HomeMy WebLinkAboutFIRE ALARM SUBMITTAL - 21-00250 - BYUI Manwaring Center Activities & Involvement - Remodel FIRE CONTROL INSTRUMENTS-GAMEWELL-BOSCH 1481 SOUTH MAJOR STREET S.L.C., UT 84115 P. 801-468-8300 F. 801-468-8305 BYU-I Manwaring 2021 525 South Center Street Rexburg. ID 83460 Manwaring Center Remodel 2021 BYU-Idaho Fire Alarm System Submittal & Drawings PROJECT Equipment Manufacturer: Gamewell-FCI Manwaring Center Authorized Distributor: Nelson Fire Systems Remodel 2021 1481 S Major St BYU-Idaho SLC, UT 84115 Fire Alarm System 801-468-8300... BYU-I Manwarin 2021 Remodel 525 South Center Street Rexburg, ID 83460 TABLE OF CONTENTS Data Sheet Part No. Description Gamewell-FCI E3 Series Emergency Evacuation System (Existing) Gamewell-FCI SPCWL Speaker Only – Ceiling Mount Gamewell-FCI SPSCWL Speaker/Strobe – Ceiling Mount Gamewell-FCI HPFF8 NAC Power Supply (Existing) Battery Calculations HPFF8 Battery Calc CKT Voltage Drops Drawings Sheet No. Description Cover Page FA-C-01 Fire Alarm Cover Riser Diagram FA-R-01 Fire Alarm Riser and Matrix Level 1 FA-1-01 Notification Circuits E3 Series with LCD-SLP Display E3 Series with LCD-E3 Display E3 Series® Control Panel Expandable Emergency Evacuation System Analog and Networking Systems General The E3 Series® Expandable Emergency Evacuation System by Gamewell-FCI is in the forefront of the latest generation of fire alarm control panels. The E3 Series System is designed for use in virtually any application because it features a modular assembly that is configured per project requirements. Employing the new high-speed Velociti® sensors, the E3 Series provides previously unattainable polling speed and response together with the flexibility demanded by today’s emergency evacuation systems. In addition to the sensors’ high-speed polling rate, the Velociti Series of sensors feature bi-polar LEDs that flash green for normal polling, and light red steadily to indicate an alarm. The E3 Series is equipped with an 80-character LCD-E3 alphanumeric LCD display or 4.3” color touchscreen LCD-SLP display. Up to six keyboard LCD displays may be remotely located. In addition, you can install five of the familiar LCD-7100/RAN-7100 remote displays. The displays show instant system status information and can be connected in any desired area of an installation. FEATURES & BENEFITS • Styles 4, 6, or 7* signaling line circuits • IBC Seismic Certified • Listed under UL® Standard 864, 9th Edition • Listed under UL Standard UL2572 for Mass Notification • UL Listed for smoke control (dedicated and non-dedicated) when properly configured • UL Listed and FM Approved for Pre- action/Deluge and Agent Releasing • Two to 244 SLCs each supporting 159 sensors, 159 modules and 159 addressable sounder bases • 625K bits per second ARCNET communications using wire, fiber, or mixed configurations for installation flexibility • High-speed 32 bit processor and 8100 event history log • Advanced Boolean logic-based programming such as AND, OR, NOT, time delay and calendar functions configurable via computer programming • Supports up to (16), ASM-16 addressable switch or ANU-48 LED driver modules per ILI- MB-E3/ILI95-MB-E3 •Two Class A, Style Z or Class B, Style Y, notification appliance circuits rated at 2.0 amps. per circuit •Integral city connection • Up to 9 levels of sensitivity adjustment • Flexible 115,200 baud high speed RS-232 interface • 40 character user- defined text per device •Supports the following: - 15 LCD-SLP displays/ annunciators - 6 LCD-E3 displays/ annunciators - 5 LCD-7100/RAN-7100 remote LED annunciators per ILI-MB-E3/ ILI95-MB-E3 • Polls 318 devices in less than two seconds • Activate up to 159 outputs in less than five seconds • LED’s blink associated device address during Walk Test. • Fully digital, high- precision protocol •Drift compensation • Pre-Alarm adjustable between 15 levels for both Alert and Action • Day/night automatic sensing adjustment •Sensitivity windows • Ion 0.05 - 2% obscuration • Photo 1 - 3% obscuration • Laser 0.02 - 2% obscuration • MCS Acclimate 2.5 - 4%, also self- adjustable options: 1- 2%, 2-3%, 3-4% •HARSH 1-3% obscuration • Each Loop Card has its own integral processor providing maximum survivability on loss of any other component. SLC provides full response on loss of any other system processor •Optional programmable switches can be configured to enable, disable or group any combination of output devices • Integrated point or Grouped Cross Zoning allows for numerous devices installed at any location to cooperate and determine alarm condition • Automatic detector sensitivity testing •Signals DIRTY and VERY DIRTY detector maintenance alerts 2 General A high-speed 32-bit processor can easily implement a wide array of applications used in small office buildings or used in multi-complex, high-rise installations. The 64 node networking is made possible by 625K bits per second ARCNET communications using twisted-pair copper cable, fiber-optic cable, or a combination of both. In addition, the Addressable Node Expander (ANX) board expands the network to 122 nodes. The basic E3 Series is equipped with the following modules: • PM-9 Power Supply • ASM-16 (Addressable Switch Module) • ILI-MB-E3/ILI95-MB-E3 (Intelligent Loop Interface-Main Board) • ILI-S-E3/ILI95-S-E3 (Intelligent Loop Interface- Expansion Board) • LCD-E3 (LCD Keypad Display) The ASM-16 features 16 software programmable switches, each accompanied by red, green and yellow LEDs that can be programmed to indicate the operation of the switches. Additional ASM-16 modules may be added to expand the operation to a plateau previously unimagined. The Intelligent Loop Interface - Expansion Board (ILI- S-E3/ILI95-S-E3 provides the E3 Series control panel with two additional electrically isolated signaling line circuits. The layout is similar to the ILI-MB-E3/ILI95- MB-E3 with the exception that a number of components are omitted. It occupies one node on the Broadband network. Each ILI-MB-E3/ILI95-MB-E3 can support as many as sixteen ANU-48 LED Driver modules supporting hundreds of LEDs on a third party graphic annunciator to use for remote annunciation. The ANU-48 modules may be installed in any Listed remote annunciator. It can be remotely located via an RS-485 serial interface. An array of cabinets allows for neat, compact, attractive installations. Installation The E3 Series Expandable Emergency Evacuation System offers four cabinet size options. A typical cabinet includes a backbox, an inner door, and an outer door. The E3 Series cabinet assembly is a compact 19 3/8” (49 cm) wide, wall-mounted enclosure. • Cabinet A includes the following four options: - Cabinet A1 inner door mounted to the backbox. The backbox houses one NGA module. - Cabinet A2 inner door mounted to the backbox. The backbox houses one LCD-E3 module. - Two or three-bay inner door mounted to the backbox. - The backbox typically houses one LCD-E3, or one NGA, and one or two ASM-16 modules. • Cabinet B contains a space for the following modules installed inside the backbox: Additional module options mounted on the backbox include the following: The 2-bay inner door houses one LCD-E3 module and one ASM-16 module. • Both Cabinets C and D include the following: - Pre-assembled outer door that provides visibility to the fire fighter’s phone handset and a microphone voice messaging system. - Two inner door panel selections that may contain optional modules to meet the facility operation requirements. In the Cabinet B, C and D backboxes, the ANX appears in the same place as the ILI-MB-E3/ILI95-MB-E3 and PM-9/PM-9G. For information on the installation instructions for any of the E3 Series cabinets, refer to the E3 Series® Expandable Emergency Evacuation Manual, Part Number: LS10080-051GF-E. For other options including information on the system’s compatibility with the retrofit equipment, refer to the panel's installation manual, P/N:LS10080- 051GF-E or the Compatibility Addendum for Gamewell-FCI Manuals, P/N: 9000-0427-L8. Ordering Information ILI-MB-E3: Intelligent Loop Interface-Main Board ILI95-MB-E3: Intelligent Loop Interface-Main Board ILI-S-E3: Intelligent Loop Interface-Expansion Board ILI95-S-E3: Intelligent Loop Interface-Expansion Board ANX-SR: Addressable Node Expander-Single Ring ANX-MR-FO: Addressable Node Expander-Multi-Ring Fiber Optic ANX-MR-UTP: Addressable Node Expander-Multi- Ring Twisted-pair LCD-E3: LCD-E3, LCD Keypad Display LCD-SLP: LCD Color Touchscreen with five programmable switches RPT-E3-UTP: Network Repeater, unshielded, twisted- pair FML-E3: Multi-Mode Fiber-Optic Module FSL-E3: Single-Mode Fiber-Optic Module DACT-E3: Digital Alarm Communicator Transmitter ANU-48: ANU-48 LED Driver Module ASM-16: Addressable Switch Module NGA: LCD Network Graphic Annunciator PM-9: Power Supply Module, 120 VAC PM-9G: Power Supply Module, 220/240 VAC LCD-7100: Remote LCD Display RAN-7100: Remote LCD Display Note: For additional information on the cabinets, refer to the E3 Series Cabinets data sheet (Part Number: 9020-0649). - ILI-MB-E3 - PM-9 - ILI95-MB-E3 - PM-9G - ANX - DACT-E3 - ILI-S-E3 - ILI95-S-E3 - RPT-E3-UTP - E3 Series® Control Panel Technical Specifications 9020-0637 | S | 09/17 ©2017 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx E3 Series®, Velociti® and Gamewell-FCI® are registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriter’s Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s E3 Series® Control Panel and other products available by visiting www.Gamewell-FCI.com Seismic Battery Bracket Kits For information on the types of Seismic Battery Bracket Kits that are available, the Seismic Battery Bracket Kit Part Numbers and the Installation Instructions, refer to the following documents: • Seismic Battery Bracket Installation Guide, P/N: 53839 • E3 Series Cabinets Data Sheet, P/N: 9020-0649 SYSTEM Operating Voltage: 24 VDC Operating Temperature: Not to exceed the range of 32°- 120° F (0 -49° C) Relative Humidity: Not to exceed 93%, non- condensing at 90° F (32° C) Primary Power Supply: 9 amps @ 55 AH capacity TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. STANDARDS The E3 Series fire alarm control panel is designed to comply with the following standards: UL Standards UL 864 9th Edition: Automatic Fire Detector Alarm Manual Fire Alarm Waterflow Alarm Supervisory Releasing Device Service Releasing/Pre-Action Deluge Releasing/Agent Releasing Automatic Smoke Alarm, Non-coded and Master Coded Operation UUKL for Smoke Control UL 2572 for Mass Notification Systems NFPA Standards NFPA 13 - Standard for Installation of Sprinkler Systems NFPA 16 - Standard for Foam-Water Sprinkler and Foam Water Spray Systems NFPA 72 - National Fire Alarm Code: Central Station Fire Alarm Systems Auxiliary Fire Alarm Systems Proprietary Fire Alarm Systems Local Fire Alarm Systems Remote Station Fire Alarm Systems NFPA 13 Sprinkler NFPA 12A Halon 1301 NFPA 15 Water Spray NFPA 16 Foam Water NFPA 750 Water Mist NFPA 2001 Clean Agent NFPA 12 CO2 Carbon Dioxide NFPA 17 Dry Chemical/17A Wet Chemical Seismic Codes International Building Code IBC 2013 IBC 2009 IBC 2006 IBC 2003 IBC 2000 (Seismic) California Building Code CBC 2007 (Seismic) STANDARDS The E3 Series Control Panel is designed to comply with the following standards: UL Standards: UL 864 9th Edition UL 2572 for Mass Notification AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S1869, 2572 for Mass Notification FM: 3025415 MEA FDNY: 6175, COA #: 231-06-E CSFM: 7165-1703:0125 City of Chicago: Class 1, Class 2, High Rise City of Denver Approved The VMC Group, Reference Certificate of Compliance: VMA-45894-02C (Revision 1) ISO 9001 Certification GAMEWELL-FCI12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.©2016 by Honeywell International Inc. All rights reserved www.gamewell-fci.com 9021-60930 Rev. A page 1 of 3 Indoor Selectable-Output Speaker Strobes and Dual Voltage Evacuation Speakers for Ceiling Applications L-Series Indoor Ceiling Speaker Strobes and Dual Speakers APPROVED FM SIGNALING PENDING Description The L-Series indoor selectable-output speaker strobes and dual-voltage evacuation speakers offer a modern, aes- thetic plug-in design that reduce costly ground faults. The universal mounting plate can be used in ceiling applica- tions and its flexible design enables the Installer to easily perform the following: • Pre-wire mounting plates. • Dress the wires. • Confirm wiring continuity before the Installer plugs-in the speakers. In addition, this product includes a protective plastic cover which shields exposed speaker components and prevents nicked wires. These devices enable faster installations by providing instant feedback to the Installer to ensure the following: • The wiring is properly connected. • The rotary switches are set to the selected voltage and power settings. • The 7 field-selectable candela settings are configured for wall speaker strobes. The low total harmonic distortion of the SP speaker offers both high-fidelity and high-volume sound output so that it can be used in high ambient noise applications. L-Series makes installation easy To install the L-Series speakers or speaker strobe, do thefollowing: 1. Attach a universal mounting plate to a 4 x 4 x 2 1/8 inch backbox. Flush-mount applications do not require an extension ring. 2. Connect the notification appliance circuit or speaker wiring to the terminals on the mounting plate. 3. To attach the speaker or speaker strobe to the mount- ing plate, insert the product tabs into the mounting plate grooves. 4. Hinge the device into position to lock the product pins into the mounting plate terminals. 5. A catch temporarily holds the device in place until you secure the device with a captured mounting screw. L-Series Speaker and Speaker StrobeSpecifications Architectural/Engineering Specifications General The L-Series speaker and speaker strobes shall mount to a 4 x 4 x 2 1/8-inch backbox. A universal mounting plateshall be used for the mounting ceiling and wall products. The notification appliance circuit and amplifier wiring shallterminate at the universal mounting plate. Features • Includes a plug-in feature and protective cover to reduce ground faults. • Contains a universal mounting plate with an on-board shorting spring that is used to test the wiring continuity before an installation. • No extension ring required. • Field-selectable candela settings on ceiling units: - 15 - 30 - 75 - 95 - 115 - 150 - 177 • Uses an automatic selection of 12- or 24-volt operation at 15 and 30 candela. • Provides a rotary switch that simplifies the field selection of speaker voltage (25) and 70.7 VRMS) and the follow- ing power settings: – 1/4 watt – 1/2 watt – 1 watt – 2 watts • Offers speakers with both high-fidelity and high-volume sound output. • Compatible with the System Sensor synchronization protocol. • Supports electrical compatibility with the existing SpectrAlert and the SpectrAlert Advance products. • Designed with a tamper-resistant construction. • Built with an updated modern design. Ceiling Speaker Strobes GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118page 2 of 3 www.gamewell-fci.com 9021-60930 Rev. A UL Current Draw Data Table 1 lists the UL maximum strobe current draw. Table 2 lists the ceiling mount speaker sound outputs. Table 3 lists the ceiling-mount speaker strobe sound out-puts. L-Series Speaker and Speaker Strobe Specifications (Continued) Architectural/Engineering Specifications (Continued) General (Continued) Also, the L-Series speaker strobes, when used with the Sync•Circuit. Module accessory, shall be powered from anon-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When these devicesare used with the Sync•Circuit Module, either of the follow- ing may occur. • 12-volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts. • 24-volt rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. The Indoor L-Series products shall operate between 32° Fand 120°F from a regulated DC, or full-wave rectified, unfil- tered power supply. Speaker strobes shall have the follow-ing field-selectable candela settings: - 15 - 30 - 75 - 95 - 115- 150 - 177 SpeakerThe speaker shall be an L-Series model _______ dual- voltage transformer speaker capable of operating at 25.0or 70.7 nominal VRMS. It should be listed to UL Standard 1480 and shall be approved for fire protective service. Thespeaker shall have a frequency range of 400 to 4,000 Hzand shall have an operating temperature between 32°Fand 120°F. The speaker shall have power taps and voltagethat are selected by rotary switches. Speaker Strobe Combination The speaker strobe shall be an L-Series model__________ listed to UL Standard 1480 and UL Standard1971 and be approved for fire protective signaling sys-tems. The speaker shall be capable of operating at 25.0 or 70.7 nominal VRMS selected via rotary switch, and shallhave a frequency range of 400 to 4,000 Hz. The speaker shall have power taps that are selected by rotary switch.The strobe shall comply with the NFPA 72 requirements forvisible signaling appliances, flashing at 1 Hz over thestrobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Synchronization Module The module shall be a Sync•Circuit model MDL3 listed to UL Standard 464 and shall be approved for fire protectiveservice. The module shall synchronize SpectrAlert strobes at 1 Hz. The module shall mount to a 4 11/16 x 4 11/16 x 21/8-inch back box. The module shall also control two StyleY (Class B) circuits or one Style Z (Class A) circuit. Themodule shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will syn-chronize all the zones they control. The module shall not operate on a coded power supply. Physical Specifications Operating Temperature: 32°F to 120°F (0°C to 49°C) Humidity Range: 10 to 93% non-condensing Dimensions,Ceiling-Mount: Diameter Depth SPC Speaker 6.8 in, 173 mm 1.0 in, 25 mm With Surface Mount Backbox6.9 in, 176 mm 3.5 in, 89 mm SPSC Speaker Strobe 6.8 in, 173 mm 2.8 in, 73 mm With Surface Mount Backbox 6.9 in, 176 mm 5.37 in,136 mm Electrical/Operating Specifications Nominal Voltage (speakers): 25 Volts or 70.7 Volts(nominal) Maximum Supervisory Voltage (speakers): 50 VDC Strobe Flash Rate: 1 flash per secondNominal Voltage (strobes): Regulated 12 VDC or Regulated 24 VDC/FWR Operating Voltage Range(includes fire alarm panelswith built-in sync): 8 to 17.5 V (12 V nominal) or16 to 33 V (24 V nominal) Operating Voltage with MDL3 Sync Module: 8.5 to 17.5 V (12 V nominal)or 16.5 to 33 V (24 V nominal) Frequency Range Frequency Range: 400 to 4,000 Hz Power: ¼, ½, 1, 2 watts Candela 8-17.5 Volts 16-33 Volts FWRDC DC 15 87 41 60 30 153 63 86 75 NA 111 142 95 NA 134 164 115 NA 158 191 150 NA 189 228 177 NA 226 264 Table 1: UL Max. Strobe Current Draw (mA RMS) Setting UL Reverberant (dBA @10 ft) UL Anechoic (dBA @10 ft) 1/4 W 79 79 1/2 W 82 82 1 W 85 85 2 W 88 88 Table 2: Ceiling-Mount Speaker Sound Output Setting UL Reverberant (dBA @10 ft) UL Anechoic (dBA @10 ft) 1/4 W 77 77 1/2 W 80 80 1 W 83 83 2 W 86 86 Table 3: Ceiling-Mount Speaker Strobe Sound Output GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 www.gamewell-fci.com 9021-60930 Rev. A page 3 of 3 Dimensions Figure 1 shows the speaker dimensions. Figure 2 shows the speaker dimensions. Surface Mounting Figure 3 illustrates the ceiling-mount speaker and speaker strobes with the SBBCR/SBBCWL surface mount back-box. Figure 1 Speaker Dimensions Figure 2 Speaker Dimensions Figure 3 Ceiling-Mount Speaker and Speaker Strobe with SBBCRL/SBBCWL Surface Mount Backbox L-Series Ordering Information SpectrAlert Speakers and Strobes Ceiling Mount Part Number Description SPCWL White Speaker only SPCRL Red Speaker only SPSCWL White Speaker Strobe SPSCRL Red Speaker Strobe SPSCWL-P Plain, Speaker Strobe SPSCWL-SP Fuego, Speaker Strobe SPSCWL-CLR-ALERT Alert, Speaker Strobe,Clear Lens Accessories SBBCWL White, Universal Ceiling Surface Mount Back Box SBBCRL Red, Universal Ceiling Surface Mount Back Box TRC-2W White, Universal Ceiling Trim Ring TRC-2 Red, Universal Ceiling Trim Ring GAMEWELL-FCI12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. ©2010 by Honeywell International Inc. All rights reserved.www.gamewell-fci.com 9021-60521 Rev. B page 1 of 2 HPFF8 NAC Expander/Power SupplyDescription The Gamewell-FCI, HPFF8 is a Notification Appliance Cir- cuit (NAC) expansion panel designed to extend the power capabilities of existing NACs and provide power for the auxiliary devices. The HPFF8 connects to any 12 or 24V Fire Alarm Control Panel (FACP) or stand alone. The HPFF8 is available in 8.0 amps. It provides regulated and filtered 24VDC power to each of the four NACs and an auxiliary output. The NAC outputs are rated at 3.0 amps each (the total output cannot exceed 8.0 amps). The auxil- iary output is rated at 2.0 amps. This output is continuously supplied, even in alarm, and therefore must be taken into account for power supply loading and battery size calcula- tions. The NAC outputs may be configured as any of the follow- ing: • Four Class B (Style Y) • Two Class A (Style Z) • Two Class B and one Class A • Four Class A with the optional HPP31076 Class A adapter installed These power supplies contain an internal Battery charger capable of charging up to 26.0 amp-hour (AH) batteries. The HPFF8 is mounted in lockable wall cabinet units that can accommodate up to two (2), 18AH batteries. A multi- pack option allows for up to four chassis mount units installed in a single lockable SBB-D4 enclosure. These chassis mount units have a "CM" suffix, HPFF8CM and can accommodate two 12AH batteries. Power supplies are available in either 120VAC/60 Hz or 240VAC/50 Hz. One of the most challenging aspects of a retrofit applica- tion is locating the existing End-of-Line (EOL) resistor. In these applications that have EOL values, other than the 3.9k normally used with the HPFF8, a single resistor matching the existing EOL can be used as a reference for all the outputs. This feature speeds the installation and the system checkout, because the actual EOL does not need to be located and changed in the circuit. The reference resistor must be within the range of 1.9k to 25k. Features • Four (4) supervised notification application circuits (NACs) capable of supplying +24VDC at 3.0 amp maximum each • NAC output circuits may be configured as any of the following: - Four Class B (Style Y) - Two Class B & one Class A - Two Class A (Style Z) - Four Class A with the optional HPP31076 Class A adapter installed • Four field-programmable operational modes • 2.0 amp auxiliary continuously supplied output • Two (2) fully supervised input/output control circuits • Temporal coding and sync protocols compatible with the following notification appliance brands: - System Sensor - Faraday - Gamewell - Amseco - Cooper-Wheelock - Gentex • Supervised AC input, battery voltage, auxiliary output, charger, and earth ground faults • Trouble indication for supervision of the following: - NAC circuits - Auxiliary output - AC input - Charger - Battery voltage - Open contacts in the initiat- ing device signal inputs (for FACP trouble notification)- Earth ground faults by individual status LED's • Separate Trouble and AC Fail Form-C relay Contacts HPFF8 An ISO 9001-2000 Company 7315-1637:0102 SIGNALING S24562 FM APPROVED GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-71189021-60521 Rev. B page 2 of 2 www.gamewell-fci.com Features (Continued) • The Trouble Form-C relay contacts selectable for imme- diate or a 2 hour delay with AC failure • 26 AH battery charger capability; the wall cabinet supports two 12V 18AH batteries, while the multi-pack equipment cabinets supports two 12V 12AH batteries. • NAC Overload protection and indication • Up to four chassis mount units (HPFF8CM) can be installed in the SBB-D4 backbox • Wall mount units can be configured to internally house the following: - one AOM-2SF single control module - one AOM-2R single relay module Specifications Primary Input Power:120VAC/60Hz, 3.6A or 220VAC/50Hz, 1.5A Secondary Power:24 volt operation: two (2), 7-24 AH batteries Battery Charging Capacity:Up to 26 AH batteries mounted Battery Space: HPFF8 Cabinet:Up to two 18AH batteries SBB-D4 Cabinet:Up to two 12AH batteries per supply Total Output Power:8.0A max Standby Current: 0.030 A Auxiliary Power Output:0.15A under all conditions 2.0A if load is removed dur-ing operation (external relay or AC Fail Relay is required) Specifications (Continued) NAC Output Ratings:24VDC fully regulated, 3.0A max per circuit (8.0A total) End-of-Line Resistor Range: 2K to 25k ohm, ½ watt Common Trouble Relay/AC Fail Relay:2.0A at 28VDC or 120VAC Input Control Circuit:16-30VDC @ 5mA min. Temperature Rating:32°F to 120°F (0°C to 49°C Relative Humidity:10% to 93% non-condensing Cabinet Dimensions: HPFF8 Cabinet:16.65” W x 19.0” H x 5.2” D (42.29 W x 48.26 H 13.23 D cm) SBB-D4 Cabinet:24” W x 45.9” H x 5.15” D (60.96 W x 116.52 H x 13.1D cm) Ordering Information Part Number Description HPFF8 8A fire rated power supply operating at 120VAC/60 Hz. Unit includes red enclosure with HPP lock and key HPFF8CM 8A fire rated power supply - chassis mounted operating at 120VAC/60 Hz. Unit includes mounting hardware for installation in the SBB-D4 enclosure HPFF8E 8A fire rated power supply operating at 240VAC/50 Hz HPFF8CME 8A fire rated power supply chassis mounted operating at 240VAC/50 Hz HPP31076 Class A (Style Z) NAC module FCI-VDR-D4 Vented door, PK-625 lock and key for SBB-D4 backbox, black SBB-D4 Backbox, accepts up to 4 chassis, black Standby 0.075 A Alarm 2.578 A Qty Draw Non-Alarm Qty Draw Alarm 1 x 0.07500 0.07500 1 x 0.20600 0.20600 2 x 0.00000 0.00000 2 x 0.05400 0.10800 2 x 0.00000 0.00000 2 x 0.07100 0.14200 5 x 0.00000 0.00000 5 x 0.13700 0.68500 0 x 0.00000 0 x 0.18500 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0.00000 0.93500 1 x 0.00000 0.00000 1 x 0.05400 0.05400 1 x 0.00000 0.00000 1 x 0.07100 0.07100 4 x 0.00000 0.00000 4 x 0.13700 0.54800 0 x 0.00000 0 x 0.18500 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0.00000 0.67300 4 x 0.00000 0.00000 4 x 0.05400 0.21600 0 x 0.00000 0 x 0.07100 4 x 0.00000 0.00000 4 x 0.13700 0.54800 0 x 0.00000 0 x 0.18500 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0.00000 0.76400 0 x 0.00000 0 x 0.05400 0 x 0.00000 0 x 0.07100 0 x 0.00000 0 x 0.13700 0 x 0.00000 0 x 0.18500 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0.00000 0.00000 0 x 0.00000 0 x 0.03000 0 x 0.03700 0 x 0.00850 0 x 0.02000 0 x 0.04000 0 x 0.05000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0.00000 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000Other compatible devices 7. Compatible Devices not listed 0.075 6. Auxiliary Power PR-3 FIRERAY5000 CO1224TR E3SMRCO/E3SA Auxiliary Device Total Alarm Load: 3. L3 SPSCWL15 TB4 Totals (Max 2 Amps): SPSCWL115 SPSCWL15 SPSCWL30 SPSCWL75 NAC #4 Totals (Max 3 Amps): Other compatible devices Other compatible devices Total Non-Alarm Load: SPSCWL115 2. L2 NAC #1 Totals (Max 3 Amps): Secondary Alarm CurrentSecondary Non-Alarm Current 1. System Modules 1. L1 HPFF8 Main Circuit Board 2.578 System Current Draw - HPFF8 New Total Current SPSCWL115 SPSCWL30 NAC #2 Totals (Max 3 Amps): Device SPSCWL15 SPSCWL75 NAC #3 Totals (Max 3 Amps): SPSCWL115 4. . SPSCWL15 SPSCWL30 SPSCWL75 SPSCWL30 SPSCWL75 Protected Premises:Date:6.30.2021 Address: City:State:UT Zip:83460 Prepared By:Phone:801.468.8300 Address:Email: City:State:UT Zip:84115 Secondary Load Requirements 2.93 Amp Hours Total (AH) 1.80 0.64 2.44 x 1.2 2.93 AH 8 Amp Hours TRUE 1481 S Major Street Office@nelsonfire.com Salt Lake City Secondary Power Requirements Manwaring Center - BYU-Idaho 525 South Center Street Rexburg Nelson Fire Systems HPFF8 Power Supply Time (hours) Required Standby Time 24 hoursx Total Secondary Load from the calculation table below. 0.075 A Secondary Load Requirements Total Secondary Load Secondary Alarm Load x2.578 A Required Alarm Time (hours) 0.250 hours Current Draw Secondary Standby Load Select batteries from the list below. Battery Selection 8.0 AH BAT-1270 Battery (12 volt) Derating factor Page 2 of 131 Battery Distribution Chart Comments 5.07 2.16 0.77 Secondary Alarm Load (AH) * Derating FactorSecondary Alarm Load Shows amp-hour distribution of your selections. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). Spare Battery Capacity Secondary Standby Load 2. Selected battery size meets secondary load requirements. Battery Selection (AH) - Secondary Load Requirements (AH) Secondary Standby Load (AH) * Derating Factor 1. Batteries will fit in the FACP cabinet. Spare Battery Capacity 63% Secondary Standby Load 27% Secondary Alarm Load 10% Spare Battery Capacity Secondary Standby Load Secondary Alarm Load Page 3 of 131 Honeywell Online Tools For Fire Version 2.0.14 PROJECT DETAILS Project Name : Manwaring Center Remodel 2021 - BYU-Idaho Project Code : Project Location : 525 South Center Street, Rexburg, Idaho, 83460 PREPARED BY Nelson Fire Systems 1481 S Major St, Salt Lake City, Utah, 84115 Voltage Drop Calculations POWER SOURCE : FF8 New  MODEL NUMBER : HPFF8 BRAND : HPP CLASS B   20.4 VOLTS DC POWER CIRCUIT: L1   3 Amps   14 AWG   9 DEVICES   25.43 % (0.763) AMPS USED 4.54 % (0.926) VOLTAGE DROP POWER SOURCE : FF8 New  MODEL NUMBER : HPFF8 BRAND : HPP CLASS B   20.4 VOLTS   DC POWER CIRCUIT: L2   3 Amps   14 AWG   6 DEVICES   18.27 % (0.548) AMPS USED 9.37 % (1.911) VOLTAGE DROP #MODEL CANDELA PATTERN VOLUME TONE CURRENT (amps) DISTANCE FROM PREVIOUS DEVICE (Ft) 12 AWG 14 AWG 16 AWG 18 AWG 1 SPSCWL 30 0.063 395 19.530 19.019 18.201 16.902 2 SPSCWL 75 0.111 30 19.472 18.926 18.053 16.667 3 SPSCWL 75 0.111 40 19.412 18.831 17.901 16.425 4 SPSCWL 15 0.041 35 19.375 18.772 17.807 16.276 5 SPSCWL 75 0.111 180 19.214 18.517 17.401 15.630 6 SPSCWL 75 0.111 40 19.196 18.489 17.356 15.558 Voltage Drop 1.204 1.911 3.044 4.842 #MODEL CANDELA PATTERN VOLUME TONE CURRENT (amps) DISTANCE FROM PREVIOUS DEVICE (Ft) 12 AWG 14 AWG 16 AWG 18 AWG 1 SPSCWL 75 0.111 70 20.185 20.059 19.857 19.537 2 SPSCWL 75 0.111 30 20.106 19.934 19.658 19.221 3 SPSCWL 30 0.063 35 20.030 19.813 19.466 18.915 4 SPSCWL 30 0.063 35 19.963 19.706 19.296 18.645 5 SPSCWL 75 0.111 35 19.905 19.613 19.148 18.410 6 SPSCWL 75 0.111 30 19.868 19.555 19.055 18.263 7 SPSCWL 75 0.111 40 19.837 19.506 18.977 18.138 8 SPSCWL 15 0.041 30 19.827 19.490 18.952 18.098 9 SPSCWL 15 0.041 60 19.817 19.474 18.927 18.058 Voltage Drop 0.583 0.926 1.473 2.342 Page: 1 07/07/2021 11:45:37 AM POWER SOURCE : FF8 New  MODEL NUMBER : HPFF8   BRAND : HPP   CLASS B   20.4 VOLTS   DC POWER CIRCUIT: L3   3 Amps   14 AWG   8 DEVICES   22.6 % (0.678) AMPS USED   18.66 % (3.806) VOLTAGE DROP #MODEL CANDELA PATTERN VOLUME TONE CURRENT (amps) DISTANCE FROM PREVIOUS DEVICE (Ft) 12 AWG 14 AWG 16 AWG 18 AWG 1 SPSCWL 75 0.111 750 18.356 17.156 15.234 12.183 2 SPSCWL 75 0.111 70 18.196 16.903 14.831 11.542 3 SPSCWL 75 0.111 30 18.141 16.816 14.692 11.321 4 SPSCWL 75 0.111 30 18.099 16.750 14.587 11.154 5 SPSCWL 15 0.041 25 18.075 16.713 14.528 11.059 6 SPSCWL 75 0.111 35 18.048 16.670 14.459 10.950 7 SPSCWL 15 0.041 110 18.012 16.612 14.367 10.804 8 SPSCWL 15 0.041 70 18.000 16.594 14.338 10.758 Voltage Drop 2.400 3.806 6.062 9.642 Page: 2 07/07/2021 11:45:37 AM MANWARING CENTER REMODEL BYU - IDAHO FIRE ALARM SYSTEM JPK XXXX TDT (ARCH C) 1/16" = 1' XXXX XXXX MA N W A R I N G C E N T E R R E M O D E L BY U - I D A H O 52 5 S O U T H C E N T E R S T R E E T RE X B U R G , I D A H O 8 3 4 6 0 FI R E A L A R M S Y S T E M PROJECT COVER SHEET FA-C-01 NELSON FIRE SYSTEMS DRAWN BY: DESIGNED BY: APPROVED BY: DATE: SCALE: PROJECT NO: REVISION NO: DRAWING NAME: NO T E : NF S D R A W I N G S A R E B A S E D O N T H E P R O J E C T AR C H I T E C T U R E / E N G I N E E R ( A / E ) P L A N S A N D SP E C I F I C A T I O N S F U R N I S H E D T O N F S . A / E I S S O L E L Y RE S P O N S I B L E ( N O T N F S ) F O R T H E T Y P E , S I Z E , LO C A T I O N , A N D S U I T A B I L I T Y O F A L L F I R E A L A R M S , CO N T R O L P A N E L S , A N D O T H E R D E V I C E S S H O W N O N TH E A / E P L A N S . N F S D R A W I N G S A R E T O S H O W O N L Y TH E W I R I N G D I A G R A M S B E T W E E N F I R E A L A R M DE V I C E S A N D C O N T R O L P A N E L S . N F S I S N O T RE S P O N S I B L E F O R T H E I N F O R M A T I O N S H O W N O N T H E A/ E P L A N S . NELSON FIRE SYSTEMS PAGE: INDEX OF DRAWINGS PAGE 1 2 3 FA-C-01 FA-R-01 FA-1-01 SHEET #LEVEL PROJECT COVER SHEET / INDEX OF DRAWINGS FIRE ALARM BUILDING RISER DIAGRAM / MATRIX LEVEL 1 DEVICE SCHEDULE COUNTS SPEAKER/STROBE- CEILING SPSCWL DESCRIPTION FIRE ALARM CONTROL UNIT EXISTING TRANPSONDER PANEL EXISTING SS FACU TRAN C 4 SQ. 2-1/8" DEEP BOX MINIMUM w/1-1/2" EXT. RING EXISTING TO REMAIN EXISTING TO REMAIN PART NUMBER MOUNTING REQUIREMENTSYMBOL 23 18 SHEET CONTENTS NOTIFICATION CIRCUITS SPEAKER ONLY- CEILING SPCWLSC 4 SQ. 2-1/8" DEEP BOX MINIMUM w/1-1/2" EXT. RING. VOICE PANEL EXISTINGINX EXISTING TO REMAIN MANWARING CENTER 2021 C.DWG 6/29/2021 LEVEL 1 DO NOT USE SHIELDED WIRE ON ADDRESSABLE CIRCUIT JPK XXXX TDT (ARCH C) 1/16" = 1' XXXX XXXX MA N W A R I N G C E N T E R R E M O D E L BY U - I D A H O FI R E A L A R M R I S E R D I A G R A M / M A T R I X 52 5 S O U T H C E N T E R S T R E E T RE X B U R G , I D A H O 8 3 4 6 0 FI R E A L A R M S Y S T E M FIRE RISER DIAGRAM / MATRIX FA-R-01 NELSON FIRE SYSTEMS DRAWN BY: DESIGNED BY: APPROVED BY: DATE: SCALE: PROJECT NO: REVISION NO: DRAWING NAME: NO T E : NF S D R A W I N G S A R E B A S E D O N T H E P R O J E C T AR C H I T E C T U R E / E N G I N E E R ( A / E ) P L A N S A N D SP E C I F I C A T I O N S F U R N I S H E D T O N F S . A / E I S S O L E L Y RE S P O N S I B L E ( N O T N F S ) F O R T H E T Y P E , S I Z E , LO C A T I O N , A N D S U I T A B I L I T Y O F A L L F I R E A L A R M S , CO N T R O L P A N E L S , A N D O T H E R D E V I C E S S H O W N O N TH E A / E P L A N S . N F S D R A W I N G S A R E T O S H O W O N L Y TH E W I R I N G D I A G R A M S B E T W E E N F I R E A L A R M DE V I C E S A N D C O N T R O L P A N E L S . N F S I S N O T RE S P O N S I B L E F O R T H E I N F O R M A T I O N S H O W N O N T H E A/ E P L A N S . NELSON FIRE SYSTEMS PAGE: LEVEL 1- SMOKE DETECTORS LEVEL 1- HEAT DETECTORS LEVEL 1- PULL STATIONS LEVEL 1- TAMPER SWITCH LEVEL 1- WATERFLOW SWITCH LOSS OF POWER ANY PANEL OR NAC LOW BATTERY CONDITIONS OPEN CIRCUIT CONDITIONS GROUND FAULTS FACP ANNUNCIATION NOTIFICATION FIRE SAFETY CONTROL REPORTING SYSTEM INPUTS SYSTEM OUTPUTSFIRE ALARM INPUT/OUTPUT MATRIX AL A R M S I G N A L T O F I R E A L A R M D I S P L A Y SU P E R V I S O R Y S I G N A L T O F I R E A L A R M D I S P L A Y TR O U B L E S I G N A L T O F I R E A L A R M D I S P L A Y BU I L D I N G S P E A K E R / S T R O B E S HV A C S H U T - D O W N FI R E / S M O K E D A M P E R S RE L E A S E M A G N E T I C D O O R H O L D E R S AL A R M S I G N A L T O M O N I T O R I N G C O M P A N Y SU P E R V I S O R Y S I G N A L T O M O N I T O R I N G C O M P A N Y TR O U B L E S I G N A L T O M O N I T O R I N G C O M P A N Y MANWARING CENTER 2021 R.DWG 6/29/2021 EXISTING VOICE PANEL FACU EXISTING EXISTING BATTERY CABINET EXISTING TRANSPONDER EXISTING TRANSPONDER 1/2W SP1-1 1/2W SP1-2 1/2W SP1-3 1/2W SP1-4 1/2W SP1-5 1/2W SP1-6 1/2W SP1-7 1/2W SP1-8 1/4W SP1-9 1 PAIR #14'S TWISTED SHIELDED SPEAKER CIRCUITL1-1 75cd L1-2 75cd L1-3 30cd L1-4 30cd L1-5 75cd L1-6 75cd L1-7 75cd L1-8 15cd 1/2W SP1-24 1/2W SP1-23 1/4W SP1-22 1/4W SP1-21 1/4W SP1-20 1/4W SP1-19 1/4W SP1-18 1/4W SP1-17 1/2W SP1-16 1/2W SP1-15 1/2W SP1-14 1/2W SP1-13 L2-6 75cd L2-5 75cd L2-4 15cd L2-3 75cd L2-2 75cd L2-1 30cd 6 #14'S (3) STROBE CIRCUITS SS CSC S CSCSCSCSC SS CSSCSSC SS C SS CSSCSSCSSC SS C SS C SS C SS CSSC SS C SS C SS CSCSCSCSC S CSC SS C SS CSSC SS C SS C SS C 1/4W SP1-10 1/4W SP1-11 1/2W SP1-12 L1-9 15cd 1/2W SP1-25 1/4W SP1-26 1/4W SP1-27 1/4W SP1-28 1/4W SP1-29 1/2W SP1-30 1/2W SP1-31 1/2W SP1-32 1/2W SP1-33 1/2W SP1-34 1/2W SP1-35 1/2W SP1-36 1/4W SP1-37 1/4W SP1-38 1/4W SP1-39 1/2W SP1-40 1/2W SP1-41 L3-1 75cd L3-2 75cd L3-3 75cd L3-4 15cd L3-5 15cd L3-6 75cd L3-7 15cd L3-8 15cd SPCWL - CEILING SPEAKER ONLY TO NEXT DEVICESPEAKER CKT OUTIN SPSCWL - CEILING SPEAKER STROBE TO NEXT DEVICESPEAKER CKT OUTIN TO NEXT DEVICE(+) (-)STROBE CIRCUIT IN OUT(+) (-) DEVICE LEGEND SS SPEAKER/STROBE- CEILING DESCRIPTIONCOUNTSSYMBOL 23 S SPEAKER ONLY- CEILING18 C C E.O.L. 3.9K E.O.L. 4.7K E.O.L. 3.9K E.O.L. 3.9K S CSCSCSCSCSC AK XXXX TDT (ARCH C) 1/16" = 1' XXXX XXXX MA N W A R I N G C E N T E R R E M O D E L BY U - I D A H O 52 5 S O U T H C E N T E R S T R E E T RE X B U R G , I D A H O 8 3 4 6 0 FI R E A L A R M S Y S T E M MAIN LEVEL NOTIFICATION FA-1-01 SYSTEM NOTES: TO EXISTING CLOSEST TRANSPONDER LOCATED ON LEVEL 1 ADDED TO MEET CODE (6/18/21) REVISION NOTES: 25'10'50' W E S N 1 Z NELSON FIRE SYSTEMS DRAWN BY: DESIGNED BY: APPROVED BY: DATE: SCALE: PROJECT NO: REVISION NO: DRAWING NAME: NO T E : NF S D R A W I N G S A R E B A S E D O N T H E P R O J E C T AR C H I T E C T U R E / E N G I N E E R ( A / E ) P L A N S A N D SP E C I F I C A T I O N S F U R N I S H E D T O N F S . A / E I S S O L E L Y RE S P O N S I B L E ( N O T N F S ) F O R T H E T Y P E , S I Z E , LO C A T I O N , A N D S U I T A B I L I T Y O F A L L F I R E A L A R M S , CO N T R O L P A N E L S , A N D O T H E R D E V I C E S S H O W N O N TH E A / E P L A N S . N F S D R A W I N G S A R E T O S H O W O N L Y TH E W I R I N G D I A G R A M S B E T W E E N F I R E A L A R M DE V I C E S A N D C O N T R O L P A N E L S . N F S I S N O T RE S P O N S I B L E F O R T H E I N F O R M A T I O N S H O W N O N T H E A/ E P L A N S . NELSON FIRE SYSTEMS PAGE: 801-468-8300 MANWARING CENTER 2021.DWG 6/29/2021 DEVICE LEGEND SS SPEAKER/STROBE- CEILING DESCRIPTIONCOUNTSSYMBOL 23 S SPEAKER ONLY- CEILING18 ADDED OR REMOVED DEVICES (ADJUSTMENT ACCOUNTED FOR IN COUNTS ABOVE) ADDED SPEAKER/STROBE- CEILING2SS DESCRIPTIONCOUNTS SYMBOL WIRE SCHEDULE NOTE DESCRIPTION WIRES A B SPEAKER CIRCUIT 1 PAIR #14'S TWISTED/SHIELDED STROBE CIRCUIT 2 #14'S 1. INSTALLATION SHALL COMPLY WITH NEC, NFPA 72 AND OTHER APPLICABLE CODES AS REQUIRED BY THE LOCAL AHJ. CLASS "B" WIRING IS REQUIRED. 2. WIRING DEPICTED ON THESE PLAN IS SCHEMATIC - ACTUAL WIRE LOCATIONS MAY DIFFER FROM THESE PLANS. WIRING SHALL BE PERFORMED AS ACTUAL BUILDING CONSTRUCTION CONDITION ALLOW AND TO MINIMIZE PENETRATIONS THROUGH AREA SEPARATION WALLS AND FIRE WALLS. THE USE OF A RACEWAY IS PERMITTED AS LONG AS NO 110V OR HIGHER CABLES ARE IN THE RACEWAY. 3. POWER-LIMITED (PL) AND NONPOWER-LIMITED (NPL) CKT WIRING MUST REMAIN SEPARATED IN CABINET. ALL PL CKT WIRING MUST REMAIN AT LEAST 0.25" AWAY FROM ANY NPL CKT. FURTHERMORE, ALL PL AND NPL CKT WIRING MUST ENTER AND EXIT THE CABINET THROUGH A DIFFERENT KNOCKOUT AND/OR SEPARATE CONDUIT. 4. ONLY FIRE ALARM WIRING IS PERMITTED IN FIRE ALARM CONDUIT. DO NOT USE 110V OR HIGHER IN FIRE ALARM CONDUIT. 5. SMOKE DETECTORS SHALL BE INSTALLED AND COVERED UNTIL TESTING AND FINAL INSPECTION ARE COMPLETED. DO NOT INSTALL SMOKE DETECTORS UNTIL BUILDING IS CLEAN. 6. LOCATE SMOKE DETECTORS A MINIMUM OF THREE (3) FEET FROM MECHANICAL DIFFUSERS. 7.DO NOT USE SHIELDED WIRE ON ADDRESSABLE CKTS. 8. A SMOKE DETECTOR MUST BE IN EVERY ROOM WITH A FIRE ALARM CONTROL UNIT OR POWER SUPPLY. 9. FIRE ALARM CKTS NEED TO BE FREE OF GROUNDS, FAULTS, AND SHORTS PRIOR TO CONNECTION TO FIRE ALARM EQUIPMENT. 10.DEDICATED 120 VAC CKTS SHALL BE MARKED AS "FIRE ALARM CKT" AND BE ACCESSIBLE ONLY TO PERSONNEL. DISCONNECTS FOR THESE CKTS WILL BE RED IN COLOR AND THEIR LOCATION WILL BE NOTED AT EACH CONTROL UNIT. 11.WHEN MORE THAN TWO VISUAL NOTIFICATION APPLIANCES ARE IN THE SAME ROOM OR ADJACENT SPACE WITHIN THE FIELD OF VIEW, THEY SHALL BE SYNCHRONIZED. 12.BUILDING CONSTRUCTION TYPE: IIB 12.1. MAINTAIN PATHWAY SURVIVABILITY LEVEL 0 GENERAL NOTES: KEYPLAN RESTROOMS OUT OF SCOPE PROTECT AND/OR REESTABLISH CONTINUITY TO ALL FIRE ALARM DEVICES IN AREA 127 STUDENT SUPPORT/MENTOR 124A MENTORING 124B MENTORING 124C MENTORING 124D MENTORING 124E MENTORING 124F MENTORING 126 TRAINING 1T CORRIDOR 120 GREETING 1J CORRIDOR 117C118B STORAGE 118A KITCHEN 129L OFFICE 129M OFFICE 129K STORAGE 129J OFFICE 129H OFFICE 129G OFFICE 129F STORAGE 129E OFFICE 129D OFFICE 129C OFFICE 129B OFFICE 129 CAMPUS RECREATION 129N STORAGE 129A LOBBY 32 CORRIDOR STORAGECHAIR 117A SEMINAR 1X CORRIDOR 120A COLLABORATION 120C INFO SS C S C S C SP1-391/4W S C SP1-381/4W S C SP1-371/4W S CSP1-361/2W S C SP1-351/2W SP1-121/2WL1-915cd SS CSP1-161/2WL2-415cd SS C SP1-241/2WL2-675cd SS C SP1-231/2WL2-575cd SS CSP1-331/2WL3-515cd SS CSP1-341/2WL3-675cd SS C SP1-311/2WL3-375cd SS C SP1-301/2WL3-275cd SS C SP1-251/2WL3-175cd SS C SP1-411/2WL3-815cd SS C SP1-11/2WL1-175cd SS C SP1-31/2WL1-330cd SS CSP1-51/2WL1-575cd SS C SP1-41/2WL1-430cd SS CSP1-71/2WL1-775cd SS C SP1-81/2WL1-815cd SP1-111/4W SS C SP1-321/2WL3-415cd SP1-291/4W SP1-281/4W SP1-271/4W SP1-261/4W SS (E) S C S C S C S C S CSP1-101/4W S CSP1-91/4W SS C SP1-401/2WL3-715cd SP1-221/4W SP1-211/4W SP1-201/4W SP1-191/4W SP1-181/4W SP1-171/4W SS CSP1-61/2WL1-675cd SS C SP1-21/2WL1-275cd 1 A,(3)B SS C SP1-151/2WL2-375cd SS C SP1-141/2WL2-275cd SS C SP1-131/2WL2-130cd 1 A,(3)B TRAN(E) C C C TRANSPONDER- EXISTING E.O.L. 3.9KE.O.L. 4.7K E.O.L. 3.9K E.O.L. 3.9K S C S C S C S C S C S C