HomeMy WebLinkAboutFA REPORT - 21-00250 - BYUI Manwaring Center Activities & Involvement - RemodelFIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION
To be completed by the system installation contractor at the time of system acceptance and approval.
It shall be permitted to modify this form as needed to provide a more complete and/or clear record.
Insert N/A in all unused lines.
Attach additional sheets, data, or calculations as necessary to provide a complete record.
1. PROPERTY INFORMATION
Name of property:
BYU-I Manwaring Center Remodel
Address:
525 South Center Street. Rexburg, ID. 83460
Description of property:
University Mixed Use Building
Occupancy type:
Name of property representative:
Byron Gilbert
Address:
Phone:
Fax:
E-mail:
Authority having jurisdiction over this property:
Rexburg City
Phone:
208-372-2171
Fax:
E-mail:
2. INSTALLATION, SERVICE, AND TESTING CONTRACTOR INFORMATION
Installation contractor for this equipment:
Nelson Fire Systems
Address:
1481 South Major Street Salt Lake City, Utah 84115
License or certification number:
AE332
Phone:
801-468-8300
Fax:
801-468-8305
E-mail:
office@nelsonfire.com
Service organization for this equipment:
Address:
License or certification number:
Phone:
Fax:
E-mail:
A contract for test and inspection in accordance with NFPA standards is in effect as of:
Contracted testing company:
Address:
Phone:
Fax:
E-mail:
Contract expires:
Contract number:
Frequency of routine inspections:
3. DESCRIPTION OF SYSTEM OR SERVICE
Fire alarm system (nonvoice)
Fire alarm with in-building fire emergency voice alarm communication system (EVACS)
Mass notification system (MNS)
Combination system, with the following components:
Fire alarm EVACS MNS Two-way, in-building, emergency communication system
Other (specify):
3. DESCRIPTION OF SYSTEM OR SERVICE (continued)
NFPA 72 edition:
2013
Additional description of system(s):
3.1 Control Unit
Manufacturer:
Gamewell-FCI
Model number:
E3 Series
3.2 Mass Notification System This system does not incorporate an MNS
3.2.1 System Type:
In-building MNS—combination
In-building MNS—stand-alone Wide-area MNS Distributed recipient MNS
Other (specify):
3.2.2 System Features:
Combination fire alarm/MNS MNS autonomous control unit Wide-area MNS to regional national
alerting interface
Local operating console (LOC) Direct recipient MNS (DRMNS) Wide-area MNS to DRMNS interface
Wide-area MNS to high-power speaker array (HPSA) interface In-building MNS to wide-area MNS interface
Other (specify):
3.3 System Documentation
An owner’s manual, a copy of the manufacturer’s instructions, a written sequence of operation, and a copy of
the numbered record drawings are stored on site.
Location:
At Main FACP
3.4 System Software This system does not have alterable site-specific software.
Operating system (executive) software revision level:
3.41
Site-specific software revision date:
Revision completed by:
Tadd Timothy
A copy of the site-specific software is stored on site. Location:
Main FACP
3.5 Off-Premises Signal Transmission This system does not have off-premises transmission.
Name of organization receiving alarm signals with phone numbers:
Alarm:
BYU-I Dispatch
Phone:
208-496-3000
Supervisory:
Same As Above
Phone:
Trouble:
Same as Above
Phone:
Entity to which alarms are retransmitted:
Phone:
Method of retransmission:
If Chapter 26, specify the means of transmission from the protected premises to the supervising station:
Supervised Station Alarm Systems
If Chapter 27, specify the type of auxiliary alarm system: Local energy Shunt Wired Wireless
4. CIRCUITS AND PATHWAYS
4.1 Signaling Line Pathways
4.1.1 Pathways Class Designations and Survivability
Pathways class:
Survivability level:
Quantity:
(See NFPA 72, Sections 12.3 and 12.4)
4.1.2 Pathways Utilizing Two or More Media
Quantity:
Description:
4.1.3 Device Power Pathways
No separate power pathways from the signaling line pathway
Power pathways are separate but of the same pathway classification as the signaling line pathway
Power pathways are separate and different classification from the signaling line pathway
4.1.4 Isolation Modules
Quantity:
4.2 Alarm Initiating Device Pathways
4.2.1 Pathways Class Designations and Survivability
Pathways class:
Survivability level:
Quantity:
(See NFPA 72, Sections 12.3 and 12.4)
4.2.2 Pathways Utilizing Two or More Media
Quantity:
Description:
4.2.3 Device Power Pathways
No separate power pathways from the initiating device pathway
Power pathways are separate but of the same pathway classification as the initiating device pathway
Power pathways are separate and different classification from the initiating device pathway
4.3 Non-Voice Audible System Pathways
4.3.1 Pathways Class Designations and Survivability
Pathways class:
Class B
Survivability level:
level 1
Quantity:
4
(See NFPA 72, Sections 12.3 and 12.4)
4.3.2 Pathways Utilizing Two or More Media
Quantity:
Description:
4.3.3 Device Power Pathways
No separate power pathways from the notification appliance pathway
Power pathways are separate but of the same pathway classification as the notification appliance pathway
Power pathways are separate and different classification from the notification appliance pathway
5. ALARM INITIATING DEVICES
5.1 Manual Initiating Devices
5.1.1 Manual Fire Alarm Boxes This system does not have manual fire alarm boxes.
Type and number of devices: Addressable:
Conventional:
Coded:
Transmitter:
Other (specify):
5.1.2 Other Alarm Boxes This system does not have other alarm boxes.
Description:
Type and number of devices: Addressable:
Conventional:
Coded:
Transmitter:
Other (specify):
5.2 Automatic Initiating Devices
5.2.1 Smoke Detectors This system does not have smoke detectors.
Type and number of devices: Addressable:
Conventional:
Other (specify):
Type of coverage: Complete area Partial area Nonrequired partial area
Other (specify):
Type of smoke detector sensing technology: Ionization Photoelectric Multicriteria Aspirating Beam
Other (specify):
5.2.2 Duct Smoke Detectors This system does not have alarm-causing duct smoke detectors.
Type and number of devices: Addressable:
Conventional:
Other (specify):
Type of coverage:
Type of smoke detector sensing technology: Ionization Photoelectric Aspirating Beam
5.2.3 Radiant Energy (Flame) Detectors This system does not have radiant energy detectors.
Type and number of devices: Addressable:
Conventional:
Other (specify):
Type of coverage:
5.2.4 Gas Detectors This system does not have gas detectors.
Type of detector(s):
Number of devices: Addressable:
Conventional:
Type of coverage:
5.2.5 Heat Detectors This system does not have heat detectors.
Type and number of devices: Addressable:
Conventional:
Type of coverage: Complete area Partial area Nonrequired partial area Linear Spot
Type of heat detector sensing technology: Fixed temperature Rate-of-rise Rate compensated
5. ALARM INITIATING DEVICES (continued)
5.2.6 Addressable Monitoring Modules This system does not have monitoring modules.
Number of devices:
5.2.7 Waterflow Alarm Devices This system does not have waterflow alarm devices.
Type and number of devices: Addressable:
Conventional:
Coded:
Transmitter:
5.2.8 Alarm Verification This system does not incorporate alarm verification.
Number of devices subject to alarm verification:
Alarm verification set for:
seconds
5.2.9 Presignal This system does not incorporate pre-signal.
Number of devices subject to presignal:
Describe presignal functions:
5.2.10 Positive Alarm Sequence (PAS) This system does not incorporate PAS.
Describe PAS:
5.2.11 Other Initiating Devices This system does not have other initiating devices.
Describe:
6. SUPERVISORY SIGNAL-INITIATING DEVICES
6.1 Sprinkler System Supervisory Devices This system does not have sprinkler supervisory devices.
Type and number of devices: Addressable:
Conventional:
Coded:
Transmitter:
Other (specify):
6.2 Fire Pump Description and Supervisory Devices This system does not have a fire pump.
Type fire pump: Electric pump Engine
Type and number of devices: Addressable:
Conventional:
Coded:
Transmitter:
Other (specify):
6.2.1 Fire Pump Functions Supervised
Power Running Phase reversal Selector switch not in auto Engine or control panel trouble Low fuel
Other (specify):
6.3 Duct Smoke Detectors (DSDs) This system does not have DSDs causing supervisory signals.
Type and number of devices: Addressable:
Conventional:
Other (specify):
Type of coverage:
Type of smoke detector sensing technology: Ionization Photoelectric Aspirating Beam
6.4 Other Supervisory Devices This system does not have other supervisory devices.
Describe:
7. MONITORED SYSTEMS
7.1 Engine-Driven Generator This system does not have a generator.
7.1.1 Generator Functions Supervised
Engine or control panel trouble Generator running Selector switch not in auto Low fuel
Other (specify):
7.2 Special Hazard Suppression Systems This system does not monitor special hazard systems.
Description of special hazard system(s):
7.3 Other Monitoring Systems This system does not monitor other systems.
Description of special hazard system(s):
8. ANNUNCIATORS This system does not have annunciators.
8.1 Location and Description of Annunciators
Location 1:
Level 1 North Entrance
Location 2:
Level 2 South Entrance
Location 3:
9. ALARM NOTIFICATION APPLIANCES
9.1 In-Building Fire Emergency Voice Alarm Communication System This system does not have an EVACS.
Number of single voice alarm channels:
1
Number of multiple voice alarm channels:
Number of speakers:
41
Number of speaker circuits:
2
Location of amplification and sound-processing equipment:
1st floor electrical room
Location of paging microphone stations:
Location 1:
Level 1 north entrance
Location 2:
Level 1 main facp
Location 3:
Level 2 south entrance
9.2 Nonvoice Notification Appliances This system does not have nonvoice notification appliances.
Horns:
With visible:
Bells:
With visible:
Chimes:
With visible:
Visible only:
Other (describe):
9.3 Notification Appliance Power Extender Panels This system does not have power extender panels.
Quantity:
Locations:
level 1 facp/ elec room
10. MASS NOTIFICATION CONTROLS, APPLIANCES, AND CIRCUITS This system does not have an MNS.
10.1 MNS Local Operating Consoles
Location 1:
Location 2:
Location 3:
10.2 High-Power Speaker Arrays
Number of HPSA speaker initiation zones:
Location 1:
Location 2:
Location 3:
10.3 Mass Notification Devices
Combination fire alarm/MNS visible appliances:
MNS-only visible appliances:
Textual signs:
Other (describe):
Supervision class:
10.3.1 Special Hazard Notification
This system does not have special suppression predischarge notification.
MNS systems DO NOT override notification appliances required to provide special suppression
predischarge notification.
11. TWO-WAY EMERGENCY COMMUNICATION SYSTEMS
11.1 Telephone System This system does not have a two-way telephone system.
Number of telephone jacks installed:
Number of warden stations installed:
Number of telephone handsets stored on site:
Type of telephone system installed: Electrically powered Sound powered
11.2 Two-Way Radio Communications Enhancement System
This system does not have a two-way radio communications enhancement system.
Percentage of area covered by two-way radio service: Critical areas:
% General building areas:
%
Amplification component locations:
Inbound signal strength:
dBm
Outbound signal strength:
dBm
Donor antenna isolation is:
dB above the signal booster gain
Radio frequencies covered:
Radio system monitor panel location:
11. TWO-WAY EMERGENCY COMMUNICATION SYSTEMS (continued)
11.3 Area of Refuge (Area of Rescue Assistance) Emergency Communications Systems
This system does not have an area of refuge (area of rescue assistance) emergency communications system.
Number of stations:
Location of central control point:
Days and hours when central control point is attended:
Location of alternate control point:
Days and hours when alternate control point is attended:
11.4 Elevator Emergency Communications Systems
This system does not have an elevator emergency communications system.
Number of elevators with stations:
Location of central control point:
Days and hours when central control point is attended:
Location of alternate control point:
Days and hours when alternate control point is attended:
11.5 Other Two-Way Communication Systems
Describe:
12. CONTROL FUNCTIONS
This system activates the following control fuctions:
Hold-open door releasing devices Smoke management HVAC shutdown F/S dampers
Door unlocking Elevator recall Fuel source shutdown Extinguishing agent release
Elevator shunt trip Mass notification system override of fire alarm notification appliances
Other (specify):
12.1 Addressable Control Modules This system does not have control modules.
Number of devices:
Other (specify):
13. SYSTEM POWER
13.1 Control Unit
13.1.1 Primary Power
Input voltage of control panel:
120 vac
Control panel amps:
9
Overcurrent protection:
Type:
Circuit Breaker
Amps:
20
Location (of primary supply panel board):
Electrical room
Disconnecting means location:
Electrical room
13.1.2 Engine-Driven Generator This system does not have a generator.
Location of generator:
Location of fuel storage:
Type of fuel:
13. SYSTEM POWER (continued)
13.1.3 Uninterruptible Power System This system does not have a UPS.
Equipment powered by a UPS system:
Location of UPS system:
Calculated capacity of UPS batteries to drive the system components connected to it:
In standby mode (hours):
In alarm mode (minutes):
13.1.4 Batteries
Location:
1st floor elec room
Type:
Seal Lead Acid
Nominal voltage:
24
Amp/hour rating:
26
Calculated capacity of batteries to drive the system:
In standby mode (hours):
24
In alarm mode (minutes):
15
Batteries are marked with date of manufacture Battery calculations are attached
13.2 In-Building Fire Emergency Voice Alarm Communication System or Mass Notification System
This system does not have an EVACS or MNS system.
13.2.1 Primary Power
Input voltage of EVACS or MNS panel:
120
EVACS or MNS panel amps:
Overcurrent protection:
Type:
Circuit Breaker
Amps:
Location (of primary supply panel board):
1st floor elec room
Disconnecting means location:
1st floor elec room
13.2.2 Engine-Driven Generator This system does not have a generator.
Location of generator:
Location of fuel storage:
Type of fuel:
13.2.3 Uninterruptible Power System This system does not have a UPS.
Equipment powered by a UPS system:
Location of UPS system:
Calculated capacity of UPS batteries to drive the system components connected to it:
In standby mode (hours):
In alarm mode (minutes):
13.2.4 Batteries
Location:
1st floor elec room
Type:
Sealed Lead Acid
Nominal voltage:
24
Amp/hour rating:
26
Calculated capacity of batteries to drive the system:
In standby mode (hours):
24
In alarm mode (minutes):
15
Batteries are marked with date of manufacture Battery calculations are attached
13. SYSTEM POWER (continued)
13.3 Notification Appliance Power Extender Panels This system does not have power extender panels.
13.3.1 Primary Power
Input voltage of power extender panel(s):
24
Power extender panel amps:
8
Overcurrent protection:
Type:
Circuit Breaker
Amps:
20
Location (of primary supply panel board):
floor electrical room
Disconnecting means location:
floor electrical room
13.3.2 Engine-Driven Generator This system does not have a generator.
Location of generator:
Location of fuel storage:
Type of fuel:
13.3.3 Uninterruptible Power System This system does not have a UPS.
Equipment powered by a UPS system:
Location of UPS system:
Calculated capacity of UPS batteries to drive the system components connected to it:
In standby mode (hours):
In alarm mode (minutes):
13.3.4 Batteries
Location:
1st floor electrical room
Type:
Sealed Lead Acid
Nominal voltage:
24
Amp/hour rating:
8
Calculated capacity of batteries to drive the system:
In standby mode (hours):
24
In alarm mode (minutes):
15
Batteries are marked with date of manufacture Battery calculations are attached
14. RECORD OF SYSTEM INSTALLATION
Fill out after all installation is complete and wiring has been checked for opens, shorts, ground faults, and improper
branching, but before confucting operational acceptance tests.
This is a:
New system
Modification to an existing system
Permit number:
The system has been installed in accordance with the following requirements: (Note any or all that apply.)
NFPA 72, Edition:
NFPA 70, National Electrical Code, Article 760, Edition:
Manufacturer’s published instructions
Other (specify):
System deviations from referenced NFPA standards:
Signed:
Printed name:
Date:
Organization:
Wheeler Electric
Title:
Phone:
15. RECORD OF SYSTEM OPERATIONAL ACCEPTANCE TEST
New system
All operational features and functions of this system were tested by, or in the presence of, the signer shown
below, on the date shown below, and were found to be operating properly in accordance with the requirements
for the following:
Modifications to an existing system
All newly modified operational features and functions of the system were tested by, or in the presence of, the
signer shown below, on the date shown below, and were found to be operating properly in accordance with the
requirements of the following:
NFPA 72, Edition:
NFPA 70, National Electrical Code, Article 760, Edition:
Manufacturer’s published instructions
Other (specify):
Individual device testing documentation [Inspection and Testing Form (Figure 14.6.2.4) is attached]
Signed:
Printed name:
Tadd Timothy
Date:
Organization:
Nelson Fire Systems
Title:
Project Manager
Phone:
801-468-8300
16. CERTIFICATIONS AND APPROVALS
16.1 System Installation Contractor:
This system, as specified herein, has been installed and tested according to all NFPA standards cited herein.
Signed:
Printed name:
Tadd Timothy
Date:
Organization:
Nelson Fire Systems
Title:
Project Manager
Phone:
801-468-8300
16.2 System Service Contractor:
The undersigned has a service contract for this system in effect as of the date shown below.
Signed:
Printed name:
Date:
Organization:
Title:
Phone:
16.3 Supervising Station:
This system, as specified herein, will be monitored according to all NFPA standards cited herein.
Signed:
Printed name:
Date:
Organization:
Title:
Phone:
16. CERTIFICATIONS AND APPROVALS (continued)
16.4 Property or Owner Representative:
This system, as specified herein, will be monitored according to all NFPA standards cited herein.
Signed:
Printed name:
Date:
Organization:
Title:
Phone:
16.5 Authority Having Jurisdiction:
I have witnessed a satisfactory acceptance test of this system and find it to be installed and operating properly
in accordance with its approved plans and specifications, with its approved sequence of operations, and with all
NFPA standards cited herein.
Signed:
Printed name:
Date:
Organization:
Title:
Phone: