HomeMy WebLinkAboutCOMCHECK - 21-00717 - Metal Office Building Vet ClinicCOMcheck Software Version 4.1.5.3
Envelope Compliance Certificate
Project Information
Energy Code:
2018 IECC
Project Title:
Location:
Rexburg, Idaho
Climate Zone:
6b
Project Type:
New Construction
Construction Site:
Owner/Agent: Designer/Contractor:
Additional Efficiency Package(s)
Credits: 1.0 Required 1.0 Proposed
On -site Renewable Energy, 1.0 credit
Building Area Floor Area
1-Warehouse : Nonresidential 5000
Envelope Assemblies
Assembly
Gross Area
Cavity
Cont.
Proposed
Budget U-
or
R-Value
R-Value
U-Factor
Factona�
Perimeter
Roof 1: Metal Building, Standing Seam, Liner System with Thermal
5840
36.0
0.0
0.031
0.031
Blocks (b), [Bldg. Use 1 - Warehouse]
Exterior Wall 1: Metal Building Wall, Single Layer Mineral Fiber (in
6120
30.0
0.0
0.052
0.052
cavity, thermal block at girt), [Bldg. Use 1 - Warehouse]
(a) Budget U-factors are used for software baseline calculations ONLY, and are not code requirements.
(b) Thermal spacer block with minimum R-3.5 must be installed above the purlin/batt, and the roof deck secured to the purlins
,ne PASSES: Desion 0.0% better than code
Envelope Compliance Statement
Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed envelope systems have been
designed to meet the 2018 IECC requirements in COMcheck Version 4.1.5.3 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Signature Date
Project Title: Report date: 11/22/21
Data filename: Untitled.cck Page 1 of 8