LL. 903.1.2 Warehouse sprinkler systems. An automatic sprinkler system
shall be installed in warehouse type buildings where any portion of the building has
an open ceiling height ovex• twelve (12) feet.
MM. 903,Z Where required. Approved automatic sprinkler systems in new
buildings and structures shall be provided in the locations described in Sections
903.2.. 1 through 903.2.12.
NN. 903.3.1.2 NEPA 13R sprinkler systems. Where allowed in buildings of
Grasp R, with three (3) to twelve (12) dwelling units, automatic sprinkler systems
shall be installed throughout in accordance with NFPA 1.3R or NFPA 13.
4C). 9U3.3.7 Fire department connections. The location of fire department
connections shall be within 15q feed of a hydrant and adjacent to the fire apparatus
access road.
PP. 903.3.8 Approved piping. Transitional piping between the undergra�ind
water supply main and the fire sprinkler riser shall be ductile iron.
QQ. 945.1 General. Standpipe systems shall be provided in new buildings and
structures in accordance with this section. The hose threads used in connection with
standpipe systems shall be approved and shall be compatible with dire department
dose threads. The location of fire department lose connections shall be approved.
All Standpipe systems shall be automatic standpipe systems as defined by NFPA 14
unless approved by the Fire Chief or his designee. In buildings used for high -piled
combustible stora�c, fire protection shall be in accordance with Chapter 23,
RR. 907.1 General. This section covers the application, installation,
performance, and maintenance of fire alarm systems and their components in new
.1 and existing buildings and structures. The requirements of S
iection 907.2 are
applicable to new buildings and structures. The requirements of Section 907. 3 are
applicably to existing buildings and .,tructures. Na partial fire alarm and detection
systems shall be allowed.
SS. 907.7.1. Wiring. Wiring shall comply with the requirements of NFPA 70
and NFPA 72. 'wireless protection sNistems utilizing radio-frequency transmitting
devices shall comply ��vith the special requirc;ments of supervision of low-power
wireless systems in NFPA 72. All wiring not installed in conduit shah be installed,
with approved dangers or protective devices. All hangers or protective devices must
meet the approval, of the fire code ofFicial.
ictal.
TT. 907.7.3.2.3 Zone and address location labeling. Tire alarm control paiiels
(FACP) shall have all zones and address points plainly and permanently labeled as to
their location, on the outside of the panel or on an easily readable map of the
building affixed to the outside of the panel.