HomeMy WebLinkAboutCONCRETE TEST - 19-00577 - Ollie Manor - New MFRFile Name:
21020FB09152021EV
1A2CCD53-C0C5-4ED5-8DDB-769037808A1D 1
4103 E 605 N Suite 1 Rigby, ID 83442 208.881.0081 www.connectengr.com
Compressive Strength of Concrete Test Specimens
Project Number:
21020
Cumulative Test Load Amount:
10.0
Project Name:
Adam's Elementary
Test Location:
Sidewalk along the fence on S 2nd E, last half on
sidewalk on the Northwest side of the building
Client:
Madison School District
Admixtures:
Ticket Number:
10034
Contractor:
Mills Concrete
Supplier:
IMC
Mix Number:
3326104
Pour Date:
9/9/2021
Cylinder Log #:
577
Field Test Results:
Set #:
1
Slump
(inches):
6.0
Slump
Maximum
(in):
5.0
Entrained Air
(%):
7.00
Entrained Air
Spec. (%):
Concrete
Temperature
(°F):
63
Ambient
Temperature
(°F):
50
Unit Weight
(PCF):
139.36
Tested By:
Y. Kabwika
Date:
9/9/2021
Time Tested:
8:15 AM
Picked Up By:
E. Vail
Date:
9/9/2021
Time:
10:30 AM
Max, Min Temperature
104.7, 39.7
File Name:
21020FB09152021EV
1A2CCD53-C0C5-4ED5-8DDB-769037808A1D 2
Initial Break Results:
Cylinder
#:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Break
Type:
Required
28 day
Strength
(psi):
A 7 9/16/2021 4.00 12.56 33,105.0 2635.75 Type 1 3,500.0
Date:
09/20/2021
Reviewed By:
E. Vail
Signature: