Loading...
HomeMy WebLinkAboutLOAD SHORT FORM - 21-00838 - 2361 W 860 S - New SFRCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Oct-25 17:17:07 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF16B7 princeton.rup Calc = MJ8 House faces: N SF16B7Job:Load Short Form Date:Entire House Vince ByramBy: High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com Project Information Cody PuzeyFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Information InfiltrationClgHtg SimplifiedMethod89-6Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1476Design TD (°F) H-Daily range 5050Inside humidity (%) -3162Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Goodman Mfg.Make Goodman Mfg. Trade GOODMAN Trade GOODMAN, JANITROL, AMANA DISTI... Model GMH950703BX Cond GSX130241C* AHRI ref 2002183 Coil Capf3030bx AHRI ref 4765510 Efficiency 95 AFUE Efficiency 11.0 EER, 13 SEER Heating input Btuh69000 Sensible cooling Btuh16100 Heating output Btuh52440 Latent cooling Btuh6900 Temperature rise °F62 Total cooling Btuh23000 Actual air flow cfm920 Actual air flow cfm767 Air flow factor cfm/Btuh0.027 Air flow factor cfm/Btuh0.095 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Room2 52 0 0 0 0 Room3 150 2249 312 61 30 Room4 250 3514 1126 95 107 Room5 242 2129 1011 58 96 Room6 169 2805 924 76 88 Room7 50 589 98 16 9 Room8 154 2146 532 58 50 Room9 132 2793 573 76 54 Room10 35 898 241 24 23 Room11 82 3287 565 89 54 Room1 604 13605 2696 368 256 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Oct-25 17:17:07 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 2 S:\High Country\Wrightsoft\SF16B7 princeton.rup Calc = MJ8 House faces: N Entire House d 1920 34014 8081 920 767 Other equip loads 1821 335 Equip. @ 0.94 RSM 7911 Latent cooling 0 TOTALS 1920 35835 7911 920 767 2021-Oct-25 17:17:07 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF16B7 princeton.rup Calc = MJ8 House faces: N SF16B7Job:Building Analysis Date:Entire House Vince ByramBy: High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com Project Information Cody PuzeyFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) SimplifiedMethod)H(34-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Doors Ceilings Floors Infiltration Ventilation % of loadBtuhBtuh/ft²Component 30.5109234.9Walls 15.9570122.8Glazing 2.590022.0Doors 5.017771.5Ceilings 12.846003.93.9Floors 28.2101144.0Infiltration 00Ducts 00Piping 00Humidification 5.11821Ventilation0Adjustments 100.035835Total Cooling Walls Glazing Doors Ceilings Other Infiltration Ventilation % of loadBtuhBtuh/ft²Component 12.510490.5Walls 56.2472818.9Glazing 2.62195.4Doors 11.79820.8Ceilings 1.61340.1Floors 11.59690.4Infiltration 00Ducts 4.0335Ventilation 00Internal gains 00Blower 0Adjustments 100.08416Total Latent Cooling Load = 0 Btuh Overall U-va lue = 0.0 65 Btuh/ft²-°F Data entries checked. 2021-Oct-25 17:17:08 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF16B7 princeton.rup Calc = MJ8 House faces: N SF16B7Job:Component Constructions Date:Entire House Vince ByramBy: High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com Project Information Cody PuzeyFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) SimplifiedMethod)H(34-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Frm wall, vnl ext, 3/8" wood shth, r-22 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 2510.4726184.9422.00.065530n 2700.4728164.9422.00.065570e 2500.4725994.9422.00.065526s 2780.4728904.9422.00.065585w 10490.47109234.9422.00.0652211all Partitions (none) Windows 61C: 61C; NFRC rated (SHGC=0.32); 6.67 ft head ht 0.30095n 97810.3216922.80 51234.134222.800.30015e 260118.6318922.800.300140s 409116.4570122.800.300250all Doors 11P0: Door, mtl pur core type 2195.3790022.010.50.29041n Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 5/8" gypsum board int fnsh 9820.8417771.5250.00.0201169 Floors 19A-30bscp: Part floor, carpet flr fnsh, r-30 ins, frm flr, 12" thkns, 1/2" gypsum board int fnsh 1340.407292.1730.00.034336 22B-10cpm: Bg floor, heavy dry or light damp soil, on grade depth, r-10 edge ins, carpet flr fnsh 00377727.010.00.355140 009427.010.00.3553 00387127.010.00.355143all Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Oct-25 17:17:08 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF16B7 princeton.rup Calc = MJ8 House faces: N SF16B7Job:Project Summary Date:Entire House Vince ByramBy: High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com Project Information Cody PuzeyFor:3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Notes: Design Information Idaho Falls, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-6 Outside db °F89Inside db °F70 Inside db °F75 Design TD °F76 Design TD °F14Daily range H Relative humidity %50Moisture difference gr/lb-31 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh34014 Structure Btuh8081 Ducts Btuh0 Ducts Btuh0Central vent (26 cfm)1821 Btuh Central vent (26 cfm)Btuh335 Outside air Outside airHumidificationBtuh0Blower Btuh0 Piping Btuh0Equipment load Btuh35835 Use manufacturer's data n Rate/swing multiplier 0.94InfiltrationEquipment sensible load Btuh7911 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh-1347 Ducts Btuh0Central vent (26 cfm)Btuh-466 CoolingHeating Outside air19201920Area (ft²)Equipment latent load Btuh0 1728017280Volume (ft³)Air changes/hour 0.260.50 Equipment Total Load (Sen+Lat)Btuh7911 Equiv. AVF (cfm)75144 Req. total capacity at 0.70 SHR ton0.9 Heating Equipment Summary Cooling Equipment Summary Make Goodman Mfg.Make Goodman Mfg.Trade GOODMAN Trade GOODMAN, JANITROL, AMANA DISTI... Model GMH950703BX Cond GSX130241C*AHRI ref 2002183 Coil Capf3030bx AHRI ref 4765510Efficiency95 AFUE Efficiency 11.0 EER, 13 SEER Heating input Btuh69000 Sensible cooling Btuh16100Heating output Btuh52440 Latent cooling Btuh6900 Temperature rise °F62 Total cooling Btuh23000Actual air flow cfm920 Actual air flow cfm767 Air flow factor cfm/Btuh0.027 Air flow factor cfm/Btuh0.095Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 1.00 2021-Oct-25 17:17:08 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF16B7 princeton.rup Calc = MJ8 House faces: N SF16B7Job:AED Assessment Date:Entire House Vince ByramBy: High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com Project Information Cody PuzeyFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) )H(34-Da ily ra nge (°F) 60-We t bu lb (°F) 7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limitGlazing load (Btuh)Hour of Day 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 41.5%. House does not have adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 636 Btuh (PFG - 1.3*AFG) Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Oct-25 17:17:08Right-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1S:\High Country\Wrightsoft\SF16B7 princeton.rup Calc = MJ8 House faces: N SF16B7Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com 1 Room name Entire House Room2 2 Exposed wall 278.0 ft 17.0 ft 3 Room height 9.0 dft 9.0 heat/coolft 4 Room dimensions ft4.0x13.0 5 Room area 1920.0 f t²52.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 666 530 2618 251 117 117 578 56 .GG 61C61C 0.3000.300 nn 22.8022.80 10.2810.28 95 0 2169 978 0 0 0 0 .DD 11P011P0 0.2900.290 nn 22.0422.04 5.365.36 41 41 900 219 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 585 570 2816 270 0 0 0 0 1 1 GG 61C61C 0.3000.300 ee 22.8022.80 34.1434.14 15 0 342 512 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 666 526 2599 250 0 0 0 0 GG 61C61C 0.3000.300 ss 22.8022.80 18.6018.60 140 0 3189 2601 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 585 585 2890 278 36 36 178 17 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 1169 1169 1777 982 0 0 0 0 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 336 336 729 134 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 773 140 3777 0 52 17 459 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 60 3 94 0 0 0 0 0 6 c) AED excursion 636 -3 Envelope loss/gain 23900 7112 1214 70 12 a)Infiltration 10114 969 618 59 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)34014 8081 1833 129 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 -1833 -129 14 Subtotal 34014 8081 0 0 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 34014 8081 0 0 Air required (cfm)Air required (cfm)920 767 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Oct-25 17:17:08Right-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 2S:\High Country\Wrightsoft\SF16B7 princeton.rup Calc = MJ8 House faces: N SF16B7Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com 1 Room name Room3 Room4 2 Exposed wall 25.0 ft 31.0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft15.0x10.0 ft250.0x1.0 5 Room area 150.0 f t²250.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 0 0 0 0 135 115 567 54 .GG 61C61C 0.3000.300 nn 22.8022.80 10.2810.28 0 0 0 0 20 0 459 207 .DD 11P011P0 0.2900.290 nn 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 135 135 667 64 144 129 637 61 1 1 GG 61C61C 0.3000.300 ee 22.8022.80 34.1434.14 0 0 0 0 15 0 342 512 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 90 90 445 43 0 0 0 0 GG 61C61C 0.3000.300 ss 22.8022.80 18.6018.60 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 150 150 228 126 250 250 380 210 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -7 -27 Envelope loss/gain 1339 225 2386 1018 12 a)Infiltration 910 87 1128 108 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2249 312 3514 1126 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 2249 312 3514 1126 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2249 312 3514 1126 Air required (cfm)Air required (cfm)61 30 95 107 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Oct-25 17:17:08Right-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 3S:\High Country\Wrightsoft\SF16B7 princeton.rup Calc = MJ8 House faces: N SF16B7Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com 1 Room name Room5 Room6 2 Exposed wall 14.0 ft 26.0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft242.0x1.0 ft13.0x13.0 5 Room area 242.0 f t²169.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 0 0 0 0 0 0 0 0 .GG 61C61C 0.3000.300 nn 22.8022.80 10.2810.28 0 0 0 0 0 0 0 0 .DD 11P011P0 0.2900.290 nn 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 0 0 0 0 0 0 0 0 1 1 GG 61C61C 0.3000.300 ee 22.8022.80 34.1434.14 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 126 96 474 46 117 92 454 44 GG 61C61C 0.3000.300 ss 22.8022.80 18.6018.60 30 0 684 558 25 0 570 465 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 0 0 0 0 117 117 578 56 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 242 242 368 203 169 169 257 142 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 60 3 94 0 0 0 0 0 6 c) AED excursion 156 128 Envelope loss/gain 1620 962 1859 834 12 a)Infiltration 509 49 946 91 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2129 1011 2805 924 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 2129 1011 2805 924 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2129 1011 2805 924 Air required (cfm)Air required (cfm)58 96 76 88 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Oct-25 17:17:08Right-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 4S:\High Country\Wrightsoft\SF16B7 princeton.rup Calc = MJ8 House faces: N SF16B7Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com 1 Room name Room7 Room8 2 Exposed wall 5.0 ft 14.0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft5.0x10.0 ft14.0x11.0 5 Room area 50.0 f t²154.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 0 0 0 0 99 74 366 35 .GG 61C61C 0.3000.300 nn 22.8022.80 10.2810.28 0 0 0 0 25 0 570 257 .DD 11P011P0 0.2900.290 nn 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 0 0 0 0 9 9 44 4 1 1 GG 61C61C 0.3000.300 ee 22.8022.80 34.1434.14 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ss 22.8022.80 18.6018.60 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 45 45 222 21 18 18 89 9 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 50 50 76 42 154 154 234 129 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 50 50 108 20 154 154 334 62 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -2 -13 Envelope loss/gain 407 81 1637 483 12 a)Infiltration 182 17 509 49 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)589 98 2146 532 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 589 98 2146 532 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 589 98 2146 532 Air required (cfm)Air required (cfm)16 9 58 50 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Oct-25 17:17:08Right-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 5S:\High Country\Wrightsoft\SF16B7 princeton.rup Calc = MJ8 House faces: N SF16B7Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com 1 Room name Room9 Room10 2 Exposed wall 23.0 ft 7.0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft12.0x11.0 ft5.0x7.0 5 Room area 132.0 f t²35.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 99 74 366 35 0 0 0 0 .GG 61C61C 0.3000.300 nn 22.8022.80 10.2810.28 25 0 570 257 0 0 0 0 .DD 11P011P0 0.2900.290 nn 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 0 0 0 0 0 0 0 0 1 1 GG 61C61C 0.3000.300 ee 22.8022.80 34.1434.14 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 0 0 0 0 63 55 272 26 GG 61C61C 0.3000.300 ss 22.8022.80 18.6018.60 0 0 0 0 8 0 182 149 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 108 108 534 51 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 132 132 201 111 0 0 0 0 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 132 132 286 53 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 35 7 189 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -14 42 Envelope loss/gain 1956 493 643 217 12 a)Infiltration 837 80 255 24 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2793 573 898 241 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 2793 573 898 241 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2793 573 898 241 Air required (cfm)Air required (cfm)76 54 24 23 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Oct-25 17:17:08Right-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 6S:\High Country\Wrightsoft\SF16B7 princeton.rup Calc = MJ8 House faces: N SF16B7Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com 1 Room name Room11 Room1 2 Exposed wall 15.0 ft 101.0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft82.0x1.0 ft604.0x1.0 5 Room area 82.0 f t²604.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 0 0 0 0 216 150 742 71 .GG 61C61C 0.3000.300 nn 22.8022.80 10.2810.28 0 0 0 0 25 0 570 257 .DD 11P011P0 0.2900.290 nn 22.0422.04 5.365.36 0 0 0 0 41 41 900 219 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 0 0 0 0 297 297 1467 141 1 1 GG 61C61C 0.3000.300 ee 22.8022.80 34.1434.14 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 54 39 193 19 216 154 761 73 GG 61C61C 0.3000.300 ss 22.8022.80 18.6018.60 15 0 342 279 62 0 1411 1151 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 81 81 400 38 180 180 889 85 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 0 0 0 0 22 22 33 18 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 82 15 405 0 604 101 2725 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 79 298 Envelope loss/gain 1339 415 9499 2314 12 a)Infiltration 546 52 3675 352 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1885 467 13173 2666 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 1402 98 431 30 14 Subtotal 3287 565 13605 2696 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 3287 565 13605 2696 Air required (cfm)Air required (cfm)89 54 368 256 Job #: SF16B7 Performed by Vince Byram for: Cody Puzey 3758 Yellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 High Country Heating P.O. Box 627 Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 highcountryhtg@gmail.com Scale: 1 : 62 Page 1 Ri ght -Suit e ® Un iv ersal 2019 19.0.13 RSU20477 2021-Oct-25 17:17:30 ...Wrightsoft\SF16B7 princeton.rup N 2nd Story Room3 Room4 Room5 Room6 Room7 Room8 Room9 96 cfm 58 cfm 156 cfm 105 cfm 53 cfm 53 cfm 88 cfm 16 cfm 58 cfm 76 cfm 88 cfm 76 cfm 61 cfm Job #: SF16B7 Performed by Vince Byram for: Cody Puzey 3758 Yellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 High Country Heating P.O. Box 627 Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 highcountryhtg@gmail.com Scale: 1 : 62 Page 2 Ri ght -Suit e ® Un iv ersal 2019 19.0.13 RSU20477 2021-Oct-25 17:17:30 ...Wrightsoft\SF16B7 princeton.rup N Main Floor Room1 Room2 Room10 Room11 36'-0" 6 " 92 cfm 92 cfm 92 cfm 24 cfm 89 cfm 481 cfm 14x3.25 6 " 14x3.25 12 x 8 6 " 14x3.25 6 "6 "6 " 6 "6 "6 " 6 " 6 " 16 x 8 6 " 3-14x3.25 16 x 814x3.25 14x3.25 92 cfm 6 " 12 x 8 12 x 8 6 " 2021-Oct-25 17:17:09 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 1 S:\High Country\Wrightsoft\SF16B7 princeton.rup Calc = MJ8 House faces: N SF16B7Job:Duct System Summary Date:Entire House Vince ByramBy: High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com Project Information Cody PuzeyFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0.34in H2O0.34 Available static pressure in H2O0.36in H2O0.36 Supply / return available pressure 0.178 / 0.182 in H2O in H2O0.178 / 0.182 Lowest friction rate in/100ft0.081in/100ft0.081 Actual air flow cfm767cfm920 Total effective length (TEL)ft446 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st1B180.040.0ShMt0x06.00.08164923401hRoom1 st1150.023.0ShMt0x06.00.10364923401hRoom1-A st1B170.049.0ShMt0x06.00.08164923401hRoom1-B st1A180.038.0ShMt0x06.00.08164923401hRoom1-C st1165.013.0ShMt0x06.00.1002324898hRoom10 st1175.011.0ShMt0x06.00.09554893287hRoom11 st1A150.039.0ShMt0x06.00.09430612249hRoom3 st1A170.041.0ShMt0x06.00.0845348563cRoom4 st1A160.046.0ShMt0x06.00.0865348563cRoom4-A st1130.025.0ShMt0x06.00.11596581011cRoom5 st1160.016.0ShMt0x06.00.1018876924cRoom6 st1175.09.0ShMt0x06.00.097916589hRoom7 st1140.033.0ShMt0x06.00.10350582146hRoom8 st1175.020.0ShMt0x06.00.09154762793hRoom9 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st1 Peak AVF 920 767 0.081 1035 13.7 16x8 ShtMetl st1A Peak AVF 432 328 0.081 648 10.5 12x8 ShtMetl st1 st1B Peak AVF 184 128 0.081 276 7.6 12x8 ShtMetl st1A 2021-Oct-25 17:17:09 Rig ht-Su ite® U niv er sal 20 19 19 .0.13 RSU2 0477 Page 2 S:\High Country\Wrightsoft\SF16B7 princeton.rup Calc = MJ8 House faces: N Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb2 0x 760 88 105.0 0.174 278 5.0 3.25x14 10x9 SJSp rt1 rb4 0x 580 50 96.0 0.190 184 4.2 3.25x14 10x9 SJSp rt1 rb3 0x 760 54 127.0 0.144 239 4.9 3.25x14 10x9 SJSp rt1 rb1 0x 4810 332 226.0 0.081 508 10.9 3-3.25x14 3-10x27 SJSp rt1 rb6 0x 740 105 141.0 0.129 333 5.6 3.25x14 10x9 SJSp rt1 rb5 0x 1560 137 194.0 0.094 493 7.0 3.25x14 10x9 SJSp rt1A Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 920 767 0.081 1035 13.7 16x8 ShtMetl rt1A Peak AVF 156 137 0.094 234 7.0 12x8 ShtMetl rt1