.0x6.0 5 Room area 602.3 ft²36.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12E-0sw12E-0sw 0.0680.068 nn 5.225.22 0.650.65 0 0 0 0 0 0 0 0.WW 12E-0sw12E-0sw 0.0680.068 ee 5.225.22 0.650.65 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.3000.300 ee 23.0123.01 47.1347.13 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 11 WW 15B13-0wc-615B13-0wc-6 0.0930.093 ee 4.804.80 0.060.06 0 0 0 0 0 0 0 0 GG 1D-c2ov1D-c2ov 0.3000.300 ee 23.0123.01 47.1347.13 0 0 0 0 0 0 0 0 WW 12E-0sw12E-0sw 0.0680.068 ss 5.225.22 0.650.65 0 0 0 0 0 0 0 0WW15B13-0wc-615B13-0wc-6 0.0930.093 ss 4.924.92 0.070.07 162 162 797 11 0 0 0 0 WW 12E-0sw12E-0sw 0.0680.068 ww 5.225.22 0.650.65 333 333 1737 215 0 0 0 0GG1D-c2ov1D-c2ov 0.3000.300 ww 23.0123.01 47.1347.13 0 0 0 0 0 0 0 0 WW 15B13-0wc-615B13-0wc-6 0.0930.093 ww 7.137.13 0.000.00 0 -50 -353 0 0 0 0 0GG1D-c2ov1D-c2ov 0.3000.300 ww 23.0123.01 47.1347.13 32 0 736 1508 0 0 0 0DD11D011D00.3900.390 ww 29.9129.91 7.257.25 18 18 523 127 0 0 0 0 CC 16B-38ad16B-38ad 0.0260.026 --1.991.99 1.091.09 0 0 0 0 0 0 0 0FF19A-38cvtp19A-38cvtp 0.0290.029 --1.911.91 0.360.36 602 602 1151 219 36 36 69 13 6 c) AED excursion 266 -1 Envelope loss/gain 4592 2347 69 12 12 a)Infiltration 871 83 0 0 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 900 0 Subtotal (lines 6 to 13)5462 3329 69 12 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution244725461614Subtotal7910358313018 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 7910 3583 130 18 Air required (cfm)Air required (cfm)280 242 5 1 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-16 10:57:07Right-Suite® Universal 2021 21.0.10 RSU28163 Page 4...s\Dougs Const. Repair\Dan Highland\Highland.rup Calc = MJ8 Front Door faces: W HighlandJob:Right-J® Worksheet 01/15/2022Date:Entire House Gene MillerBy:266 MowhawkPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Master Bath 2 Exposed wall 30.3 ft 5.5 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft13.0x13.5 ft8.8x5.5 5 Room area 175.5 ft²48.1 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12E-0sw12E-0sw 0.0680.068 nn 5.225.22 0.650.65 122 122 634 78 50 50 258 32.WW 12E-0sw12E-0sw 0.0680.068 ee 5.225.22 0.650.65 117 93 485 60 0 0 0 0.GG 1D-c2ov1D-c2ov 0.3000.300 ee 23.0123.01 47.1347.13 24 0 552 1131 0 0 0 0 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 11 WW 15B13-0wc-615B13-0wc-6 0.0930.093 ee 4.804.80 0.060.06 0 0 0 0 0 0 0 0 GG 1D-c2ov1D-c2ov 0.3000.300 ee 23.0123.01 47.1347.13 0 0 0 0 0 0 0 0 WW 12E-0sw12E-0sw 0.0680.068 ss 5.225.22 0.650.65 34 34 176 22 0 0 0 0WW15B13-0wc-615B13-0wc-6 0.0930.093 ss 4.924.92 0.070.07 0 0 0 0 0 0 0 0 WW 12E-0sw12E-0sw 0.0680.068 ww 5.225.22 0.650.65 0 0 0 0 0 0 0 0GG1D-c2ov1D-c2ov 0.3000.300 ww 23.0123.01 47.1347.13 0 0 0 0 0 0 0 0 WW 15B13-0wc-615B13-0wc-6 0.0930.093 ww 7.137.13 0.000.00 0 0 0 0 0 0 0 0GG1D-c2ov1D-c2ov 0.3000.300 ww 23.0123.01 47.1347.13 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 CC 16B-38ad16B-38ad 0.0260.026 --1.991.99 1.091.09 176 176 350 192 48 48 96 53FF19A-38cvtp19A-38cvtp 0.0290.029 --1.911.91 0.360.36 0 0 0 0 0 0 0 0 6 c) AED excursion -90 -8 Envelope loss/gain 2197 1393 354 77 12 a)Infiltration 627 60 114 11 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 2 460 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2824 1913 468 88 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution10513714Subtotal2834191848195 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2834 1918 481 95 Air required (cfm)Air required (cfm)100 130 17 6 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-16 10:57:07Right-Suite® Universal 2021 21.0.10 RSU28163 Page 5...s\Dougs Const. Repair\Dan Highland\Highland.rup Calc = MJ8 Front Door faces: W HighlandJob:Right-J® Worksheet 01/15/2022Date:Entire House Gene MillerBy:266 MowhawkPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Room8 Bedroom 2 2 Exposed wall 0 ft 26.0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft4.3x5.5 ft13.0x13.0 5 Room area 23.4 ft²169.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12E-0sw12E-0sw 0.0680.068 nn 5.225.22 0.650.65 0 0 0 0 117 117 610 76.WW 12E-0sw12E-0sw 0.0680.068 ee 5.225.22 0.650.65 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.3000.300 ee 23.0123.01 47.1347.13 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 11 WW 15B13-0wc-615B13-0wc-6 0.0930.093 ee 4.804.80 0.060.06 0 0 0 0 0 0 0 0 GG 1D-c2ov1D-c2ov 0.3000.300 ee 23.0123.01 47.1347.13 0 0 0 0 0 0 0 0 WW 12E-0sw12E-0sw 0.0680.068 ss 5.225.22 0.650.65 0 0 0 0 0 0 0 0WW15B13-0wc-615B13-0wc-6 0.0930.093 ss 4.924.92 0.070.07 0 0 0 0 0 0 0 0 WW 12E-0sw12E-0sw 0.0680.068 ww 5.225.22 0.650.65 0 0 0 0 117 101 527 65GG1D-c2ov1D-c2ov 0.3000.300 ww 23.0123.01 47.1347.13 0 0 0 0 16 0 368 754 WW 15B13-0wc-615B13-0wc-6 0.0930.093 ww 7.137.13 0.000.00 0 0 0 0 0 0 0 0GG1D-c2ov1D-c2ov 0.3000.300 ww 23.0123.01 47.1347.13 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 CC 16B-38ad16B-38ad 0.0260.026 --1.991.99 1.091.09 23 23 47 26 169 169 337 185FF19A-38cvtp19A-38cvtp 0.0290.029 --1.911.91 0.360.36 0 0 0 0 0 0 0 0 6 c) AED excursion -2 147 Envelope loss/gain 47 24 1842 1226 12 a)Infiltration 0 0 539 51 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 1 230 Appliances/other 0 0 Subtotal (lines 6 to 13)47 24 2381 1508 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution-47 -24 10 514Subtotal0023911513 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 0 0 2391 1513 Air required (cfm)Air required (cfm)0 0 85 102 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-16 10:57:07Right-Suite® Universal 2021 21.0.10 RSU28163 Page 6...s\Dougs Const. Repair\Dan Highland\Highland.rup Calc = MJ8 Front Door faces: W HighlandJob:Right-J® Worksheet 01/15/2022Date:Entire House Gene MillerBy:266 MowhawkPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Kit/Din/Great Rm 2 Exposed wall 102.3 ft3Room height 9.0 heat/coolft 4 Room dimensions ft37.0x28.3 5 Room area 1045.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12E-0sw 0.068 n 5.22 0.65 0 0 0 0.W 12E-0sw 0.068 e 5.22 0.65 333 260 1353 168.G 1D-c2ov 0.300 e 23.01 47.13 56 0 1289 2639 .D 11D0 0.390 e 29.91 7.25 18 18 523 127 11 W 15B13-0wc-6 0.093 e 4.80 0.06 0 0 0 0 G 1D-c2ov 0.300 e 23.01 47.13 0 0 0 0 W 12E-0sw 0.068 s 5.22 0.65 254 254 1326 164W15B13-0wc-6 0.093 s 4.92 0.07 0 0 0 0 W 12E-0sw 0.068 w 5.22 0.65 333 333 1737 215G1D-c2ov 0.300 w 23.01 47.13 0 0 0 0 W 15B13-0wc-6 0.093 w 7.13 0.00 0 0 0 0G1D-c2ov 0.300 w 23.01 47.13 0 0 0 0D11D00.390 w 29.91 7.25 0 0 0 0 C 16B-38ad 0.026 -1.99 1.09 1045 1045 2084 1144F19A-38cvtp 0.029 -1.91 0.36 0 0 0 0 6 c) AED excursion -441 Envelope loss/gain 8313 4016 12 a)Infiltration 2120 202 b)Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 2900 Subtotal (lines 6 to 13)10433 7118 Less external load 0 0 Less transfer 0 0Redistribution13714Subtotal104467125 15 Duct loads -0%0%0 0 Total room load 10446 7125 Air required (cfm)370 481 Job #: Highland Performed by Gene Miller for: Dougs Construction Repair 418 N 4014 E Suite #4 Rigby, Id 83442 Phone: 208-356-9331 Mechanical Compliance Solutions 4181 Aschli lane Idaho Falls, ID 83406 Phone: 208-881-3243 gene.mechcompliancesolutions@gmail.com Scale: 1 : 74 Page 1 Ri ght-Suite® Universal 2021 21.0.10 RSU28163 2022-Jan-16 10:57:48 ...Repair\Dan Highland\Highland.rup N Basement Storage Utility Bedroom 3Bedroom 4 Living Rm B Bath5 cfm 110 cfm 129 cfm 140 cfm 140 cfm 6 " 8 " 6 " 6 " 6 " 6 "8 " 6 " 6 " 8 " 20 x 824 x 8 6 " 6 " 6 " 6 " 16 x 8 12 x 8 16 x 8 32 x 85-14x3.25 Job #: Highland Performed by Gene Miller for: Dougs Construction Repair 418 N 4014 E Suite #4 Rigby, Id 83442 Phone: 208-356-9331 Mechanical Compliance Solutions 4181 Aschli lane Idaho Falls, ID 83406 Phone: 208-881-3243 gene.mechcompliancesolutions@gmail.com Scale: 1 : 74 Page 2 Right-Suite® Universal 2021 21.0.10 RSU28163 2022-Jan-16 10:57:49 ...Repair\Dan Highland\Highland.rup N Main Master Bath Room8 Bedroom 2 Kit/Din/Great Rm 1170 cfm 96 cfm 96 cfm 96 cfm 96 cfm 96 cfm 17 cfm 130 cfm 51 cfm 51 cfm 2022-Jan-16 10:57:08 Right-Suite® Universal 2021 21.0.10 RSU28163 Page 1 ...s\Dougs Const. Repair\Dan Highland\Highland.rup Calc = MJ8 Front Door faces: W HighlandJob:Duct System Summary 01/15/2022Date:Entire House Gene MillerBy: 266 MowhawkPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Dougs Construction RepairFor: 418 N 4014 E Suite #4, Rigby, Id 83442 Phone: 208-356-9331 CoolingHeating External static pressure in H2O0.90in H2O0.90 Pressure losses in H2O0in H2O0 Available static pressure in H2O0.90in H2O0.90 Supply / return available pressure 0.576 / 0.324 in H2O in H2O0.576 / 0.324 Lowest friction rate in/100ft0.188in/100ft0.188 Actual air flow cfm1170cfm1070 Total effective length (TEL)ft478 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st2B220.027.5VlFx0x06.00.23315130hB Bath st2B205.032.0VlFx0x06.00.243617481hBath st2B205.041.8VlFx0x06.00.2335142756cBedroom 2 st2B240.040.0VlFx0x06.00.2065142756cBedroom 2-A st2B260.045.5VlFx0x08.00.188971293628hBedroom 3 st2B210.040.8VlFx0x06.00.230110841635cBedroom 4 st1165.024.3VlFx0x06.00.30496741425cKit/Din/Great Rm st2A175.020.8VlFx0x06.00.29496741425cKit/Din/Great Rm-A st1A195.016.8VlFx0x06.00.27296741425cKit/Din/Great Rm-B st2A165.022.0VlFx0x06.00.30896741425cKit/Din/Great Rm-C st2A155.027.5VlFx0x06.00.31596741425cKit/Din/Great Rm-D st2135.016.8VlFx0x06.00.3791211403955hLiving Rm st1A185.032.0VlFx0x08.00.2651211403955hLiving Rm-A st2B250.047.0VlFx0x08.00.1941301001918cMaster Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st1 Peak AVF 288 313 0.265 282 7.3 20x8 ShtMetl st1A Peak AVF 214 217 0.265 244 7.3 16x8 ShtMetl st1 st2A Peak AVF 642 736 0.188 828 10.8 16x8 ShtMetl st2 st2B Peak AVF 419 447 0.188 671 9.0 12x8 ShtMetl st2A st2 Peak AVF 782 857 0.188 642 11.3 24x8 ShtMetl 2022-Jan-16 10:57:08 Right-Suite® Universal 2021 21.0.10 RSU28163 Page 2 ...s\Dougs Const. Repair\Dan Highland\Highland.rup Calc = MJ8 Front Door faces: W Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb1 0x 10700 1170 172.3 0.188 741 12.8 5-3.25x14 5-10x46 SJSp rt1 Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 1070 1170 0.188 658 12.8 32x8 ShtMetl