October 8, 2007
Permit Number: 07 00125
Project Name:
Project Type:
Review ActIF
ion
Rexburg Medical Center Addition
Commercial Addition
Review Item
Administrative review
Permit Tech Motes
Parcel #'s
— AC—ticffl—S-ReqtA-r eA for A��row,al
Contractor information includinn ��nna+� �r�
required prior to work
_.
commencing.
A"'Construction Permit" is required to be filled
out and signed by the contractor installing the
system(s) rather than by the general contractor.
[his permit is required to install any fire related
equipment -see application in the permit packet.�iAn industrial wastewater ischarge
is
required to be completed nrinr tn
the
application
issuance of
f ly NtN t rut. ►-xpp»catian was maiied
31271U7.
19 EMain St.
Rexburg, Idaho $3440
Phone (2Q8) 359-3020
Fax (los) 359-3022
IV " 0=0 1.
I TY OF
I-E"URG
pn cap Fonar), Comrnuniiy
October 8, 2007
Permit Number: 07 00125
Project Name:
Project Type:
Review item
Review Action
Rexburg Medical Center Addition
Commercial Addition
Building Department Review
Electrical Service review
Electrical Circuits Review
Complies with approved Site Plan Review
Exiting Review
Building Type Compliance
Water and Sewer Service
Plumbing Sewer Drain Review
Plumbing Storm Drain Review
Plumbing potable Water Review
Energy Conservation Compliance Review
Miscellaneous
Accessibility Review
Height and Area Review
Ac-No-ri-s-Re-qat-redfdrp�
_Arowal
Make sure that the pool and exam roomy meet
the 2005 NEC requirements and don't hesitate
to coli for questions concerning these yr other
items.
Site plan has been reviewed.
Space under stairs must be drywalled.
Building is Type VB.
All plumbing services are required to be tested
and inspected before cowering.
All drains are required to be tested and
inspected before covering. All drains ars
required to be installed according to the Uniform
Plumbing Code 2p03 Edition.
All storm drains and overflow piping will b�
tested and inspected before covering.
All water lines are required to be tested and
I
nspected before covering.
Proper backflow prevention is required to be
tested and inspected prior to final plumbing
inspection,
Lighting energy complies with the current
codes(2003), Approvedto issue the permit.
Provide flood certificate.
Provide ramp details that meet the
requirements of ANSI 117. 1.
Several measurements on the prints are
incorrect for handicapped res#rooms. See
approved prints
OK.
19 E Main St.
Rexburg, Who 83440
Phone {208} 359-3020
Fax (2D8) 359-3022
03/29/2007
03/2,9/12007
04/10/2007
04/10/2007
04/10/2007
04/11/2007
04/11/2007
04/11 /2007
04/11/2007
04/12/2007
}
I TY OF
EXBURG
CAW ,.
October 8, 2007
Permit Number: 07 00125
Project Name:
Project Type;
Review Idem
Review Action
Rexburg Medical Center Addition
Commercial Addition
Energy Conservation Compliance Review
Building Codi Fire Compflance Review
Mechanical Review
Structural Review
Parcel #'s RPRXBCA0205103
&ct[Q—n$ Required fQr ApprQval
The envelope print out was net completed
properly. Resubmit envelope portion of energy
review.
Meets code requirements.
Meets cede requirements.
Special inspections are required for concrete
foundation walls. Provide a letter from the
special inspection firm. Page 3.1 messing from
large set of plans.
19 E Main St.
Rexburg,. Idaho 83440
Phone (20$) 359-3020
Fax (2D8) 359-3022
Aroved
-." VA
I TY
F
R" EXBURG
October 8, 2007
Permit Number: 07 00125
Project Name:
Project Type:
Review Item
Review Action
Rexburg Medical Center Addition
Commercial Addition
Fire Department Review
Required Fire Flaw
Water Supply
Fire Access Roads
Fire Extinguishers
Automatic Fire Extinguishing Systems
Standpipes
Commercial Cooking
Alarm Systems
Other Comments
Parcel #'s RPRXBCA0205103
19 E Main St.
Rexburg, Idaho 83.440
Phone (2(l$) 359.3020
Fax (208) 359-3022
Actions Re -C 1 uire—df-0 r Ap-brvval —A� d
See site plan review 04/11/2007
See site plan review 04/11/2007
See site plan review 04/11/2007
All fire extinguishers are required to be installed- a411 112007
prier to final fire inspection,
Submit letter of intent from certified fare sprinkler 04/11/2007
contractor,
N/A 04/11/2007
Not required,. 04/11/2007
Please submit letter ofintent firvm certified fire X411 12007
alarm contractor. Plans must be appraved
before fire warm system is installed.
04/11/2007
�Lbx1S Ups
t
CITY OF
R-EXBLTG
America'iami� y Community
Review Action
October 8, 2007
Permit Number: 07 00125
Project Name: Rexburg Medical Center Addition
19 E Main St.
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
Project Type: Commercial Addition
Review Item A�C—flQns Re u�red fog- A
q-- �a�ro�al — A#p.roved
Planning Staff Review -
Development Standards Review
Parcel #'s RPRXBCA0205103
Design Review Committee mei 10/2/2007 and
decided that since the addition is an the back of
the building, and to keep the addition uniform
with the existing building, we would not request
changes to the facade. Two Maple trees, or
similar, are required along the Northern facade
to visually break up the large expanse from
neighboring properties. Please add these to the
plans.
10/05/2007
CITY F
October 8, 2007
Permit Number.* 07 00124
Project Name:
Project Type:
Review item
Review Action
Rexburg Medical Center Addition
Site Plan Review
Building Department Review
Fire Separation
Plumbing Review
Number of Parking Spaces
Miscellaneous
Parcel #'s
RPRXBCA0205103
19 E Main St.
Rexburg, Idaho 83440
Phone (2018) 359-3020
Fax (208) 359-3022
&zt—iQns,---Required for Ap�r�v t A roved
Meets code requirements..
5 handicapped parking spaces are required as
Per the 2003 International Building Code (113C)
Table 1106.1.
Provide heights for parking lot and sidewalks.
The plans identify a ramp. If the slope of the
sidewalk that accesses an entrance is greater
than 1/20, then provide ramp details that meet
the requirements of ANSI 117. 1.
04/06/2007
.:M► iL7
{ CITY 0 V
EXBURG
6P ------ ..2.-
Review Action
October 8, 2007
Permit Number: 07 00124
Project Name: Rexburg Medical Center Addition
Project Type: Site Plan Review
Rp-uipw 1fa
Fire Department Review
Additional Comments
Fere Lane Signage
Fire Access Roads
Water Supply
-- -w- %.- - -
19 w-
19 E Main S#.
Rexburg, Idaho 8344{}
Phare (2Q8) 359-3020
Fax (208) 359-3022
—_ Actions Requlredf Approval___ unproved
PLEASE ADDRESS NOTED COMMENTS. 03/28/2007
Parcel #'s "RXBCA0205103
NOT REQUIRED
PROVIDED
EXISTINGWA E SUPPLYMAYBE
INADEQUATE DEPENDING UPON FINAL
SQUARE FOOTAGE, BUILDING
CONSTRUCTION, ETC. WILL BUILDING BE
FIRE SPRINKLERED? PLEASE PROVIDE
ADDITIONAL DETAILS.
UPON REVIEW OF THE SITE PLAN AND
SUBMITTED BUILDING PLANS, THE
REQUIRED WATER SUPPLY IS 1500 GPM
WITH THE BUILDING BEING FULLY FIRE
SPRINKLERED AS NOTED. CURRENTLY
ONLY ONE FIRE HYDRANT IS AVAILABLE.
ONE ADDITIONAL FIRE HYDRANT WILL BE
REQUIRED TO MEET MINIMUM FIRE FLOWS.
JRW NOTED ADDITIONAL FIRE HYDRANT
TO BE INSTALLED, PLEASE PR0VinF=nq1T1=
PLAN WITH PROPOSED
HYDRANT FLOWS.
LOCATION AND
03/28/2007
03/28/2007
I;p
ITS' 0 11
REXBtJRG
-�.�-- CAV
America's Family
October 8, 2007
Permit Number: 07 00124
Project Name:
Project Type:
Review Action
Rexburg Medical Center Addition
Site Pias Review
Review Item—
Planning
Staff Review
Approved Site Plan
Approved Site Plan
Approved Site Plan
Approved Site Plan
Approved Site Plan
Approved Site Plan
Approved Site Pian
Actiqns_RWV,jred fow�—ADDrovala
Project appears to be located in the FEMA
designated flood plain {done AE, base flood
elevation 4867}. Must provide elevation
0 cer#ificate showing lowest floor at 1 footVlei
BFE or a flood proofing certificate.
This issue is forwarded to the building official
for resolution.
Dumpster cannot be located uvi#hing 20 feet of
any public thoroughfare (street, sidewalk, or
internal pedestrian walkway). Proposed
location is too close to walkway.
Signage requires a separate permit and is not
part of this site plan approval. Signs wino be
allowed in the public right-of-way.
ADA access ramps must be provided for
handicapped parking stalls.
No park ing spalls are allowed in the required 20
foot front yard setback. Front yard setback
shall be appropriately landscapede.{ hedges ,
berms, shrubs, trieflunS, etc.}
Please extend the landscaped ,portion of the
Southeast corner, of the lot back to the 20 foot
setback line.
as edge of perking area along the east
property dine should have a landscape buffer or
wheel stops:
A!+ �4 0
ighting must conform to Commercial
Lighting Standards. Please. submit a lighting
plan. for review.
111uminace levels shall not exceed 0.2 foot-
candles at the property boundaries. Proposed
lighting violates this standard. Please revise.
Illuminance levels cannot exceed p.2 foot-
candles at the property boundaries. Please
revise. High pressure sodium lamps must be
19 E Main St.
Rexburg, Idaho 83440
Phone (2Q8) 359-302
Fax (208) 35943022
Ap�rv�►ed
05/18/2007
05/18/2007
05/18/2007
05/18/2007
10/02/2007
10/02/2007
10/05/200
7
TTY 0 r.
RExBuRG
October 8, 2007
Permit Number: 07 00124
Project Name:
Project Type:
Review Item -
0
Approved Site Plan
Parcel #'s
Review Action
Rexburg Medical Center Addition
Site Plan Review
RPRXBCA0205103
ire t Q—r A mro v a [ - —
used..
Parking must be screened from public right,of-
way with landscaping (hedges, berms, trees,
shrubs, etc.). Please provide landscaping plan
for review.
Please provide landscaping details i
on the site plan.
n a legend
Proposed landscaping must meet the foliowing
minimum standards for planting size:
5 gailon shrub, 2 inch caliper for deciduous,
arld 7 foot for evergreen. Also, the design
review C6mmittee will accept two Maple trees',
or similar, along the Northern facade of the
building to visually break up the large expanse
of building from adjacent properties.
19 F. Main St.
Rexburg, Idaho 83440
Phone (208) 355-3[]20
Fax (208) 359-3022
10/05/2007
i4 `
I TY OF
RExBL.jRG,
UCtOber 8, 2007
Permit Number: 07 00124
Project Name:
Project Type:
Review Action
Rexburg Medical Center Additive
Site Plan Review
Review Item
Public Works Re
view
Approved Site Pian
Parcel #'s R-PRXBCA0205103
0
The water seryice line shows a new 2 inch
line. Will this be adequate for the fire
suppression system?
2'. A lighting plan for the parking needs to be
submitted.
3. There needs to be a minimum of 22 deet of
drive space between the parking stalls.
4. What is the plan for management of storm
water runoff?
5. Handicapped marking at the approached
reed to be marked with truncated domes.
5. The site sign is shown within the public right-
of-way. This sign must be an the development
property.
7. The trash enclosure size does not provide
adequate pickup. The minimum size is 11 feet
by 7 feet, and the design and materials need to
be shown. The enclosure should be Turned to
the north to provide for easier pickup and less
chance for conflict with cap parking.
Items have been adequatelyaddressed.