LOAD SHORT FORM - 21-01027 - 1139 Greenside Loop - New SFR
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:45 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 1 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Web...Job:Load Short Form 03-06-2020Date:Entire House Claudia MartinezBy: Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com Project Information T. Webb Construction-Webb ResidenceFor: Design Information InfiltrationClgHtg SimplifiedMethod89-6Outside db (°F) Semi-tightConstruction quality7570Inside db (°F) 0Fireplaces1476Design TD (°F) H-Daily range 5030Inside humidity (%) -3135Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Day & Night Make Day & Night Trade DAY & NIGHT Trade 13 SEER N SERIES R410A AC Model N9MSN0801716A Cond N4A330*KN AHRI ref 4705249 Coil END4X36L17A1++TDR AHRI ref 9390974 Efficiency 96 AFUE Efficiency 11.0 EER, 13 SEER Heating input Btuh80000 Sensible cooling Btuh24769 Heating output Btuh63180 Latent cooling Btuh0 Temperature rise °F63 Total cooling Btuh24769 Actual air flow cfm1090 Actual air flow cfm1270 Air flow factor cfm/Btuh0.028 Air flow factor cfm/Btuh0.062 Static pressure in H2O0.90 Static pressure in H2O0.90 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Basement Zone 2544 16448 6105 461 378 Main Zone 2549 22401 16148 629 1000 Entire House 5092 38849 20515 1090 1270 Other equip loads 8440 1555 Equip. @ 0.94 RSM 20745 Latent cooling 0 TOTALS 5092 47289 20745 1090 1270 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:45 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 2 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Web...Job:Load Short Form 03-06-2020Date:Basement Zone Claudia MartinezBy: Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com Project Information T. Webb Construction-Webb ResidenceFor: Design Information InfiltrationClgHtg SimplifiedMethod89-6Outside db (°F) Semi-tightConstruction quality7570Inside db (°F) 0Fireplaces1476Design TD (°F) H-Daily range 5030Inside humidity (%) -3135Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref n/a Coil n/a AHRI ref n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling Btuh0 Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0 Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0 Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Utilty 209 0 0 0 0 Mechanical 81 0 0 0 0 Bed. 4 205 1680 33 47 2 Bed 3 258 2769 874 78 54 Family Rm 1226 7324 2570 205 159 Laundry 64 107 479 3 30 Bath 1 108 1067 25 30 2 Bed 5 193 1628 1059 46 66 Bed 6 199 1873 1065 53 66 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:45 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 3 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E Basement Zone 2544 16448 6105 461 378 Other equip loads 0 0 Equip. @ 0.94 RSM 5738 Latent cooling 0 TOTALS 2544 16448 5738 461 378 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:45 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 4 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Web...Job:Load Short Form 03-06-2020Date:Main Zone Claudia MartinezBy: Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com Project Information T. Webb Construction-Webb ResidenceFor: Design Information InfiltrationClgHtg SimplifiedMethod89-6Outside db (°F) Semi-tightConstruction quality7570Inside db (°F) 0Fireplaces1476Design TD (°F) H-Daily range 5030Inside humidity (%) -3135Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref n/a Coil n/a AHRI ref n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling Btuh0 Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0 Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0 Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Laundry 2 108 1717 844 48 52 Office 176 2853 1973 80 122 Kitch-Dinn 509 3512 3948 99 244 Great-Entry 837 4463 4040 125 250 Master 263 3224 2844 90 176 Master Bath 169 1017 196 29 12 Master Closet 77 690 333 19 21 Bed. 2 205 2993 1613 84 100 Bath 2 41 63 32 2 2 1/2 Bath 30 258 41 7 3 Mudd 60 1612 285 45 18 Pantry 74 0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:45 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 5 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E Main Zone 2549 22401 16148 629 1000 Other equip loads 0 0 Equip. @ 0.94 RSM 15179 Latent cooling 761 TOTALS 2549 22401 15940 629 1000 2020-Mar-13 12:28:45 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 1 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Web...Job:Building Analysis 03-06-2020Date: Entire House Claudia MartinezBy: Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com Project Information T. Webb Construction-Webb ResidenceFor: Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-31.535.2Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F) SimplifiedMethod)H(34-Daily range (°F) Semi-tightConstruction quality60-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Doors Ceilings Floors Infiltration Ventilation % of loadBtuhBtuh/ft²Component 33.1156614.2Walls 15.6735924.3Glazing 2.6124529.6Doors 8.238861.5Ceilings 9.142851.71.7Floors 13.664142.7Infiltration 00Ducts 00Piping 00Humidification 17.88440Ventilation 0Adjustments 100.047289Total Cooling Walls Glazing Other Ceilings Infiltration Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 3.78220.2Walls 45.41001033.1Glazing 1.43037.2Doors 9.721470.8Ceilings 000Floors 2.86220.3Infiltration 00Ducts 7.01555Ventilation 30.06610Internal gains 00Blower 0Adjustments 100.022069Total Latent Cooling Load = 0 Btuh Overall U-value = 0.045 Btuh/ft²-°F Data entries checked. 2020-Mar-13 12:28:45 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 2 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Web...Job:Building Analysis 03-06-2020Date: Basement Zone Claudia MartinezBy: Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com Project Information T. Webb Construction-Webb ResidenceFor: Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-31.535.2Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F) SimplifiedMethod)H(34-Daily range (°F) Semi-tightConstruction quality60-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Other Floors Infiltration % of loadBtuhBtuh/ft²Component 49.180813.8Walls 14.8243224.3Glazing 000Doors 0.1121.5Ceilings 25.942531.71.7Floors 10.216702.7Infiltration 00Ducts 00Piping 00Humidification 00Ventilation 0Adjustments 100.016448Total Cooling Other Glazing Infiltration Internal Gains % of loadBtuhBtuh/ft²Component 1.5940.0Walls 72.8444244.4Glazing 000Doors 0.170.8Ceilings 000Floors 2.71620.3Infiltration 00Ducts 00Ventilation 22.91400Internal gains 00Blower 0Adjustments 100.06105Total Latent Cooling Load = 0 Btuh Overall U-value = 0.038 Btuh/ft²-°F WARNING: window to floor area ratio = 3.9% - less than 5%. 2020-Mar-13 12:28:45 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 3 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Web...Job:Building Analysis 03-06-2020Date: Main Zone Claudia MartinezBy: Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com Project Information T. Webb Construction-Webb ResidenceFor: Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-31.535.2Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F) SimplifiedMethod)H(34-Daily range (°F) Semi-tightConstruction quality60-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Doors Ceilings Other Infiltration % of loadBtuhBtuh/ft²Component 33.875804.9Walls 22.0492724.3Glazing 5.6124529.6Doors 17.338741.5Ceilings 0.1311.71.7Floors 21.247442.7Infiltration 00Ducts 00Piping 00Humidification 00Ventilation 0Adjustments 100.022401Total Cooling Walls Glazing Other Ceilings Infiltration Internal Gains % of loadBtuhBtuh/ft²Component 4.57280.5Walls 45.2730636.1Glazing 1.93037.2Doors 13.321410.8Ceilings 000Floors 2.84600.3Infiltration 00Ducts 00Ventilation 32.35210Internal gains 00Blower 0Adjustments 100.016148Total Latent Cooling Load = 761 Btuh Overall U-value = 0.053 Btuh/ft²-°F Data entries checked. 2020-Mar-13 12:28:45 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 1 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Web...Job:Component Constructions 03-06-2020Date:Entire House Claudia MartinezBy: Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com Project Information T. Webb Construction-Webb ResidenceFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-31.535.2Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F) SimplifiedMethod)H(34-Daily range (°F) Semi-tightConstruction quality60-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 1920.4719944.9421.00.065404n 2170.4722564.9421.00.065457e 1900.4719764.9421.00.065400s 1300.4713554.9421.00.065274w 7280.4775804.9421.00.0651534all 15B19-0wc-6: Bg wall, light dry soil, 2"x4" wood int frm, concrete wall, r-19 cav ins, 8" thk, 1/2" gypsum board int fnsh 270.0520703.8219.00.043542n 290.0522333.8219.00.043585e 200.0418603.7019.00.043502s 180.0419183.6519.00.043525w 940.0480813.7519.00.0432155all Partitions (none) Windows 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; 6.67 ft head ht 32110.674024.300.32030n 208034.4146924.300.32060e 34018.943824.300.32018s 75518.997324.300.32040s 322734.4228024.300.32094w 206534.4145924.300.32060w 878829.0735924.300.320303all Doors 11D0: Door, wd sc type 3037.22124529.600.39042e Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 21470.8438861.5250.00.0202557 Floors 21A-28v: Bg floor, light dry soil, 6.5' depth, vinyl flr fnsh 00.0222544 0042531.67 00311.6700.02219 0042851.6700.0222563all 2020-Mar-13 12:28:45 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 2 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E 2020-Mar-13 12:28:45 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 3 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Web...Job:Component Constructions 03-06-2020Date:Basement Zone Claudia MartinezBy: Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com Project Information T. Webb Construction-Webb ResidenceFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-31.535.2Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F) SimplifiedMethod)H(34-Daily range (°F) Semi-tightConstruction quality60-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 15B19-0wc-6: Bg wall, light dry soil, 2"x4" wood int frm, concrete wall, r-19 cav ins, 8" thk, 1/2" gypsum board int fnsh 270.0520703.8219.00.043542n 290.0522333.8219.00.043585e 200.0418603.7019.00.043502s 180.0419183.6519.00.043525w 940.0480813.7519.00.0432155all Partitions (none) Windows 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; 6.67 ft head ht 75518.997324.300.32040s 206534.4145924.300.32060w 282128.2243224.300.320100all Doors (none) Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 70.84121.5250.00.0208 Floors 21A-28v: Bg floor, light dry soil, 6.5' depth, vinyl flr fnsh 00.0222544 0042531.67 2020-Mar-13 12:28:45 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 4 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Web...Job:Component Constructions 03-06-2020Date:Main Zone Claudia MartinezBy: Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com Project Information T. Webb Construction-Webb ResidenceFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-31.535.2Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F) SimplifiedMethod)H(34-Daily range (°F) Semi-tightConstruction quality60-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 1920.4719944.9421.00.065404n 2170.4722564.9421.00.065457e 1900.4719764.9421.00.065400s 1300.4713554.9421.00.065274w 7280.4775804.9421.00.0651534all Partitions (none) Windows 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; 6.67 ft head ht 32110.674024.300.32030n 208034.4146924.300.32060e 34018.943824.300.32018s 322734.4228024.300.32094w 596829.5492724.300.320203all Doors 11D0: Door, wd sc type 3037.22124529.600.39042e Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 21410.8438741.5250.00.0202549 Floors 21A-28v: Bg floor, light dry soil, 6.5' depth, vinyl flr fnsh 00.02219 00311.67 2020-Mar-13 12:28:45 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 1 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Web...Job:AED Assessment 03-06-2020Date: Entire House Claudia MartinezBy: Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com Project Information T. Webb Construction-Webb ResidenceFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-31.535.2Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F) )H(34-Daily range (°F) 60-Wet bulb (°F) 7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limit Gla z i n g l o a d ( B t u h ) Hour of Day 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 45.1%. House does not have adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 1221 Btuh (PFG - 1.3*AFG) 2020-Mar-13 12:28:45 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 2 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Web...Job:AED Assessment 03-06-2020Date: Basement Zone Claudia MartinezBy: Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com Project Information T. Webb Construction-Webb ResidenceFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-31.535.2Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F) )H(34-Daily range (°F) 60-Wet bulb (°F) 7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limit Gla z i n g l o a d ( B t u h ) Hour of Day 0 500 1,000 1,500 2,000 2,500 3,000 3,500 4,000 4,500 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 59.4%. Zone does not have adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 1621 Btuh (PFG - ALP) 2020-Mar-13 12:28:45 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 3 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Web...Job:AED Assessment 03-06-2020Date: Main Zone Claudia MartinezBy: Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com Project Information T. Webb Construction-Webb ResidenceFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-31.535.2Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F) )H(34-Daily range (°F) 60-Wet bulb (°F) 7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limit Gla z i n g l o a d ( B t u h ) Hour of Day 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 37.6%. Zone does not have adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 1338 Btuh (PFG - ALP) Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:45Right-Suite® Universal 2019 19.0.15 RSU20783 Page 1...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J8® Form J1 03-06-2020Date:Entire House Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Name of Room Entire House Basement Zone 2 Running Feet of Exposed Wall 466.0 ft 250.5 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.8 ft²10911.0ft 9.0 ft²5545.4ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)ft²5092.3 ft²2543.8 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²5092.3°0 ft²2543.8° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 4.944.94 0.470.47 434 1994 192 0 0 0 .GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 24.3224.32 10.5610.56 30 740 321 0 0 0 .WallWall 15B19-0wc-615B19-0wc-6 nn 3.823.82 0.050.05 542 2070 27 542 2070 27 .WallWall 12F-0sw12F-0sw ee 4.944.94 0.470.47 559 2256 217 0 0 011GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.3224.32 34.4234.42 60 1469 2080 0 0 0 DoorDoor 11D011D0 ee 29.6429.64 7.217.21 42 1245 303 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ee 3.823.82 0.050.05 585 2233 29 585 2233 29 WallWall 12F-0sw12F-0sw ss 4.944.94 0.470.47 418 1976 190 0 0 0 GlazGlaz 2 glazing, clr low-e s2 glazing, clr low-e s 24.3224.32 18.8818.88 18 438 340 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ss 3.703.70 0.040.04 542 1860 20 542 1860 20 GlazGlaz 2 glazing, clr low-e s2 glazing, clr low-e s 24.3224.32 18.8818.88 40 973 755 40 973 755 WallWall 12F-0sw12F-0sw ww 4.944.94 0.470.47 368 1355 130 0 0 0 GlazGlaz 2 glazing, clr low-e w2 glazing, clr low-e w 24.3224.32 34.4234.42 94 2280 3227 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ww 3.653.65 0.040.04 585 1918 18 585 1918 18GlazGlaz2 glazing, clr low-e w2 glazing, clr low-e w 24.3224.32 34.4234.42 60 1459 2065 60 1459 2065 CeilCeil 16B-50ad16B-50ad --1.521.52 0.840.84 2557 3886 2147 8 12 7 FlorFlor 21A-28v21A-28v --1.671.67 0.000.00 2544 4253 0 2544 4253 0 FlorFlor 21A-28v21A-28v --1.671.67 0.000.00 19 31 0 0 0 0 Infiltration Heating Load (Btuh)0.190.19 6414 1670 Effect WAR WAR 12 Sensible Load (Btuh)ACH 1.00 622 1.00 162 0.100.10 Latent Load (Btuh)-864 -225 Internal a Occupants at 230 and 200 Btuh 7 1610 1400 0 0 0 b Scenario number 4800 1400 13 c Default Adjustments d Custom Appliances 200 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 38849 20515 536 16448 6105 -225 Duct EHLF & ESGF 00 00 0 0 0 0 15 Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 120120 E CfmE Cfm 120120 8440 1555 -2161 0 0 0 17 Winter Humidification Load Gal/Day 00 0 0 18 Piping Load 0 0 19 Blower Heat 0 0 20 AED Excursion & Latent Moisture Migration Load 1221 1621 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 47289 22069 0 16448 6105 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:45Right-Suite® Universal 2019 19.0.15 RSU20783 Page 2...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J8® Form J1 03-06-2020Date:Entire House Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Name of Room Main Zone 2 Running Feet of Exposed Wall 215.5 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.7 ft²5371.7ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)ft²2548.5 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²2548.5° Type of Exposure Const., Number Panel Faces HTM Area or Length Btuh Area or Length Btuh Htg.Clg.Heating S-Clg L-Clg Heating S-Clg L-Clg 6 Wall 12F-0sw n 4.94 0.47 434 1994 192 .Glaz 2 glazing, clr low-e n 24.32 10.56 30 740 321 .Wall 15B19-0wc-6 n 3.82 0.05 0 0 0 .Wall 12F-0sw e 4.94 0.47 559 2256 21711Glaz2 glazing, clr low-e e 24.32 34.42 60 1469 2080 Door 11D0 e 29.64 7.21 42 1245 303 Wall 15B19-0wc-6 e 3.82 0.05 0 0 0 Wall 12F-0sw s 4.94 0.47 418 1976 190 Glaz 2 glazing, clr low-e s 24.32 18.88 18 438 340 Wall 15B19-0wc-6 s 3.70 0.04 0 0 0 Glaz 2 glazing, clr low-e s 24.32 18.88 0 0 0 Wall 12F-0sw w 4.94 0.47 368 1355 130 Glaz 2 glazing, clr low-e w 24.32 34.42 94 2280 3227 Wall 15B19-0wc-6 w 3.65 0.04 0 0 0Glaz2 glazing, clr low-e w 24.32 34.42 0 0 0 Ceil 16B-50ad -1.52 0.84 2549 3874 2141 Flor 21A-28v -1.67 0.00 0 0 0 Flor 21A-28v -1.67 0.00 19 31 0 Infiltration Heating Load (Btuh)0.19 4744 Effect WAR 12 Sensible Load (Btuh)ACH 1.00 460 0.10 Latent Load (Btuh)-639 Internal a Occupants at 230 and 200 Btuh 7 1610 1400 b Scenario number 3400 13 c Default Adjustments d Custom Appliances 200 0 e Plants 0 14 Subtotals Sum lines 6 through 12 22401 16148 761 Duct EHLF & ESGF 0 0 0 0 15 Loads ELG 0 Vent Cfm16Ventilation Loads 120 E Cfm 120 0 0 0 17 Winter Humidification Load Gal/Day 0 0 18 Piping Load 0 19 Blower Heat 0 20 AED Excursion & Latent Moisture Migration Load 1338 21 Total Load Sum lines 13 through 19 22401 16148 761 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:45Right-Suite® Universal 2019 19.0.15 RSU20783 Page 3...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J8® Form J1 03-06-2020Date:Basement Zone Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Name of Room Basement Zone Utilty 2 Running Feet of Exposed Wall 250.5 ft 24.3 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²5545.4ft 9.0 ft²562.5ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)ft²2543.8 1.0 x 209.3 ft ft²209.3 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²2543.8°0 ft²209.3° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0 .GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 0.000.00 0.000.00 0 0 0 0 0 0 .WallWall 15B19-0wc-615B19-0wc-6 nn 3.823.82 0.050.05 542 2070 27 54 206 3 .WallWall 12F-0sw12F-0sw ee 0.000.00 0.000.00 0 0 0 0 0 011GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 0.000.00 0.000.00 0 0 0 0 0 0 DoorDoor 11D011D0 ee 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ee 3.823.82 0.050.05 585 2233 29 164 627 8 WallWall 12F-0sw12F-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e s2 glazing, clr low-e s 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ss 3.703.70 0.040.04 542 1860 20 0 0 0 GlazGlaz 2 glazing, clr low-e s2 glazing, clr low-e s 24.3224.32 18.8818.88 40 973 755 0 0 0 WallWall 12F-0sw12F-0sw ww 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e w2 glazing, clr low-e w 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ww 3.653.65 0.040.04 585 1918 18 0 0 0GlazGlaz2 glazing, clr low-e w2 glazing, clr low-e w 24.3224.32 34.4234.42 60 1459 2065 0 0 0 CeilCeil 16B-50ad16B-50ad --1.521.52 0.840.84 8 12 7 5 7 4 FlorFlor 21A-28v21A-28v --1.671.67 0.000.00 2544 4253 0 209 350 0 FlorFlor 21A-28v21A-28v --0.000.00 0.000.00 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.210.21 1670 162 Effect WAR WAR 12 Sensible Load (Btuh)ACH 1.00 162 0.10 16 0.110.11 Latent Load (Btuh)-225 Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 1400 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 16448 6105 -225 0 0 Duct EHLF & ESGF 00 00 0 0 0 0 15 Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 6060 E CfmE Cfm 6060 0 0 0 17 Winter Humidification Load Gal/Day 00 0 18 Piping Load 0 19 Blower Heat 0 20 AED Excursion & Latent Moisture Migration Load 1621 -1 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 16448 6105 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:45Right-Suite® Universal 2019 19.0.15 RSU20783 Page 4...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J8® Form J1 03-06-2020Date:Basement Zone Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Name of Room Mechanical Bed. 4 2 Running Feet of Exposed Wall 6.3 ft 28.8 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²346.5ft 9.0 ft²517.5ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)6.3 x 13.0 ft ft²81.3 13.0 x 15.8 ft ft²204.8 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²81.3°0 ft²204.8° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0 .GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 0.000.00 0.000.00 0 0 0 0 0 0 .WallWall 15B19-0wc-615B19-0wc-6 nn 3.823.82 0.050.05 0 0 0 142 541 7 .WallWall 12F-0sw12F-0sw ee 0.000.00 0.000.00 0 0 0 0 0 011GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 0.000.00 0.000.00 0 0 0 0 0 0 DoorDoor 11D011D0 ee 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ee 3.823.82 0.050.05 56 215 3 117 447 6 WallWall 12F-0sw12F-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e s2 glazing, clr low-e s 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ss 3.703.70 0.040.04 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e s2 glazing, clr low-e s 24.3224.32 18.8818.88 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ww 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e w2 glazing, clr low-e w 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ww 3.653.65 0.040.04 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e w2 glazing, clr low-e w 24.3224.32 34.4234.42 0 0 0 0 0 0 CeilCeil 16B-50ad16B-50ad --1.521.52 0.840.84 0 0 0 0 0 0 FlorFlor 21A-28v21A-28v --1.671.67 0.000.00 81 136 0 205 342 0 FlorFlor 21A-28v21A-28v --0.000.00 0.000.00 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.210.21 42 192 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0.02 4 0.11 19 0.110.11 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 0 0 1680 33 Duct EHLF & ESGF 00 00 0 0 0 0 15 Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 6060 E CfmE Cfm 6060 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 0 -1 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 0 0 1680 33 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:45Right-Suite® Universal 2019 19.0.15 RSU20783 Page 5...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J8® Form J1 03-06-2020Date:Basement Zone Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Name of Room Bed 3 Family Rm 2 Running Feet of Exposed Wall 36.5 ft 82.5 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²579.0ft 9.0 ft²1834.5ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)1.0 x 257.7 ft ft²257.7 1.0 x 1226.2 ft ft²1226.2 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²257.7°0 ft²1226.2° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0 .GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 0.000.00 0.000.00 0 0 0 0 0 0 .WallWall 15B19-0wc-615B19-0wc-6 nn 3.823.82 0.050.05 34 129 2 108 412 5 .WallWall 12F-0sw12F-0sw ee 0.000.00 0.000.00 0 0 0 0 0 011GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 0.000.00 0.000.00 0 0 0 0 0 0 DoorDoor 11D011D0 ee 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ee 3.823.82 0.050.05 126 481 6 0 0 0 WallWall 12F-0sw12F-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e s2 glazing, clr low-e s 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ss 3.703.70 0.040.04 169 539 5 302 1046 11 GlazGlaz 2 glazing, clr low-e s2 glazing, clr low-e s 24.3224.32 18.8818.88 20 486 378 20 486 378 WallWall 12F-0sw12F-0sw ww 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e w2 glazing, clr low-e w 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ww 3.653.65 0.040.04 0 0 0 333 1166 13GlazGlaz2 glazing, clr low-e w2 glazing, clr low-e w 24.3224.32 34.4234.42 0 0 0 20 486 688 CeilCeil 16B-50ad16B-50ad --1.521.52 0.840.84 0 0 0 0 0 0 FlorFlor 21A-28v21A-28v --1.671.67 0.000.00 258 431 0 1226 2050 0 FlorFlor 21A-28v21A-28v --0.000.00 0.000.00 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.210.21 243 550 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0.15 24 0.33 53 0.110.11 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 900 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 2769 874 7324 2570 Duct EHLF & ESGF 00 00 0 0 0 0 15 Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 6060 E CfmE Cfm 6060 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 450 498 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 2769 874 7324 2570 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:45Right-Suite® Universal 2019 19.0.15 RSU20783 Page 6...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J8® Form J1 03-06-2020Date:Basement Zone Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Name of Room Laundry Bath 1 2 Running Feet of Exposed Wall 0 ft 21.5 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²297.0ft 9.0 ft²387.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)10.3 x 6.3 ft ft²64.1 13.5 x 8.0 ft ft²108.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²64.1°0 ft²108.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0 .GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 0.000.00 0.000.00 0 0 0 0 0 0 .WallWall 15B19-0wc-615B19-0wc-6 nn 3.823.82 0.050.05 0 0 0 72 275 4 .WallWall 12F-0sw12F-0sw ee 0.000.00 0.000.00 0 0 0 0 0 011GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 0.000.00 0.000.00 0 0 0 0 0 0 DoorDoor 11D011D0 ee 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ee 3.823.82 0.050.05 0 0 0 122 464 6 WallWall 12F-0sw12F-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e s2 glazing, clr low-e s 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ss 3.703.70 0.040.04 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e s2 glazing, clr low-e s 24.3224.32 18.8818.88 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ww 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e w2 glazing, clr low-e w 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ww 3.653.65 0.040.04 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e w2 glazing, clr low-e w 24.3224.32 34.4234.42 0 0 0 0 0 0 CeilCeil 16B-50ad16B-50ad --1.521.52 0.840.84 0 0 0 3 5 3 FlorFlor 21A-28v21A-28v --1.671.67 0.000.00 64 107 0 108 181 0 FlorFlor 21A-28v21A-28v --0.000.00 0.000.00 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.210.21 0 143 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0 0 0.09 14 0.110.11 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 500 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 107 479 1067 25 Duct EHLF & ESGF 00 00 0 0 0 0 15 Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 6060 E CfmE Cfm 6060 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -21 -1 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 107 479 1067 25 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:45Right-Suite® Universal 2019 19.0.15 RSU20783 Page 7...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J8® Form J1 03-06-2020Date:Basement Zone Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Name of Room Bed 5 Bed 6 2 Running Feet of Exposed Wall 22.5 ft 28.3 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²513.0ft 9.0 ft²508.5ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)1.0 x 193.4 ft ft²193.4 13.5 x 14.8 ft ft²199.1 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²193.4°0 ft²199.1° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0 .GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 0.000.00 0.000.00 0 0 0 0 0 0 .WallWall 15B19-0wc-615B19-0wc-6 nn 3.823.82 0.050.05 0 0 0 133 507 7 .WallWall 12F-0sw12F-0sw ee 0.000.00 0.000.00 0 0 0 0 0 011GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 0.000.00 0.000.00 0 0 0 0 0 0 DoorDoor 11D011D0 ee 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ee 3.823.82 0.050.05 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e s2 glazing, clr low-e s 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ss 3.703.70 0.040.04 72 275 4 0 0 0 GlazGlaz 2 glazing, clr low-e s2 glazing, clr low-e s 24.3224.32 18.8818.88 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ww 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e w2 glazing, clr low-e w 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ww 3.653.65 0.040.04 131 393 3 122 359 2GlazGlaz2 glazing, clr low-e w2 glazing, clr low-e w 24.3224.32 34.4234.42 20 486 688 20 486 688 CeilCeil 16B-50ad16B-50ad --1.521.52 0.840.84 0 0 0 0 0 0 FlorFlor 21A-28v21A-28v --1.671.67 0.000.00 193 323 0 199 333 0 FlorFlor 21A-28v21A-28v --0.000.00 0.000.00 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.210.21 150 188 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0.09 15 0.11 18 0.110.11 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 1628 1059 1873 1065 Duct EHLF & ESGF 00 00 0 0 0 0 15 Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 6060 E CfmE Cfm 6060 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 350 349 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 1628 1059 1873 1065 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:45Right-Suite® Universal 2019 19.0.15 RSU20783 Page 8...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J8® Form J1 03-06-2020Date:Main Zone Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Name of Room Main Zone Laundry 2 2 Running Feet of Exposed Wall 215.5 ft 20.8 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.7 ft²5371.7ft 8.0 ft²368.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)ft²2548.5 1.0 x 107.5 ft ft²107.5 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²2548.5°0 ft²107.5° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 4.944.94 0.470.47 434 1994 192 62 232 22 .GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 24.3224.32 10.5610.56 30 740 321 15 365 158 .WallWall 15B19-0wc-615B19-0wc-6 nn 0.000.00 0.000.00 0 0 0 0 0 0 .WallWall 12F-0sw12F-0sw ee 4.944.94 0.470.47 559 2256 217 104 514 4911GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.3224.32 34.4234.42 60 1469 2080 0 0 0 DoorDoor 11D011D0 ee 29.6429.64 7.217.21 42 1245 303 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ee 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 4.944.94 0.470.47 418 1976 190 0 0 0 GlazGlaz 2 glazing, clr low-e s2 glazing, clr low-e s 24.3224.32 18.8818.88 18 438 340 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ss 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e s2 glazing, clr low-e s 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ww 4.944.94 0.470.47 368 1355 130 0 0 0 GlazGlaz 2 glazing, clr low-e w2 glazing, clr low-e w 24.3224.32 34.4234.42 94 2280 3227 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ww 0.000.00 0.000.00 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e w2 glazing, clr low-e w 0.000.00 0.000.00 0 0 0 0 0 0 CeilCeil 16B-50ad16B-50ad --1.521.52 0.840.84 2549 3874 2141 108 163 90 FlorFlor 21A-28v21A-28v --0.000.00 0.000.00 0 0 0 0 0 0 FlorFlor 21A-28v21A-28v --1.671.67 0.000.00 19 31 0 0 0 0 Infiltration Heating Load (Btuh)0.180.18 4744 443 Effect WAR WAR 12 Sensible Load (Btuh)ACH 1.00 460 0.09 43 0.100.10 Latent Load (Btuh)-639 Internal a Occupants at 230 and 200 Btuh 7 1610 1400 0 0 0 b Scenario number 3400 500 13 c Default Adjustments d Custom Appliances 200 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 22401 16148 761 1717 844 Duct EHLF & ESGF 00 00 0 0 0 0 15 Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 6060 E CfmE Cfm 6060 0 0 0 17 Winter Humidification Load Gal/Day 00 0 18 Piping Load 0 19 Blower Heat 0 20 AED Excursion & Latent Moisture Migration Load 1338 -19 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 22401 16148 761 1717 844 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:45Right-Suite® Universal 2019 19.0.15 RSU20783 Page 9...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J8® Form J1 03-06-2020Date:Main Zone Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Name of Room Office Kitch-Dinn 2 Running Feet of Exposed Wall 27.8 ft 25.0 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 ft²444.0ft 8.0 ft²631.3ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)1.0 x 176.0 ft ft²176.0 1.0 x 509.1 ft ft²509.1 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²176.0°0 ft²509.1° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 4.944.94 0.470.47 118 507 49 74 366 35 .GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 24.3224.32 10.5610.56 15 375 163 0 0 0 .WallWall 15B19-0wc-615B19-0wc-6 nn 0.000.00 0.000.00 0 0 0 0 0 0 .WallWall 12F-0sw12F-0sw ee 4.944.94 0.470.47 0 0 0 0 0 011GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.3224.32 34.4234.42 0 0 0 0 0 0 DoorDoor 11D011D0 ee 29.6429.64 7.217.21 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ee 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 4.944.94 0.470.47 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e s2 glazing, clr low-e s 24.3224.32 18.8818.88 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ss 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e s2 glazing, clr low-e s 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ww 4.944.94 0.470.47 104 361 35 126 468 45 GlazGlaz 2 glazing, clr low-e w2 glazing, clr low-e w 24.3224.32 34.4234.42 31 750 1061 31 760 1076 WallWall 15B19-0wc-615B19-0wc-6 ww 0.000.00 0.000.00 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e w2 glazing, clr low-e w 0.000.00 0.000.00 0 0 0 0 0 0 CeilCeil 16B-50ad16B-50ad --1.521.52 0.840.84 176 268 148 509 774 428 FlorFlor 21A-28v21A-28v --0.000.00 0.000.00 0 0 0 0 0 0 FlorFlor 21A-28v21A-28v --1.671.67 0.000.00 0 0 0 11 18 0 Infiltration Heating Load (Btuh)0.180.18 592 533 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0.12 57 0.11 52 0.100.10 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 2000 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 2853 1973 3512 3948 Duct EHLF & ESGF 00 00 0 0 0 0 15 Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 6060 E CfmE Cfm 6060 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 460 238 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 2853 1973 3512 3948 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:45Right-Suite® Universal 2019 19.0.15 RSU20783 Page 10...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J8® Form J1 03-06-2020Date:Main Zone Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Name of Room Great-Entry Master 2 Running Feet of Exposed Wall 27.5 ft 32.5 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)10.0 ft²1213.8ft 8.0 ft²520.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)1.0 x 837.4 ft ft²837.4 17.3 x 15.3 ft ft²263.1 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²837.4°0 ft²263.1° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 4.944.94 0.470.47 80 395 38 0 0 0 .GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 24.3224.32 10.5610.56 0 0 0 0 0 0 .WallWall 15B19-0wc-615B19-0wc-6 nn 0.000.00 0.000.00 0 0 0 0 0 0 .WallWall 12F-0sw12F-0sw ee 4.944.94 0.470.47 195 713 69 0 0 011GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.3224.32 34.4234.42 30 719 1018 0 0 0 DoorDoor 11D011D0 ee 29.6429.64 7.217.21 21 622 152 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ee 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 4.944.94 0.470.47 0 0 0 122 543 52 GlazGlaz 2 glazing, clr low-e s2 glazing, clr low-e s 24.3224.32 18.8818.88 0 0 0 12 292 227 WallWall 15B19-0wc-615B19-0wc-6 ss 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e s2 glazing, clr low-e s 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ww 4.944.94 0.470.47 0 0 0 138 525 50 GlazGlaz 2 glazing, clr low-e w2 glazing, clr low-e w 24.3224.32 34.4234.42 0 0 0 32 770 1090 WallWall 15B19-0wc-615B19-0wc-6 ww 0.000.00 0.000.00 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e w2 glazing, clr low-e w 0.000.00 0.000.00 0 0 0 0 0 0 CeilCeil 16B-50ad16B-50ad --1.521.52 0.840.84 837 1273 703 263 400 221 FlorFlor 21A-28v21A-28v --0.000.00 0.000.00 0 0 0 0 0 0 FlorFlor 21A-28v21A-28v --1.671.67 0.000.00 4 7 0 0 0 0 Infiltration Heating Load (Btuh)0.180.18 733 693 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0.15 71 0.15 67 0.100.10 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 5 1150 1000 2 460 400 b Scenario number 900 0 13 c Default Adjustments d Custom Appliances 0 0 200 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 4463 4040 3224 2844 Duct EHLF & ESGF 00 00 0 0 0 0 15 Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 6060 E CfmE Cfm 6060 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -61 477 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 4463 4040 3224 2844 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:45Right-Suite® Universal 2019 19.0.15 RSU20783 Page 11...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J8® Form J1 03-06-2020Date:Main Zone Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Name of Room Master Bath Master Closet 2 Running Feet of Exposed Wall 12.5 ft 7.5 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 ft²416.0ft 8.0 ft²284.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)13.5 x 12.5 ft ft²168.8 10.3 x 7.5 ft ft²76.9 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²168.8°0 ft²76.9° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 4.944.94 0.470.47 0 0 0 0 0 0 .GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 24.3224.32 10.5610.56 0 0 0 0 0 0 .WallWall 15B19-0wc-615B19-0wc-6 nn 0.000.00 0.000.00 0 0 0 0 0 0 .WallWall 12F-0sw12F-0sw ee 4.944.94 0.470.47 0 0 0 0 0 011GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.3224.32 34.4234.42 0 0 0 0 0 0 DoorDoor 11D011D0 ee 29.6429.64 7.217.21 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ee 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 4.944.94 0.470.47 100 494 47 60 267 26 GlazGlaz 2 glazing, clr low-e s2 glazing, clr low-e s 24.3224.32 18.8818.88 0 0 0 6 146 113 WallWall 15B19-0wc-615B19-0wc-6 ss 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e s2 glazing, clr low-e s 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ww 4.944.94 0.470.47 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e w2 glazing, clr low-e w 24.3224.32 34.4234.42 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ww 0.000.00 0.000.00 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e w2 glazing, clr low-e w 0.000.00 0.000.00 0 0 0 0 0 0 CeilCeil 16B-50ad16B-50ad --1.521.52 0.840.84 169 256 142 77 117 65 FlorFlor 21A-28v21A-28v --0.000.00 0.000.00 0 0 0 0 0 0 FlorFlor 21A-28v21A-28v --1.671.67 0.000.00 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.180.18 267 160 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0.06 26 0.03 16 0.100.10 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 1017 196 690 333 Duct EHLF & ESGF 00 00 0 0 0 0 15 Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 6060 E CfmE Cfm 6060 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -19 114 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 1017 196 690 333 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:45Right-Suite® Universal 2019 19.0.15 RSU20783 Page 12...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J8® Form J1 03-06-2020Date:Main Zone Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Name of Room Bed. 2 Bath 2 2 Running Feet of Exposed Wall 34.3 ft 0 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 ft²484.0ft 8.0 ft²208.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)1.0 x 205.0 ft ft²205.0 5.5 x 7.5 ft ft²41.3 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²205.0°0 ft²41.3° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 4.944.94 0.470.47 32 158 15 0 0 0 .GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 24.3224.32 10.5610.56 0 0 0 0 0 0 .WallWall 15B19-0wc-615B19-0wc-6 nn 0.000.00 0.000.00 0 0 0 0 0 0 .WallWall 12F-0sw12F-0sw ee 4.944.94 0.470.47 106 371 36 0 0 011GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.3224.32 34.4234.42 31 750 1061 0 0 0 DoorDoor 11D011D0 ee 29.6429.64 7.217.21 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ee 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 4.944.94 0.470.47 136 672 65 0 0 0 GlazGlaz 2 glazing, clr low-e s2 glazing, clr low-e s 24.3224.32 18.8818.88 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ss 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e s2 glazing, clr low-e s 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ww 4.944.94 0.470.47 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e w2 glazing, clr low-e w 24.3224.32 34.4234.42 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ww 0.000.00 0.000.00 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e w2 glazing, clr low-e w 0.000.00 0.000.00 0 0 0 0 0 0 CeilCeil 16B-50ad16B-50ad --1.521.52 0.840.84 205 312 172 41 63 35 FlorFlor 21A-28v21A-28v --0.000.00 0.000.00 0 0 0 0 0 0 FlorFlor 21A-28v21A-28v --1.671.67 0.000.00 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.180.18 731 0 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0.15 71 0 0 0.100.10 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 2993 1613 63 32 Duct EHLF & ESGF 00 00 0 0 0 0 15 Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 6060 E CfmE Cfm 6060 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 193 -3 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 2993 1613 63 32 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:45Right-Suite® Universal 2019 19.0.15 RSU20783 Page 13...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J8® Form J1 03-06-2020Date:Main Zone Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Name of Room 1/2 Bath Mudd 2 Running Feet of Exposed Wall 3.5 ft 7.0 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 ft²192.0ft 8.0 ft²248.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)3.5 x 8.5 ft ft²29.8 7.0 x 8.5 ft ft²59.5 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²29.8°0 ft²59.5° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 4.944.94 0.470.47 0 0 0 0 0 0 .GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 24.3224.32 10.5610.56 0 0 0 0 0 0 .WallWall 15B19-0wc-615B19-0wc-6 nn 0.000.00 0.000.00 0 0 0 0 0 0 .WallWall 12F-0sw12F-0sw ee 4.944.94 0.470.47 28 138 13 56 173 1711GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.3224.32 34.4234.42 0 0 0 0 0 0 DoorDoor 11D011D0 ee 29.6429.64 7.217.21 0 0 0 21 622 152 WallWall 15B19-0wc-615B19-0wc-6 ee 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 4.944.94 0.470.47 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e s2 glazing, clr low-e s 24.3224.32 18.8818.88 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ss 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e s2 glazing, clr low-e s 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ww 4.944.94 0.470.47 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e w2 glazing, clr low-e w 24.3224.32 34.4234.42 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ww 0.000.00 0.000.00 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e w2 glazing, clr low-e w 0.000.00 0.000.00 0 0 0 0 0 0 CeilCeil 16B-50ad16B-50ad --1.521.52 0.840.84 30 45 25 60 90 50 FlorFlor 21A-28v21A-28v --0.000.00 0.000.00 0 0 0 0 0 0 FlorFlor 21A-28v21A-28v --1.671.67 0.000.00 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.180.18 75 149 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0.02 7 0.03 14 0.100.10 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 258 41 1612 285 Duct EHLF & ESGF 00 00 0 0 0 0 15 Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 6060 E CfmE Cfm 6060 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -4 -21 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 258 41 1612 285 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:45Right-Suite® Universal 2019 19.0.15 RSU20783 Page 14...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J8® Form J1 03-06-2020Date:Main Zone Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Name of Room Pantry 2 Running Feet of Exposed Wall 17.3 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 ft²276.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)8.8 x 8.5 ft ft²74.4 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²74.4° Type of Exposure Const., Number Panel Faces HTM Area or Length Btuh Area or Length Btuh Htg.Clg.Heating S-Clg L-Clg Heating S-Clg L-Clg 6 Wall 12F-0sw n 4.94 0.47 68 336 32 .Glaz 2 glazing, clr low-e n 24.32 10.56 0 0 0 .Wall 15B19-0wc-6 n 0.00 0.00 0 0 0 .Wall 12F-0sw e 4.94 0.47 70 346 3311Glaz2 glazing, clr low-e e 24.32 34.42 0 0 0 Door 11D0 e 29.64 7.21 0 0 0 Wall 15B19-0wc-6 e 0.00 0.00 0 0 0 Wall 12F-0sw s 4.94 0.47 0 0 0 Glaz 2 glazing, clr low-e s 24.32 18.88 0 0 0 Wall 15B19-0wc-6 s 0.00 0.00 0 0 0 Glaz 2 glazing, clr low-e s 0.00 0.00 0 0 0 Wall 12F-0sw w 4.94 0.47 0 0 0 Glaz 2 glazing, clr low-e w 24.32 34.42 0 0 0 Wall 15B19-0wc-6 w 0.00 0.00 0 0 0Glaz2 glazing, clr low-e w 0.00 0.00 0 0 0 Ceil 16B-50ad -1.52 0.84 74 113 62 Flor 21A-28v -0.00 0.00 0 0 0 Flor 21A-28v -1.67 0.00 4 7 0 Infiltration Heating Load (Btuh)0.18 368 Effect WAR 12 Sensible Load (Btuh)ACH 0.08 36 0.10 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 b Scenario number 0 13 c Default Adjustments d Custom Appliances 0 0 e Plants 0 14 Subtotals Sum lines 6 through 12 0 0 Duct EHLF & ESGF 0 0 0 0 15 Loads ELG 0 Vent Cfm16Ventilation Loads 60 E Cfm 60 17 Winter Humidification Load Gal/Day 0 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -15 21 Total Load Sum lines 13 through 19 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:47 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 1 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Web...Job:J1 Form - Worksheet A 03-06-2020Date:Entire House Claudia MartinezBy: Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com Supporting Detail Project Name:03-06-2020T-Webb Construction- Personal Bridgewater Date: Address: Phone:T. Webb Construction-Webb Residence Job ID: Worksheet A Location and Design Conditions Weather Location: Idaho Falls, ID, US 444741 Latitude =Elevation = Indoor Conditions, Heating: 70 °FDB =%50°F75%30 RH =DB =Indoor Conditions, Cooling:RH = Table 1 Conditions 99% DB = -6 °F Hgr/lb-31°F89 Daily Range =Grains Difference =1% DB = Design Temperature Differences °F14°F76 CTD =HTD = Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:47 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 2 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Web...Job:J1 Form - Worksheet A 03-06-2020Date:Basement Zone Claudia MartinezBy: Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com Supporting Detail Project Name:03-06-2020T-Webb Construction- Personal Bridgewater Date: Address: Phone:T. Webb Construction-Webb Residence Job ID: Worksheet A Location and Design Conditions Weather Location: Idaho Falls, ID, US 444741 Latitude =Elevation = Indoor Conditions, Heating: 70 °FDB =%50°F75%30 RH =DB =Indoor Conditions, Cooling:RH = Table 1 Conditions 99% DB = -6 °F Hgr/lb-31°F89 Daily Range =Grains Difference =1% DB = Design Temperature Differences °F14°F76 CTD =HTD = Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:47 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 3 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Web...Job:J1 Form - Worksheet A 03-06-2020Date:Main Zone Claudia MartinezBy: Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com Supporting Detail Project Name:03-06-2020T-Webb Construction- Personal Bridgewater Date: Address: Phone:T. Webb Construction-Webb Residence Job ID: Worksheet A Location and Design Conditions Weather Location: Idaho Falls, ID, US 444741 Latitude =Elevation = Indoor Conditions, Heating: 70 °FDB =%50°F75%30 RH =DB =Indoor Conditions, Cooling:RH = Table 1 Conditions 99% DB = -6 °F Hgr/lb-31°F89 Daily Range =Grains Difference =1% DB = Design Temperature Differences °F14°F76 CTD =HTD = Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:47Right-Suite® Universal 2019 19.0.15 RSU20783 Page 1 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Web...Job:Project Summary 03-06-2020Date:Entire House Claudia MartinezBy: Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com Project Information T. Webb Construction-Webb ResidenceFor: INFORMATION CONTAIN WITHIN THE REPORT IS PER THE RESCHECK COMPLIANCE CERTIFICATE. IF ANY OF THESE VALUES SHOULD CHANGE, THIS REPORT WILL BE NULL AND VOID. Notes: Design Information Idaho Falls, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-6 Outside db °F89Inside db °F70 Inside db °F75 Design TD °F76 Design TD °F14Daily range H Relative humidity %50Moisture difference gr/lb-31 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh38849 Structure Btuh20515 Ducts Btuh0 Ducts Btuh0Central vent (120 cfm) 8440 Btuh Central vent (120 cfm) Btuh1555 Outside air Outside airHumidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh47289 Use manufacturer's data n Rate/swing multiplier 0.94 Infiltration Equipment sensible load Btuh20745 Method Latent Cooling Equipment Load SizingSimplified Construction quality Semi-tight0Fireplaces Structure Btuh536 Ducts Btuh0Central vent (120 cfm) Btuh-2161 CoolingHeating Outside air 50925092Area (ft²)Equipment latent load Btuh0 2883928839Volume (ft³) Air changes/hour 0.100.19 Equipment Total Load (Sen+Lat)Btuh20745 Equiv. AVF (cfm) 4891 Req. total capacity at 1.00 SHR ton1.7 Heating Equipment Summary Cooling Equipment Summary Make Day & Night Make Day & Night Trade DAY & NIGHT Trade 13 SEER N SERIES R410A AC Model N9MSN0801716A Cond N4A330*KN AHRI ref 4705249 Coil END4X36L17A1++TDR AHRI ref 9390974 Efficiency 96 AFUE Efficiency 11.0 EER, 13 SEER Heating input Btuh80000 Sensible cooling Btuh24769 Heating output Btuh63180 Latent cooling Btuh0 Temperature rise °F63 Total cooling Btuh24769 Actual air flow cfm1090 Actual air flow cfm1270 Air flow factor cfm/Btuh0.028 Air flow factor cfm/Btuh0.062 Static pressure in H2O0.90 Static pressure in H2O0.90 Space thermostat Load sensible heat ratio 1.00 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:47Right-Suite® Universal 2019 19.0.15 RSU20783 Page 2 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Web...Job:Project Summary 03-06-2020Date:Basement Zone Claudia MartinezBy: Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com Project Information T. Webb Construction-Webb ResidenceFor: INFORMATION CONTAIN WITHIN THE REPORT IS PER THE RESCHECK COMPLIANCE CERTIFICATE. IF ANY OF THESE VALUES SHOULD CHANGE, THIS REPORT WILL BE NULL AND VOID. Notes: Design Information Idaho Falls, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-6 Outside db °F89Inside db °F70 Inside db °F75 Design TD °F76 Design TD °F14Daily range H Relative humidity %50Moisture difference gr/lb-31 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh16448 Structure Btuh6105 Ducts Btuh0 Ducts Btuh0Central vent (60 cfm) 0 Btuh Central vent (60 cfm) Btuh0 Humidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh16448 Use manufacturer's data n Rate/swing multiplier 0.94 Infiltration Equipment sensible load Btuh5738 Method Latent Cooling Equipment Load SizingSimplified Construction quality Semi-tight0Fireplaces Structure Btuh-225 Ducts Btuh0Central vent (60 cfm) Btuh0 CoolingHeating 25442544Area (ft²)Equipment latent load Btuh0 67766776Volume (ft³) Air changes/hour 0.110.21 Equipment Total Load (Sen+Lat)Btuh5738 Equiv. AVF (cfm) 1324 Req. total capacity at 0.70 SHR ton0.7 Heating Equipment Summary Cooling Equipment Summary Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref n/a Coil n/a AHRI ref n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling Btuh0 Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0 Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0 Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:47Right-Suite® Universal 2019 19.0.15 RSU20783 Page 3 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Web...Job:Project Summary 03-06-2020Date:Main Zone Claudia MartinezBy: Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com Project Information T. Webb Construction-Webb ResidenceFor: INFORMATION CONTAIN WITHIN THE REPORT IS PER THE RESCHECK COMPLIANCE CERTIFICATE. IF ANY OF THESE VALUES SHOULD CHANGE, THIS REPORT WILL BE NULL AND VOID. Notes: Design Information Idaho Falls, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-6 Outside db °F89Inside db °F70 Inside db °F75 Design TD °F76 Design TD °F14Daily range H Relative humidity %50Moisture difference gr/lb-31 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh22401 Structure Btuh16148 Ducts Btuh0 Ducts Btuh0Central vent (60 cfm) 0 Btuh Central vent (60 cfm) Btuh0 Humidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh22401 Use manufacturer's data n Rate/swing multiplier 0.94 Infiltration Equipment sensible load Btuh15179 Method Latent Cooling Equipment Load SizingSimplified Construction quality Semi-tight0Fireplaces Structure Btuh761 Ducts Btuh0Central vent (60 cfm) Btuh0 CoolingHeating 25492549Area (ft²)Equipment latent load Btuh761 2206322063Volume (ft³) Air changes/hour 0.100.18 Equipment Total Load (Sen+Lat)Btuh15940 Equiv. AVF (cfm) 3668 Req. total capacity at 0.70 SHR ton1.8 Heating Equipment Summary Cooling Equipment Summary Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref n/a Coil n/a AHRI ref n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling Btuh0 Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0 Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0 Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:47Right-Suite® Universal 2019 19.0.15 RSU20783 Page 1...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J® Worksheet 03-06-2020Date:Entire House Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Room name Entire House Basement Zone 2 Exposed wall 466.0 ft 250.5 ft 3 Room height 8.8 ft 9.0 ft 4 Room dimensions 5 Room area 5092.3 ft²2543.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.944.94 0.470.47 434 404 1994 192 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.3224.32 10.5610.56 30 0 740 321 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.823.82 0.050.05 542 542 2070 27 542 542 2070 27 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.944.94 0.470.47 559 457 2256 217 0 0 0 011GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.3224.32 34.4234.42 60 0 1469 2080 0 0 0 0 DD 11D011D0 0.3900.390 ee 29.6429.64 7.217.21 42 42 1245 303 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.823.82 0.050.05 585 585 2233 29 585 585 2233 29 WW 12F-0sw12F-0sw 0.0650.065 ss 4.944.94 0.470.47 418 400 1976 190 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.3224.32 18.8818.88 18 0 438 340 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.703.70 0.040.04 542 502 1860 20 542 502 1860 20 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.3224.32 18.8818.88 40 0 973 755 40 0 973 755 WW 12F-0sw12F-0sw 0.0650.065 ww 4.944.94 0.470.47 368 274 1355 130 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.3224.32 34.4234.42 94 0 2280 3227 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.653.65 0.040.04 585 525 1918 18 585 525 1918 18GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.3224.32 34.4234.42 60 0 1459 2065 60 0 1459 2065 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 2557 2557 3886 2147 8 8 12 7 FF 21A-28v21A-28v 0.0220.022 --1.671.67 0.000.00 2544 2544 4253 0 2544 2544 4253 0 FF 21A-28v21A-28v 0.0220.022 --1.671.67 0.000.00 19 19 31 0 0 0 0 0 6 c) AED excursion 1221 1621 Envelope loss/gain 32435 13283 14778 4543 12 a) Infiltration 6414 622 1670 162 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 7 1610 0 0 Appliances/other 5000 1400 Subtotal (lines 6 to 13)38849 20515 16448 6105 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 38849 20515 16448 6105 15 Duct loads 0%0%0 0 0%0%0 0 Total room load 38849 20515 16448 6105 Air required (cfm)Air required (cfm)1090 1270 461 378 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:47Right-Suite® Universal 2019 19.0.15 RSU20783 Page 2...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J® Worksheet 03-06-2020Date:Entire House Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Room name Main Zone 2 Exposed wall 215.5 ft 3 Room height 8.7 ft 4 Room dimensions 5 Room area 2548.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12F-0sw 0.065 n 4.94 0.47 434 404 1994 192 .G 2 glazing, clr low-e 0.320 n 24.32 10.56 30 0 740 321 .W 15B19-0wc-6 0.069 n 3.82 0.05 0 0 0 0 .W 12F-0sw 0.065 e 4.94 0.47 559 457 2256 21711G2 glazing, clr low-e 0.320 e 24.32 34.42 60 0 1469 2080 D 11D0 0.390 e 29.64 7.21 42 42 1245 303 W 15B19-0wc-6 0.069 e 3.82 0.05 0 0 0 0 W 12F-0sw 0.065 s 4.94 0.47 418 400 1976 190 G 2 glazing, clr low-e 0.320 s 24.32 18.88 18 0 438 340 W 15B19-0wc-6 0.069 s 3.70 0.04 0 0 0 0 G 2 glazing, clr low-e 0.320 s 24.32 18.88 0 0 0 0 W 12F-0sw 0.065 w 4.94 0.47 368 274 1355 130 G 2 glazing, clr low-e 0.320 w 24.32 34.42 94 0 2280 3227 W 15B19-0wc-6 0.069 w 3.65 0.04 0 0 0 0G2 glazing, clr low-e 0.320 w 24.32 34.42 0 0 0 0 C 16B-50ad 0.020 -1.52 0.84 2549 2549 3874 2141 F 21A-28v 0.022 -1.67 0.00 0 0 0 0 F 21A-28v 0.022 -1.67 0.00 19 19 31 0 6 c) AED excursion 1338 Envelope loss/gain 17657 10478 12 a) Infiltration 4744 460 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 7 1610 Appliances/other 3600 Subtotal (lines 6 to 13)22401 16148 Less external load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 22401 16148 15 Duct loads 0%0%0 0 Total room load 22401 16148 Air required (cfm)629 1000 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:47Right-Suite® Universal 2019 19.0.15 RSU20783 Page 3...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J® Worksheet 03-06-2020Date:Basement Zone Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Room name Basement Zone Utilty 2 Exposed wall 250.5 ft 24.3 ft 3 Room height 9.0 ft 9.0 heat/coolft 4 Room dimensions ft209.3x1.0 5 Room area 2543.8 ft²209.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.823.82 0.050.05 542 542 2070 27 54 54 206 3 .WW 12F-0sw12F-0sw 0.0650.065 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 011GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.823.82 0.050.05 585 585 2233 29 164 164 627 8 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.703.70 0.040.04 542 502 1860 20 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.3224.32 18.8818.88 40 0 973 755 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.653.65 0.040.04 585 525 1918 18 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.3224.32 34.4234.42 60 0 1459 2065 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 8 8 12 7 5 5 7 4 FF 21A-28v21A-28v 0.0220.022 --1.671.67 0.000.00 2544 2544 4253 0 209 209 350 0 FF 21A-28v21A-28v 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 1621 -1 Envelope loss/gain 14778 4543 1190 13 12 a) Infiltration 1670 162 162 16 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 1400 0 Subtotal (lines 6 to 13)16448 6105 1352 29 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 -1352 -29 14 Subtotal 16448 6105 0 0 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 16448 6105 0 0 Air required (cfm)Air required (cfm)461 378 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:47Right-Suite® Universal 2019 19.0.15 RSU20783 Page 4...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J® Worksheet 03-06-2020Date:Basement Zone Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Room name Mechanical Bed. 4 2 Exposed wall 6.3 ft 28.8 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft13.0x6.3 ft15.8x13.0 5 Room area 81.3 ft²204.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.823.82 0.050.05 0 0 0 0 142 142 541 7 .WW 12F-0sw12F-0sw 0.0650.065 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 011GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.823.82 0.050.05 56 56 215 3 117 117 447 6 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.703.70 0.040.04 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.3224.32 18.8818.88 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.653.65 0.040.04 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.3224.32 34.4234.42 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.671.67 0.000.00 81 81 136 0 205 205 342 0 FF 21A-28v21A-28v 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 0 -1 Envelope loss/gain 351 3 1330 12 12 a) Infiltration 42 4 192 19 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)392 7 1522 30 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -392 -7 158 3 14 Subtotal 0 0 1680 33 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 0 0 1680 33 Air required (cfm)Air required (cfm)0 0 47 2 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:47Right-Suite® Universal 2019 19.0.15 RSU20783 Page 5...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J® Worksheet 03-06-2020Date:Basement Zone Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Room name Bed 3 Family Rm 2 Exposed wall 36.5 ft 82.5 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft257.7x1.0 ft1226.2x1.0 5 Room area 257.7 ft²1226.2 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.823.82 0.050.05 34 34 129 2 108 108 412 5 .WW 12F-0sw12F-0sw 0.0650.065 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 011GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.823.82 0.050.05 126 126 481 6 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.703.70 0.040.04 169 149 539 5 302 282 1046 11 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.3224.32 18.8818.88 20 0 486 378 20 0 486 378 WW 12F-0sw12F-0sw 0.0650.065 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.653.65 0.040.04 0 0 0 0 333 313 1166 13GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.3224.32 34.4234.42 0 0 0 0 20 0 486 688 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.671.67 0.000.00 258 258 431 0 1226 1226 2050 0 FF 21A-28v21A-28v 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 450 498 Envelope loss/gain 2067 840 5647 1594 12 a) Infiltration 243 24 550 53 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 900 Subtotal (lines 6 to 13)2310 864 6197 2547 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 459 10 1126 23 14 Subtotal 2769 874 7324 2570 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2769 874 7324 2570 Air required (cfm)Air required (cfm)78 54 205 159 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:47Right-Suite® Universal 2019 19.0.15 RSU20783 Page 6...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J® Worksheet 03-06-2020Date:Basement Zone Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Room name Laundry Bath 1 2 Exposed wall 0 ft 21.5 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft6.3x10.3 ft8.0x13.5 5 Room area 64.1 ft²108.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.823.82 0.050.05 0 0 0 0 72 72 275 4 .WW 12F-0sw12F-0sw 0.0650.065 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 011GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.823.82 0.050.05 0 0 0 0 122 122 464 6 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.703.70 0.040.04 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.3224.32 18.8818.88 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.653.65 0.040.04 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.3224.32 34.4234.42 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 0 0 0 0 3 3 5 3 FF 21A-28v21A-28v 0.0220.022 --1.671.67 0.000.00 64 64 107 0 108 108 181 0 FF 21A-28v21A-28v 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -21 -1 Envelope loss/gain 107 -21 924 11 12 a) Infiltration 0 0 143 14 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 500 0 Subtotal (lines 6 to 13)107 479 1067 25 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 107 479 1067 25 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 107 479 1067 25 Air required (cfm)Air required (cfm)3 30 30 2 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:47Right-Suite® Universal 2019 19.0.15 RSU20783 Page 7...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J® Worksheet 03-06-2020Date:Basement Zone Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Room name Bed 5 Bed 6 2 Exposed wall 22.5 ft 28.3 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft193.4x1.0 ft14.8x13.5 5 Room area 193.4 ft²199.1 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.823.82 0.050.05 0 0 0 0 133 133 507 7 .WW 12F-0sw12F-0sw 0.0650.065 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 011GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.823.82 0.050.05 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.703.70 0.040.04 72 72 275 4 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.3224.32 18.8818.88 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.653.65 0.040.04 131 111 393 3 122 102 359 2GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.3224.32 34.4234.42 20 0 486 688 20 0 486 688 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.671.67 0.000.00 193 193 323 0 199 199 333 0 FF 21A-28v21A-28v 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 350 349 Envelope loss/gain 1478 1045 1685 1047 12 a) Infiltration 150 15 188 18 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1628 1059 1873 1065 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1628 1059 1873 1065 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1628 1059 1873 1065 Air required (cfm)Air required (cfm)46 66 53 66 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:47Right-Suite® Universal 2019 19.0.15 RSU20783 Page 8...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J® Worksheet 03-06-2020Date:Main Zone Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Room name Main Zone Laundry 2 2 Exposed wall 215.5 ft 20.8 ft 3 Room height 8.7 ft 8.0 heat/coolft 4 Room dimensions ft107.5x1.0 5 Room area 2548.5 ft²107.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.944.94 0.470.47 434 404 1994 192 62 47 232 22 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.3224.32 10.5610.56 30 0 740 321 15 0 365 158 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.944.94 0.470.47 559 457 2256 217 104 104 514 4911GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.3224.32 34.4234.42 60 0 1469 2080 0 0 0 0 DD 11D011D0 0.3900.390 ee 29.6429.64 7.217.21 42 42 1245 303 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.944.94 0.470.47 418 400 1976 190 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.3224.32 18.8818.88 18 0 438 340 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.944.94 0.470.47 368 274 1355 130 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.3224.32 34.4234.42 94 0 2280 3227 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 2549 2549 3874 2141 108 108 163 90 FF 21A-28v21A-28v 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.671.67 0.000.00 19 19 31 0 0 0 0 0 6 c) AED excursion 1338 -19 Envelope loss/gain 17657 10478 1274 301 12 a) Infiltration 4744 460 443 43 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 7 1610 0 0 Appliances/other 3600 500 Subtotal (lines 6 to 13)22401 16148 1717 844 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 22401 16148 1717 844 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 22401 16148 1717 844 Air required (cfm)Air required (cfm)629 1000 48 52 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:47Right-Suite® Universal 2019 19.0.15 RSU20783 Page 9...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J® Worksheet 03-06-2020Date:Main Zone Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Room name Office Kitch-Dinn 2 Exposed wall 27.8 ft 25.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft176.0x1.0 ft509.1x1.0 5 Room area 176.0 ft²509.1 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.944.94 0.470.47 118 103 507 49 74 74 366 35 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.3224.32 10.5610.56 15 0 375 163 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.944.94 0.470.47 0 0 0 0 0 0 0 011GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.3224.32 34.4234.42 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ee 29.6429.64 7.217.21 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.3224.32 18.8818.88 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.944.94 0.470.47 104 73 361 35 126 95 468 45 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.3224.32 34.4234.42 31 0 750 1061 31 0 760 1076 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 176 176 268 148 509 509 774 428 FF 21A-28v21A-28v 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.671.67 0.000.00 0 0 0 0 11 11 18 0 6 c) AED excursion 460 238 Envelope loss/gain 2261 1915 2385 1821 12 a) Infiltration 592 57 533 52 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 2000 Subtotal (lines 6 to 13)2853 1973 2918 3873 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 593 76 14 Subtotal 2853 1973 3512 3948 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2853 1973 3512 3948 Air required (cfm)Air required (cfm)80 122 99 244 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:47Right-Suite® Universal 2019 19.0.15 RSU20783 Page 10...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J® Worksheet 03-06-2020Date:Main Zone Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Room name Great-Entry Master 2 Exposed wall 27.5 ft 32.5 ft 3 Room height 10.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft837.4x1.0 ft15.3x17.3 5 Room area 837.4 ft²263.1 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.944.94 0.470.47 80 80 395 38 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.3224.32 10.5610.56 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.944.94 0.470.47 195 144 713 69 0 0 0 011GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.3224.32 34.4234.42 30 0 719 1018 0 0 0 0 DD 11D011D0 0.3900.390 ee 29.6429.64 7.217.21 21 21 622 152 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.944.94 0.470.47 0 0 0 0 122 110 543 52 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.3224.32 18.8818.88 0 0 0 0 12 0 292 227 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.944.94 0.470.47 0 0 0 0 138 106 525 50 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.3224.32 34.4234.42 0 0 0 0 32 0 770 1090 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 837 837 1273 703 263 263 400 221 FF 21A-28v21A-28v 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.671.67 0.000.00 4 4 7 0 0 0 0 0 6 c) AED excursion -61 477 Envelope loss/gain 3730 1919 2531 2117 12 a) Infiltration 733 71 693 67 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 5 1150 2 460 Appliances/other 900 200 Subtotal (lines 6 to 13)4463 4040 3224 2844 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 4463 4040 3224 2844 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 4463 4040 3224 2844 Air required (cfm)Air required (cfm)125 250 90 176 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:47Right-Suite® Universal 2019 19.0.15 RSU20783 Page 11...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J® Worksheet 03-06-2020Date:Main Zone Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Room name Master Bath Master Closet 2 Exposed wall 12.5 ft 7.5 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft12.5x13.5 ft7.5x10.3 5 Room area 168.8 ft²76.9 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.944.94 0.470.47 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.3224.32 10.5610.56 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.944.94 0.470.47 0 0 0 0 0 0 0 011GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.3224.32 34.4234.42 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ee 29.6429.64 7.217.21 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.944.94 0.470.47 100 100 494 47 60 54 267 26 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.3224.32 18.8818.88 0 0 0 0 6 0 146 113 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.3224.32 34.4234.42 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 169 169 256 142 77 77 117 65 FF 21A-28v21A-28v 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.671.67 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -19 114 Envelope loss/gain 750 170 530 317 12 a) Infiltration 267 26 160 16 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1017 196 690 333 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1017 196 690 333 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1017 196 690 333 Air required (cfm)Air required (cfm)29 12 19 21 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:47Right-Suite® Universal 2019 19.0.15 RSU20783 Page 12...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J® Worksheet 03-06-2020Date:Main Zone Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Room name Bed. 2 Bath 2 2 Exposed wall 34.3 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft205.0x1.0 ft7.5x5.5 5 Room area 205.0 ft²41.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.944.94 0.470.47 32 32 158 15 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.3224.32 10.5610.56 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.944.94 0.470.47 106 75 371 36 0 0 0 011GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.3224.32 34.4234.42 31 0 750 1061 0 0 0 0 DD 11D011D0 0.3900.390 ee 29.6429.64 7.217.21 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.944.94 0.470.47 136 136 672 65 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.3224.32 18.8818.88 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.3224.32 34.4234.42 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 205 205 312 172 41 41 63 35 FF 21A-28v21A-28v 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.671.67 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 193 -3 Envelope loss/gain 2263 1542 63 32 12 a) Infiltration 731 71 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2993 1613 63 32 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 2993 1613 63 32 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2993 1613 63 32 Air required (cfm)Air required (cfm)84 100 2 2 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:47Right-Suite® Universal 2019 19.0.15 RSU20783 Page 13...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J® Worksheet 03-06-2020Date:Main Zone Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Room name 1/2 Bath Mudd 2 Exposed wall 3.5 ft 7.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft8.5x3.5 ft8.5x7.0 5 Room area 29.8 ft²59.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.944.94 0.470.47 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.3224.32 10.5610.56 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.944.94 0.470.47 28 28 138 13 56 35 173 1711GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.3224.32 34.4234.42 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ee 29.6429.64 7.217.21 0 0 0 0 21 21 622 152 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.3224.32 18.8818.88 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.3224.32 34.4234.42 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 30 30 45 25 60 60 90 50 FF 21A-28v21A-28v 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.671.67 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -4 -21 Envelope loss/gain 184 34 886 197 12 a) Infiltration 75 7 149 14 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)258 41 1035 212 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 576 73 14 Subtotal 258 41 1612 285 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 258 41 1612 285 Air required (cfm)Air required (cfm)7 3 45 18 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:47Right-Suite® Universal 2019 19.0.15 RSU20783 Page 14...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Webb R...Job:Right-J® Worksheet 03-06-2020Date:Main Zone Claudia MartinezBy:Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com 1 Room name Pantry 2 Exposed wall 17.3 ft 3 Room height 8.0 heat/coolft 4 Room dimensions ft8.5x8.8 5 Room area 74.4 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12F-0sw 0.065 n 4.94 0.47 68 68 336 32 .G 2 glazing, clr low-e 0.320 n 24.32 10.56 0 0 0 0 .W 15B19-0wc-6 0.069 n 0.00 0.00 0 0 0 0 .W 12F-0sw 0.065 e 4.94 0.47 70 70 346 3311G2 glazing, clr low-e 0.320 e 24.32 34.42 0 0 0 0 D 11D0 0.390 e 29.64 7.21 0 0 0 0 W 15B19-0wc-6 0.069 e 0.00 0.00 0 0 0 0 W 12F-0sw 0.065 s 4.94 0.47 0 0 0 0 G 2 glazing, clr low-e 0.320 s 24.32 18.88 0 0 0 0 W 15B19-0wc-6 0.069 s 0.00 0.00 0 0 0 0 G 2 glazing, clr low-e 0.320 s 0.00 0.00 0 0 0 0 W 12F-0sw 0.065 w 4.94 0.47 0 0 0 0 G 2 glazing, clr low-e 0.320 w 24.32 34.42 0 0 0 0 W 15B19-0wc-6 0.069 w 0.00 0.00 0 0 0 0G2 glazing, clr low-e 0.320 w 0.00 0.00 0 0 0 0 C 16B-50ad 0.020 -1.52 0.84 74 74 113 62 F 21A-28v 0.022 -0.00 0.00 0 0 0 0 F 21A-28v 0.022 -1.67 0.00 4 4 7 0 6 c) AED excursion -15 Envelope loss/gain 802 113 12 a) Infiltration 368 36 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13)1170 149 Less external load 0 0 Less transfer 0 0 Redistribution -1170 -149 14 Subtotal 0 0 15 Duct loads -0%0%0 0 Total room load 0 0 Air required (cfm)0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:49 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 1 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Web...Job:Loads for Multiple Orientations 03-06-2020Date:Entire House Claudia MartinezBy: Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com Project Information T. Webb Construction-Webb ResidenceFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-31.535.2Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F) )H(34-Daily range (°F) 60-Wet bulb (°F) 7.515.0Wind speed (mph) Front Door North Northeast East Southeast South Southwest West Northwest Sensible Load (Btuh) 17614 20276 20745 19730 16803 18690 19381 19259 Latent Load (Btuh) 0 0 0 0 0 0 0 0 Total Load (Btuh) 17614 20276 20745 19730 16803 18690 19381 19259 Heating AVF (cfm) 1090 1090 1090 1090 1090 1090 1090 1090 Cooling AVF (cfm) 1270 1270 1270 1270 1270 1270 1270 1270 Building Orientation Cooling Load To t a l C o o l i n g L o a d ( B t u h ) Direction Front Door faces 0 5000 10000 15000 20000 25000 N NE E SE S SW W NW Front Door faces EastCurrent Orientation: Front Door faces EastHighest Cooling Load: Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:49 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 2 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Web...Job:Loads for Multiple Orientations 03-06-2020Date:Basement Zone Claudia MartinezBy: Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com Project Information T. Webb Construction-Webb ResidenceFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-31.535.2Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F) )H(34-Daily range (°F) 60-Wet bulb (°F) 7.515.0Wind speed (mph) Front Door North Northeast East Southeast South Southwest West Northwest Sensible Load (Btuh) 5219 5644 5738 5378 4356 3811 4484 5102 Latent Load (Btuh) 0 0 0 0 0 0 0 0 Total Load (Btuh) 5219 5644 5738 5378 4356 3811 4484 5102 Heating AVF (cfm) 461 461 461 461 461 461 461 461 Cooling AVF (cfm) 408 381 378 369 347 281 316 361 Building Orientation Cooling Load To t a l C o o l i n g L o a d ( B t u h ) Direction Front Door faces 0 1000 2000 3000 4000 5000 6000 N NE E SE S SW W NW Front Door faces EastCurrent Orientation: Front Door faces EastHighest Cooling Load: Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-13 12:28:49 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 3 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Web...Job:Loads for Multiple Orientations 03-06-2020Date:Main Zone Claudia MartinezBy: Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com Project Information T. Webb Construction-Webb ResidenceFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-31.535.2Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F) )H(34-Daily range (°F) 60-Wet bulb (°F) 7.515.0Wind speed (mph) Front Door North Northeast East Southeast South Southwest West Northwest Sensible Load (Btuh) 14307 15223 15179 13892 13411 14107 14448 14194 Latent Load (Btuh) 761 761 761 761 761 761 761 761 Total Load (Btuh) 15068 15984 15940 14652 14171 14867 15208 14955 Heating AVF (cfm) 629 629 629 629 629 629 629 629 Cooling AVF (cfm) 1118 1028 1000 954 1068 1040 1020 1005 Building Orientation Cooling Load To t a l C o o l i n g L o a d ( B t u h ) Direction Front Door faces 0 5000 10000 15000 20000 N NE E SE S SW W NW Front Door faces EastCurrent Orientation: Front Door faces NortheastHighest Cooling Load: 2020-Mar-13 12:28:50 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 1 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Web...Job:Static Pressure and Friction Rate 03-06-2020Date:Entire House Claudia MartinezBy: Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com Project Information T. Webb Construction-Webb ResidenceFor: Available Static Pressure CoolingHeating (in H2O)(in H2O) 0.900.90External static pressure Pressure losses 0.250.25Coil 00Heat exchanger 0.030.03Supply diffusers 0.030.03Return grilles 00Filter 00Humidifier 0.030.03Balancing damper 00Other device 0.560.56Available static pressure Total Effective Length ReturnSupply (ft)(ft) 2523Measured length of run-out 3843Measured length of trunk 290355Equivalent length of fittings 353421Total length 774Total effective length Friction Rate CoolingHeating (in/100ft)(in/100ft) OK0.072OK0.072Supply Ducts OK0.072OK0.072Return Ducts Fitting Equivalent Length Details 4AD=60, 9L=20, 9L=20, 9L=20, 9L=20, 9L=20, 12H2=15, 9L=20, 9L=20, 9L=20, 9L=20, 12H2=15, USR1=85: TotalEL=355 Supply 6M=20, 6B6=110, 6BB=25, 6BB=25, 6BB=25, 6BA=10, 12H2=15, 6BA=10, 10B=10, 12H2=15, 8CB=5, 5J1=20: TotalEL=290 Return 2020-Mar-13 12:28:50 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 1 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E T. Webb Construction-Web...Job:Duct System Summary 03-06-2020Date:Entire House Claudia MartinezBy: Personal BridgewaterPlan:Freedom Heating, Inc. P.O Box 51966, Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Email: Freedomheatinginc@yahoo.com Project Information T. Webb Construction-Webb ResidenceFor: CoolingHeating External static pressure in H2O0.90in H2O0.90 Pressure losses in H2O0.34in H2O0.34 Available static pressure in H2O0.56in H2O0.56 Supply / return available pressure 0.305 / 0.255 in H2O in H2O0.305 / 0.255 Lowest friction rate in/100ft0.072in/100ft0.072 Actual air flow cfm1270cfm1090 Total effective length (TEL)ft774 2020-Mar-13 12:28:50 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 2 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st5150.023.5ShMt0x06.00.17537258h1/2 Bath st4A160.034.3ShMt0x06.00.157115534hBath 1 st4A150.039.5ShMt0x06.00.161115534hBath 1-A st6A220.040.3ShMt0x06.00.1172232cBath 2 st3125.063.8ShMt0x06.00.16127391385hBed 3 st3A150.059.3ShMt0x06.00.14627391385hBed 3-A st4140.033.8ShMt0x06.00.1753323530cBed 5 st4A170.045.3ShMt0x06.00.1413323530cBed 5-A st4A140.053.0ShMt0x06.00.1583326533cBed 6 st4A155.052.8ShMt0x06.00.1473326533cBed 6-A st6B355.065.8ShMt0x06.00.0725042806cBed. 2 st6B315.067.3ShMt0x06.00.0805042806cBed. 2-A st4A165.034.3ShMt0x06.00.153124840hBed. 4 st4135.034.3ShMt0x06.00.180124840hBed. 4-A st3A130.048.0ShMt0x06.00.17132411465hFamily Rm st3A160.059.0ShMt0x06.00.13932411465hFamily Rm-A st6A270.050.3ShMt0x06.00.09532411465hFamily Rm-B st3135.027.3ShMt0x06.00.18832411465hFamily Rm-C st3A155.045.8ShMt0x06.00.15232411465hFamily Rm-D st6A200.055.0ShMt0x06.00.11963311010cGreat-Entry st6125.023.3ShMt0x06.00.20563311010cGreat-Entry-A st6165.035.0ShMt0x06.00.15263311010cGreat-Entry-B st6145.043.5ShMt0x06.00.16263311010cGreat-Entry-C st5165.023.3ShMt0x06.00.16281331316cKitch-Dinn st5125.035.0ShMt0x06.00.19081331316cKitch-Dinn-A st5185.043.8ShMt0x06.00.13381331316cKitch-Dinn-B st4125.027.8ShMt0x06.00.199303479cLaundry st5A220.032.3ShMt0x06.00.1215248844cLaundry 2 st6B355.062.5ShMt0x06.00.07388451422cMaster st6A260.036.0ShMt0x06.00.103614509hMaster Bath st6B295.039.3ShMt0x06.00.091614509hMaster Bath-A st6B335.047.8ShMt0x06.00.0802119333cMaster Closet st6A240.049.3ShMt0x06.00.10588451422cMaster-A st5145.035.3ShMt0x06.00.16918451612hMudd st5A245.051.5ShMt0x06.00.1036140986cOffice st5A240.055.3ShMt0x06.00.1036140986cOffice-A 2020-Mar-13 12:28:50 Right-Suite® Universal 2019 19.0.15 RSU20783 Page 3 ...s\T-Webb Construction- Personal Bridgewater.rup Calc = MJ8 Front Door faces: E Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st5 Peak AVF 279 439 0.103 659 10.1 12x8 ShtMetl st2 st6A Peak AVF 296 405 0.072 607 10.5 12x8 ShtMetl st6 st3 Peak AVF 242 181 0.139 436 7.6 10x8 ShtMetl st1 st6 Peak AVF 390 592 0.072 667 12.1 16x8 ShtMetl st2 st6B Peak AVF 163 215 0.072 483 8.3 8x8 ShtMetl st6A st5A Peak AVF 128 174 0.103 392 7.2 8x8 ShtMetl st5 st3A Peak AVF 162 123 0.139 365 6.6 8x8 ShtMetl st3 st4A Peak AVF 129 101 0.141 290 5.5 8x8 ShtMetl st4 st4 Peak AVF 178 165 0.141 321 6.7 10x8 ShtMetl st1 st2 Peak AVF 670 1032 0.072 774 14.9 24x8 ShtMetl st1 Peak AVF 420 346 0.139 631 9.4 12x8 ShtMetl Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb8 0x 840 100 353.0 0.072 316 6.2 3.25x14 10x9 SJSp rt3A rb5 0x 780 54 247.0 0.103 246 5.3 3.25x14 10x9 SJSp rt3A rb7 0x 1380 209 158.1 0.162 661 7.0 3.25x14 10x9 SJSp rt3A rb9 0x 1170 147 232.3 0.110 466 6.6 3.25x14 10x9 SJSp rt3A rb10 0x 2090 422 207.5 0.123 445 9.6 3-3.25x14 3-10x27 SJSp rt3A rb1 0x 470 2 117.8 0.217 149 3.8 3.25x14 10x9 SJSp rt2 rb6 0x 800 122 214.5 0.119 387 6.1 3.25x14 10x9 SJSp rt2A rb4 0x 2380 190 109.8 0.233 755 6.8 3.25x14 10x9 SJSp rt3 rb3 0x 460 66 156.0 0.164 207 4.5 3.25x14 10x9 SJSp rt2A rb2 0x 530 66 280.3 0.091 209 5.1 3.25x14 10x9 SJSp rt2A Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt3A Peak AVF 626 932 0.072 699 14.3 24x8 ShtMetl rt3 rt2 Peak AVF 225 256 0.091 383 8.4 12x8 ShtMetl rt1 rt2A Peak AVF 178 254 0.091 571 8.3 8x8 ShtMetl rt2 rt3 Peak AVF 865 1122 0.072 646 15.3 25x10 ShtMetl rt1 rt1 Peak AVF 1090 1378 0.072 661 16.6 25x12 ShtMetl Job #: T. Webb Construction-Webb Reside... Performed by Claudia Martinez for: T. Webb Construction-Webb Residence Freedom Heating, Inc. P.O Box 51966 Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Freedomheatinginc@yahoo.com Scale: 1 : 128 Page 1 Right-Suite® Universal 2019 19.0.15 RSU20783 2020-Mar-13 12:29:19 ...uction- Personal Bridgewater.rup N Mainfloor Laundry 2 Office Kitch-Dinn Great-Entry Master Master Bath Master Closet Bed. 2 Bath 2 1/2 Bath Mudd Pantry Fireplace Rm. Stairs 61 cfm63 cfm 63 cfm 52 cfm 88 cfm 45 cfm 2 cfm 21 cfm 14 cfm 14 cfm 122 cfm 209 cfm 100 cfm 63 cfm 63 cfm 422 cfm 88 cfm 147 cfm 81 cfm 81 cfm 61 cfm 81 cfm 50 cfm 50 cfm 7 cfm Job #: T. Webb Construction-Webb Reside... Performed by Claudia Martinez for: T. Webb Construction-Webb Residence Freedom Heating, Inc. P.O Box 51966 Idaho Falls, ID 83405 Phone: 208-339-0344 Fax: 208-522-1320 Freedomheatinginc@yahoo.com Scale: 1 : 128 Page 2 Right-Suite® Universal 2019 19.0.15 RSU20783 2020-Mar-13 12:29:19 ...uction- Personal Bridgewater.rup N Basement Utilty Mechanical Bed. 4 Bed 3 Family Rm Laundry Bath 1 Bed 5 Bed 6 Stairs 33 cfm 33 cfm 33 cfm 33 cfm41 cfm 41 cfm 15 cfm 15 cfm 30 cfm 24 cfm 41 cfm 66 cfm 66 cfm 78 cfm 47 cfm 6 " 12 x 8 6 " 6 " 6 " 6 "6 "6 " 6 " 39 cfm 39 cfm 6 " 6 " 6 " 6 " 6 " 24 cfm 6 " 25 x 12 14x3.25 14x3.25 238 cfm14x3.25 41 cfm 6 " 14x3.25 14x3.25 12 x 8 25 x 10 3-14x3.2514x3.25 14x3.25 14x3.25 14x3.25 6 " 6 " 6 " 6 " 6 " 6 "6 " 6 " 6 " 6 " 6 " 6 " 6 "6 " 6 "6 " 6 " 6 " 6 " 24 x 8 24 x 8 41 cfm 6 " 10 x 8 8 x 8 10 x 8 8 x 8 8 x 8 12 x 8 16 x 8 6 " 12 x 88 x 8 8 x 8 Fresh air is done with insulated flex 6"