Dear Ryan,
Site and bwlding plan revi"s,ions have beenrevie��ed by all necessary departments
Mosquito Abatement building located at G10 airport Rd. flans have been aor�rn
of the exterior 1i htxn which ` �-- -
Si to B
1)
2)
3)
4)
5)
deferred submit
for the Madison Counr
,Ted 1 thQ exce-Dtion
Please show the parking configuration including accessible parking. APPROVED
Please, show snow storage ares. "PROVED
Per the Design Review Committee meeting held on a/2$/Q9, please provide a site plata shown
setbacks and location of proposed evergreen trees. The, evergree�� trees need to be a minitn.utr�g
of 7' tali at planting; please node that on the site/landscape plan. A-PPROVED
Please show future right -of wav lines. APPROVED
Please Shaw trash enclosure location as Nveil as
HAVE A DUMPSTER
enclosure details. APPROVED -WILL NOT
6) There must be a hard surface from street to the building (i.e. asphalt, concrete). APPROVED
7) 1"he attached Conditional Use Pernut conditions must be complied with. ACKNOWLEDGED
8) EXTERIOR LIGHTING WAS NOT SUBMITTED. PLEASE PROVIDE DETAILS.
AS OF 6/8/09 EXTERIOR LIGHTING PLAN AND DETAILS STILL NEED
TO BE SUBMITTED FOR R$VIEW PRIOR TO INSTALLATION.
13uildin Plan:
1} Please provide the water meter size. APPROVED
2} according to Todd Payne, the electrical engineer, the garage portion will only be used for
vehicles to be parked temporarily -not worked on. No fuel or hazard(zus materials w�11 be st0,edinit. I£ this is not accurate �x if it changes, please het us knflw u�r�xnediatcZy. All electrical
mclu+ditig the service must meet 2048 NEC requirements. ACKNOWLEDGED
4
3} Please submit structural calculations. APPROVED
4} Special inspections are required on the concrete foundation, high strength boltingand steel
welding. Please provide the name of the company performing these �spectiansAPPRVED
3) All plumbing services and drwns are required to be tested and inspected blefore coveng..ACKNOWLEDGED
19 E' Jule it "I ID 8,34-40 P 0. Box 260
Phone (208) 35p.3020 Ear (`208) ,9.3024
00'"I f IF I,- - _.-M
Building Plan Review (cont'd)
Building Plan.
REXBURG
America� Family Commw1j'13P
6) T Nvater lines for truck fil.]_ing are required to have a reduced pressure Principle backflow
preventer, not a double check. ACKNOWLEDGED
7) Building is classed as a type "LT" occupancy. The office space is considered as a tyke "B"
I
occupancy. Aone-hour separation is requLred between occupancies. APPROVED
8) 'The restroom must be accessible including the shower. APPROVED
9) Fire extinguishers are required for each occupancy. According to the plans subnu-tte.d, alarm and
sprinkler systems are not required. ACI£NOVUI,EDGED
10) The building colors must be neutral and non -reflective. Please ven"fv.. "PROVED
d
Please submit your comments and 2 comes of revised plans for review to the Community Development
Building at 19 E Main. If you have questions contactjaNell Hansen,, Building Safety Coordinator,, at
208-359.3020 ext. 346 or janellh@rexburg.0tg.