Loading...
HomeMy WebLinkAboutFIRE SPRINKLER REVIEW - 19-00577 - Ollie Manor - New MFR Hepworth 8-Plex – Rexburg 1 of 1 STATE FIRE MARSHAL IDAHO DEPARTMENT OF INSURANCE 700 W. State Street, 3rd Floor P.O. Box 83720 Boise, ID 83720-0043 (208) 334-4370 | www.doi.idaho.gov/sfm PLAN REVIEW FOR FIRE SPRINKLER SYSTEMS PLANS RECEIVED: October 29, 2020 APPROVED: November 12, 2020 REVIEWED BY: Javier Cervantes, ISFM Fire Plan Reviewer PROJECT: Hepworth 8-Plex STREET ADDRESS: 119 N. 1st E. CITY: Rexburg AHJ: Madison Fire Department SPRINKLER CONTRACTOR: Phoenix Fire Protection 4130 Airport Road Nampa, ID 83687 IDAHO LICENSE: FPSC-108 CONTACT NAME: Teri Cruickshank teri@phoenixfp.com PHONE NO: (208) 468-9115 SYSTEM DESIGNED BY: Dennis Apple dennis@phoenixfp.com PHONE NO: (208) 346-2853 TYPE OF SYSTEM: NFPA 13R HEAD COUNT: 44 TOTAL SYSTEMS: 1 OCCUPANCY CLASSIFICATION: R-2 CONSTRUCTION TYPE: V B AREA SQUARE FOOTAGE: 4,842 SCOPE OF WORK: This will be a new 8-plex designed to NFPA 13R. PLAN REVIEW COMMENTS: Approved with the following comment: 1. Pipe for FDC shall be at least the size of the FDC or Riser whichever is less. (NFPA 13R, 6.11) Approval of shop drawings is not intended to imply waiver or modification of any requirements of the Idaho State Statutes or Rules, International Fire Code, NFPA Standards or any other applicable criteria. It is acknowledged that backflow preventer is installed per the demand of the local water purveyor. The State Fire Marshal’s Office and its personnel does not take any responsibility for the back flow device.