PLAN REVIEW FOR FIRE SPRINKLER SYSTEMS
PLANS RECEIVED: October 29, 2020 APPROVED: November 12,
2020
REVIEWED BY: Javier Cervantes, ISFM Fire Plan Reviewer
PROJECT: Hepworth 8-Plex
STREET ADDRESS: 119 N. 1st E. CITY: Rexburg
AHJ: Madison Fire Department
SPRINKLER CONTRACTOR: Phoenix Fire Protection
4130 Airport Road
Nampa, ID 83687
IDAHO LICENSE: FPSC-108
CONTACT NAME: Teri Cruickshank
teri@phoenixfp.com
PHONE NO: (208) 468-9115
SYSTEM DESIGNED BY: Dennis Apple
dennis@phoenixfp.com
PHONE NO: (208) 346-2853
TYPE OF SYSTEM: NFPA 13R HEAD COUNT: 44
TOTAL SYSTEMS: 1 OCCUPANCY CLASSIFICATION: R-2
CONSTRUCTION TYPE: V B AREA SQUARE FOOTAGE: 4,842
SCOPE OF WORK: This will be a new 8-plex designed to NFPA 13R.
PLAN REVIEW COMMENTS: Approved with the following comment:
1. Pipe for FDC shall be at least the size of the FDC or Riser whichever is less. (NFPA
13R, 6.11)
Approval of shop drawings is not intended to imply waiver or modification of any requirements of the Idaho State Statutes or
Rules, International Fire Code, NFPA Standards or any other applicable criteria.
It is acknowledged that backflow preventer is installed per the demand of the local water purveyor. The State Fire Marshal’s
Office and its personnel does not take any responsibility for the back flow device.