HomeMy WebLinkAboutPLANS REVISED REDLINED APPROVED - 21-00337 - 950 Westwood Dr - Solar PanelsAuthor Name Author Email Author Phone No.: Bret Stoddard brets@rexburg.org 208-372-2171 Larry Beesley Larry.Beesley@rexburg.org 208-372-2176 Description : 950 Westwood Dr - Solar PanelsAddress : 950 Westwood DrRecord Type : Solar PanelsDocument Filename : Peck_Plans_V1 (2).pdf Comment Author Contact Information: Corrections in the following table need to be applied before a permit can be issued Review Report Approved # 21-00337 Page Reference AnnotationType Author : Department Status Page Review Comments Applicant Response Comments PV 0.0 Stamp Larry Beesley : Building Open 1 Approved - Building Inspector PV 1.0 Stamp Larry Beesley : Building Open 2 Approved - Building Inspector PV 1.0 Free text Larry Beesley : Building Open 2 Solar panels installed a minimum of 3 feet from roof ridge anda minimum of 3 feet from at least one side PV 1.0 Line Larry Beesley : Building Open 2 S 1.1 Stamp Larry Beesley : Building Open 3 Approved - Building Inspector 1-06 Stamp Larry Beesley : Building Open 12 Approved - Building Inspector 1-07 Stamp Larry Beesley : Building Open 13 Approved - Building Inspector 1-07 Free text Larry Beesley : Building Open 13 Roof and wall penetrations flashed and sealed in accordancewith IRC Chapter 9 1-07 Free text Larry Beesley : Building Open 13 Approved flashing installed with lag mounting systems 1-08 Stamp Larry Beesley : Building Open 14 Approved - Building Inspector 1-08 Free text Larry Beesley : Building Open 14 Roof and wall penetrations flashed and sealed in accordancewith IRC Chapter 9 Solar Panels The drawings and pathways are all good. The plans are missing a stamped approval from an engineer showing that this roof will hold the snow loads plus the added solar panels .This must be provided before work is permitted and done. Approval of plans does not constitute approval of variance from code Page Reference AnnotationType Author : Department Status Page Review Comments Applicant Response Comments 1-08 Free text Larry Beesley : Building Open 14 Approved flashing installed with lag mounting systems PV 0.0 Stamp Bret Stoddard :Electrical Open 1 Approved - Electrical Inspector PV 1.0 Stamp Bret Stoddard :Electrical Open 2 Approved - Electrical Inspector S 1.1 Stamp Bret Stoddard :Electrical Open 3 Approved - Electrical Inspector E 1.1 Stamp Bret Stoddard :Electrical Open 4 Approved - Electrical Inspector E 1.2 Stamp Bret Stoddard :Electrical Open 5 Approved - Electrical Inspector E 1.3 Stamp Bret Stoddard :Electrical Open 6 Approved - Electrical Inspector 1-01 Stamp Bret Stoddard :Electrical Open 7 Approved - Electrical Inspector 1-02 Stamp Bret Stoddard :Electrical Open 8 Approved - Electrical Inspector 1-03 Stamp Bret Stoddard :Electrical Open 9 Approved - Electrical Inspector 1-04 Stamp Bret Stoddard :Electrical Open 10 Approved - Electrical Inspector 1-05 Stamp Bret Stoddard :Electrical Open 11 Approved - Electrical Inspector 1-06 Stamp Bret Stoddard :Electrical Open 12 Approved - Electrical Inspector 1-07 Stamp Bret Stoddard :Electrical Open 13 Approved - Electrical Inspector 1-08 Stamp Bret Stoddard :Electrical Open 14 Approved - Electrical Inspector 1-09 Stamp Bret Stoddard :Electrical Open 15 Approved - Electrical Inspector 1-10 Stamp Bret Stoddard :Electrical Open 16 Approved - Electrical Inspector 1-10 (2)Stamp Bret Stoddard :Electrical Open 17 Approved - Electrical Inspector 1-11 (2)Stamp Bret Stoddard :Electrical Open 18 Approved - Electrical Inspector 1-11 Stamp Bret Stoddard :Electrical Open 19 Approved - Electrical Inspector Approval of plans does not constitute approval of variance from code N 1 2 7 ' - 1 0 " 97'-4" 97'-4" 1 2 7 ' - 1 0 " 11'-2" 52'-8" 10'-10" 4 0 ' - 0 " R e v GARY PECK RESIDENCE 950 WESTWOOD DR, REXBURG, ID 83440 PHONE: -(619)921-5738 EMAIL: -gpeck49@aol.com D a t e D e s c r i p t i o n R E V I S I O N S S i g n a t u r e w i t h S e a l P r o j e c t N a m e & A d d r e s s S h e e t S i z e S h e e t N u m b e r A N S I B 1 1 " X 1 7 " P V 0 . 0 S h e e t N a m e D R A W N B Y APN: RPR0CHS0020051 237 N 2ND E, REXBURG, IDAHO, 83440 PHONE: (208) 417-9908 LIC# USES EPC S H E E T I N D E X : P V 0 . 0 : C O V E R S H E E T P V 1 . 0 : S I T E P L A N S 1 . 1 : M O U N T D E T A I L S E 1 . 1 : 3 - L I N E D I A G R A M E 1 . 2 : N O T E S E 1 . 3 : W A R N I N G L A B E L S - E Q U I P M E N T S P E C S H E E T C O V E R S H E E T S C A L E : N T S 2 S A T E L L I T E V I E W P V 0 . 0 S C A L E : N T S 3 V I C I N I T Y M A P P V 0 . 0 SCALE: 1/16" = 1'-0"1PLOT PLANPV 0.0 GENERAL NOTES:a.INSTALLATION OF SOLAR PHOTOVOLTAICSYSTEM SHALL BE IN ACCORDANCE WITHNEC ARTICLE 690, AND ALL OTHERAPPLICABLE NEC CODES WHERE NOTEDOR EXISTING.b.PROPER ACCESS AND WORKINGCLEARANCE AROUND EXISTING ANDPROPOSED ELECTRICAL EQUIPMENT WILLCOMPLY WITH NEC ARTICLE 110.c.ALL CONDUCTORS, INCLUDING THEGROUNDING ELECTRODE CONDUCTORSHALL BE PROTECTED FROM PHYSICALDAMAGE IN ACCORDANCE WITH NECARTICLE 250.d.THE PV MODULES ARE CONSIDEREDNON-COMBUSTIBLE; THIS SYSTEM ISUTILITY INTERACTIVE PER UL 1741 ANDALSO INCLUDE STORAGE BATTERIES OROTHER ALTERNATIVE STORAGE SOURCES.e.ALL DC WIRES SHALL BE SIZEDACCORDING TO [NEC 690.8]f.DC CONDUCTORS SHALL BE WITHINPROTECTED RACEWAYS IN ACCORDANCEWITH [NEC 690.31]g.ALL SIGNAGE TO BE PLACED INACCORDANCE WITH LOCALJURISDICTIONAL BUILDING CODE.h.PV MODULES TO BE RATED UL 1703 CLASSC FIRE RATING OR BETTER.i.ALL EQUIPMENT TO BE CERTIFIED BY ANATIONALLY RECOGNIZED TESTINGLABORATORY. P R O T E C T I O N O F E M E R G E N C Y R E S P O N D E R S A L L S H A R P E D G E S A N D F A S T E N E R T I P S S H A L L B E C O V E R E D O R C R I M P E D O V E R T O E L I M I N A T E S H A R P E D G E S , T O M I N I M I Z E R I S K O F I N J U R Y T O E M E R G E N C Y R E S P O N D E R S . A L L R O O F M O U N T E D C O N D U I T S , B O X E S , A N D E Q U I P M E N T C R O S S I N G P A T H W A Y S A R E T O B E C L E A R L Y I D E N T I F I E D B Y A R E D / W H I T E R E F L E C T I V E T A P E O R O T H E R A P P R O V E D M A T E R I A L . R O O F A C C E S S P O I N T R O O F A C C E S S P O I N T S H A L L N O T B E L O C A T E D I N A R E A S T H A T D O N O T R E Q U I R E T H E P L A C E M E N T O F G R O U N D L A D D E R S O V E R O P E N I N G S S U C H A S W I N D O W S O R D O O R S , A N D L O C A T E D A T S T R O N G P O I N T S O F B U I L D I N G C O N S T R U C T I O N I N L O C A T I O N S W H E R E T H E A C C E S S P O I N T D O E S N O T C O N F L I C T W I T H O V E R H E A D O B S T R U C T I O N S S U C H A S T R E E L I M B S , W I R E S O R S I G N S . PHOTOVOLTAIC SYSTEM SPECIFICATIONS:PHOTOVOLT A I C R O O F M O U N T S Y S T E M 10 MODULES-ROOF MOUNT E D - 3 . 2 0 0 k W D C , 7 . 6 0 0 k W A C , 9 5 0 W E S T W O O D D R , R E X B U R G , I D 8 3 4 4 0 R O O F A C C E S S P O I N T R O O F # 1 (10) JINKO SOLAR JKM320M - 6 0 H B L SLO P E : 1 8 ° AZI M . : 2 7 0 ° EXI S T I N G I N T E R I O R M A I N S E R V I C E PA N E L T I E D T O E X T E R I O R U T I L I T Y M E T E R # 6 6 7 8 4 4 9 5 GOVERNING CODESALL WORK SHALL CONFORM TO THE FOLLOWING CODES·2018 INTERNATIONAL BUILDING CODE·2015 INTERNATIONAL RESIDENTIAL CODE·2018 INTERNATIONAL FIRE CODE·2018 INTERNATIONAL MECHANICAL CODE·2019 INTERNATIONAL FUEL GAS CODE·2018 INTERNATIONAL ENERGY CONSERVATION CODE·2017 NATIONAL ELECTRICAL CODE·2018 INTERNATIONAL EXISTING BUILDING CODE M FRONT OF HOUSE WESTWOOD DR SYSTEM SIZE: 3.200 kW DC7.600 kW ACMODULE TYPE & AMOUNT:(10) JINKO SOLAR JKM320M-60HBLMODULE DIMENSIONS:(L/W/H) 66.3"/39.45"/1.38"INVERTER:(01) GENERAC PWRCELL X7602BATTERY CAPACITY: 9.0 kWHBATTERY:(01) GENERAC PWRCELL 9 (BJ-DCB05ZKBG, IR3DCB)INTERCONNECTION METHOD: LOAD BREAKERPROPERTY LINE PROPERTY LINE PROPERTY LINE P R O P E R T Y L I N E M A I N H O U S E D R I V E W A Y GARAGE F E N C E N 3'-0"16'-9"30'-3"NEW PV ATTACHMENTAT 4'-0" O.C. R e v GARY PECK RESIDENCE 950 WESTWOOD DR, REXBURG, ID 83440 PHONE: -(619)921-5738 EMAIL: -gpeck49@aol.com D a t e D e s c r i p t i o n R E V I S I O N S S i g n a t u r e w i t h S e a l P r o j e c t N a m e & A d d r e s s S h e e t S i z e S h e e t N u m b e r A N S I B 1 1 " X 1 7 " P V 1 . 0 S h e e t N a m e D R A W N B Y APN: RPR0CHS0020051 237 N 2ND E, REXBURG, IDAHO, 83440 PHONE: (208) 417-9908 LIC# USES EPC E Q U I P M E N T L A Y O U T S I T E P L A N SCALE:1/8" = 1'-0"1SITE PLANPV 1.0 R O O F S E C T I O N ( S ) M O D U L E - 1 0 S L O P E - 1 8 ° A Z I M U T H - 2 7 0 ° M A T E R I A L - C O M P O S I T I O N S H I N G L E T R U S S S I Z E & S P A C I N G - 2 " X 4 " @ 2 4 " O . C . R O O F # 0 1 M O D U L E , A R R A Y W E I G H T ( L O A D C A L C ' S ) N u m b e r o f M o d u l e s 1 0 M o d u l e W e i g h t 4 1 . 9 L B S T o t a l M o d u l e ( A r r a y ) W e i g h t 4 1 9 . 0 0 L B S N u m b e r o f A t t a c h m e n t p o i n t 3 2 M o u n t i n g S y s t e m W e i g h t ( P e r M o d u l e ) 1 . 5 L B S M o u n t i n g S y s t e m W e i g h t 4 8 . 0 0 L B S T o t a l S y s t e m W e i g h t ( M o d u l e W e i g h t + M o u n t i n g S y s t e m W e i g h t ) 4 6 7 . 0 0 L B S W e i g h t a t E a c h A t t a c h m e n t P o i n t ( A r r a y W e i g h t / N u m b e r o f A t t a c h m e n t P o i n t ) 1 3 . 0 9 L B S M o d u l e A r e a ( 6 6 . 3 " x 3 9 . 4 5 " ) 1 8 . 1 6 S q F t T o t a l A r r a y A r e a 1 8 1 . 6 3 S q F t D i s t r i b u t e d L o a d ( T o t a l S y s t e m W e i g h t / T o t a l A r r a y A r e a ) 2 . 3 9 P e r S q F t T o t a l R o o f A r e a 2 5 6 0 S q F t T o t a l P e r c e n t a g e o r R o o f C o v e r e d T o t a l A r r a y A r e a / T o t a l R o o f A r e a ) * 1 0 0 7 . 1 0 % SYSTEM SIZE: 3.200 kW DC7.600 kW ACMODULE TYPE & AMOUNT:(10) JINKO SOLAR JKM320M-60HBLMODULE DIMENSIONS:(L/W/H) 66.3"/39.45"/1.38"INVERTER:(01) GENERAC PWRCELL X7602BATTERY CAPACITY: 9.0 kWHBATTERY:(01) GENERAC PWRCELL 9 (BJ-DCB05ZKBG, IR3DCB)PHOTOVOLTAIC SYSTEM SPECIFICATIONS:36" FIRE SETBACK36" FIRE SETBACK M ACIB CL NEW PV AC DISCONNECT GROUPED WITH SERVICEEQUIPMENT (VISIBLE, LOCKABLE, LABELED)EXISTING INTERIOR MAIN SERVICE PANEL& POINT OF INTERCONNECTION. TIED TOEXTERIOR UTILITY METER #66 784 495NEW GENERAC PWRCELL X7602 INVERTER ( 0 1 ) N E W G E N E R A C P W R C E L L 9 ( B J - D C B 0 5 Z K B G , I R 3 D C B ) N E W C R I T I C A L B A C K U P L O A D P A N E L PVLPVL FRONT OF HOUSE WESTWOOD DR ROOF #01 S T R I N G # 2 - 0 5 M O D U L E S S T R I N G # 1 - 0 5 M O D U L E S S T R I N G ( S ) S Y S T E M L E G E N D M A C 1 0 N E W J I N K O S O L A R J K M 3 2 0 M - 6 0 H B L M O D U L E S W I T H G E N E R A C S N A P R S I N L I N E D I S C O N N E C T S W I T C H N E W 0 1 - G E N E R A C P W R C E L L X 7 6 0 2 I N V E R T E R I = C O N D U I T E X T E R I O R R U N = R O O F O B S T R U C T I O N S = F I R E P A T H W A Y N E W V I S I B L E , L O C K A B L E , L A B E L E D D I S C O N N E C T L O C A T E D W I T H I N 1 0 ' F R O M T H E U T I L I T Y M E T E R N E W G E N E R A C S 2 5 0 2 P V - L I N K S U B S T R I N G O P T I M I E R S . P V L N E W C R I T I C A L B A C K U P L O A D P A N E L C L G E N E R A C P W R C E L L 9 ( B J - D C B 0 5 Z K B G , I R 3 D C B ) E N E R G Y S T O R A G E B = A T T A C H M E N T P O I N T S = R A F T E R = R A C K I N G S Y S T E M NOTE: MARKING FOR ESS DISCONNECTSHOWN IN COMPLIANCE WITH NEC 706.7 (D)DISCONNECTS (PLACED NEXT TO THE ESS)ARE REQUIRED WHEN ESS IS 5FT + ORSEPERATED BY A PARTITION WALL FROMTHE INVERTER (NEC 706.7 (E) E X I S T I N G I N T E R I O R M A I N S E R V I C E P A N E L & P O I N T O F I N T E R C O N N E C T I O N . T I E D T O E X T E R I O R U T I L I T Y M E T E R # 6 6 7 8 4 4 9 5 . Solar panels installed a minimum of 3 feet from roof ridge and a minimum of 3 feet from at least one side R e v GARY PECK RESIDENCE 950 WESTWOOD DR, REXBURG, ID 83440 PHONE: -(619)921-5738 EMAIL: -gpeck49@aol.com D a t e D e s c r i p t i o n R E V I S I O N S S i g n a t u r e w i t h S e a l P r o j e c t N a m e & A d d r e s s S h e e t S i z e S h e e t N u m b e r A N S I B 1 1 " X 1 7 " S 1 . 1 S h e e t N a m e D R A W N B Y APN: RPR0CHS0020051 237 N 2ND E, REXBURG, IDAHO, 83440 PHONE: (208) 417-9908 LIC# USES EPC M O U N T D E T A I L SCALE: NTS 2ATTACHMENT DETAIL ENLARGED VIEWS 1.1 SCALE: NTS 1ATTACHMENT DETAIL (SIDE VIEW)S 1.1 GENERAL STRUCTURAL NOTES:1.THE SOLAR PANELS ARE TO BE MOUNTED TO THEROOF FRAMING USING THE IRONRIDGE RACKINGSYSTEM WITH FLASH FOOT 2 ATTACHMENTS. THEMOUNTING FEET ARE TO BE SPACED AS SHOWNIN THE DETAILS, AND MUST BE STAGGERED TOADJACENT FRAMING MEMBERS TO SPREAD OUTTHE ADDITIONAL LOAD.2.UNLESS NOTED OTHERWISE, MOUNTINGANCHORS SHALL BE 5/16" LAG SCREWS WITH AMINIMUM OF 2-1/2" PENETRATION INTO ROOFFRAMING.3.THE PROPOSED PV SYSTEM ADDS 2.6 PSF TO THEROOF FRAMING SYSTEM.4.ROOF LIVE LOAD = 20 PSF TYPICAL, 0 PSF UNDERNEW PV SYSTEM.5.GROUND SNOW LOAD = 0 PSF6.WIND SPEED = 115 MPH7.EXPOSURE CATEGORY = 08.RISK CATEGORY = II P V M O D U L E ( E ) C O M P S H I N G L E R O O F I R O N R I D G E I N T E G R A T E D G R O U N D I N G & E N D / M I D C L A M P P V M O D U L E S I R O N R I D G E X R - 1 0 R A I L F L A S H I N G 2 " X 4 " T R U S S @ 2 4 " O C 5 / 1 6 " x 3 " S S L A G B O L T W I T H M I N 2 - 1 / 2 " T H R E A D E M B E D M E N T , S E A L E D P E N E T R A T I O N SEE (2/S 1.1) FORENLARGED VIEW I R O N R I D G E F L A S H F O O T 2 2 " X 4 " T R U S S @ 2 4 " O C R e v GARY PECK RESIDENCE 950 WESTWOOD DR, REXBURG, ID 83440 PHONE: -(619)921-5738 EMAIL: -gpeck49@aol.com D a t e D e s c r i p t i o n R E V I S I O N S S i g n a t u r e w i t h S e a l P r o j e c t N a m e & A d d r e s s S h e e t S i z e S h e e t N u m b e r A N S I B 1 1 " X 1 7 " E 1 . 1 S h e e t N a m e D R A W N B Y APN: RPR0CHS0020051 237 N 2ND E, REXBURG, IDAHO, 83440 PHONE: (208) 417-9908 LIC# USES EPC 3 - L I N E D I A G R A M N O T E : - # 6 A W G S O L I D C U E Q U I P M E N T G R O U N D C O N D U C T O R C O N T . R U N T O G R O U N D L U G O N R A C K I N G S Y S T E M . A L L R O O F T O P C O M P O N E N T S B O N D E D T O R A C K I N G S Y S T E M P E R N E C 6 9 0 . 4 3 NOTE: -1.PV WIRE - GREEN SPEC, UL SUBJECT 4703,UL 44, UL 854, 200V, 90C-RoHS2.JUNCTION BOX - SOLADECK (0799-5), UL 50,CSA C22.2 NO # 290, NEMA TYPE 3R, UL1741 PV MODULE RATING @ STCMANUFACTURERMAX. POWER-POINT CURRENT (IMP)MAX. POWER-POINT VOLTAGE (VMP)OPEN-CIRCUIT VOLTAGE (VOC)SHORT-CIRCUIT CURRENT (ISC)9.59 AMPS JINKO SOLAR JKM320M-60HBL33.4 VOLTS40.9 VOLTS10.15 AMPSNOM. MAX. POWER AT STC (PMAX)MAX. SYSTEM VOLTAGEVOC TEMPERATURE COEFFICIENT 320 WATT1000V-0.28 %/°CRooftop conductor ampacities designed in compliance withart. 690.8, Tables 310.15(B)(2)(a), 310.15(B)(3)(a),310.15(B)(3)(c), 310.15(B)(16), Chapter 9 Table 4, 5, & 9.Location specific temperature obtained from ASHRAE 2017data tablesAMBIENT TEMP (HIGH TEMP 2%)RECORD LOW TEMP-18C32°CCONDUIT HEIGHT0.5"ROOF TOP TEMP INVERTER CHARACTERISTICS - GENERAC PWRCELL X7602MAX OUTPUT POWER7600WSYSTEM OPERATING VOLTAGE380VMAX CONTINOUS OUTPUT CURRENT32AMAX INPUT VOLTAGE420VMAX INPUT CURRENT20AMAX EFFICIENCY97% P H O T O V O L T A I C S Y S T E M D C S Y S T E M S I Z E ( W A T T S ) N O M I N A L A C V O L T A G E 2 4 0 V 3 2 0 0 W A C S Y S T E M S I Z E ( W A T T S ) 7 6 0 0 W T O T A L N U M B E R O F M O D U L E S 1 0 CONDUCTOR TEMPERATURE RATE90°C 54°CWIREQTYWIRETAG #CONDUITWIRE TYPE S T R I N G W A T T A G E O P E R A T I N G V O L T A G E C O N D U I T F I L L : TEMPRATING:W I R E A M P T E M P D E - R A T E : W I R E O C P : M A X S Y S T E M V O L T A G E G R N D S I Z E WIREGAUGE: T E R M I N A L 7 5 ° C R A T I N G : N E C : M A X A M P S x x = / x = 1 . 2 5 2 4 0 V 1 6 0 0 W 8 . 3 3 A 3 8 . 4 0 A 3 5 A 90° 3 5 A / x = 1 . 2 5 2 4 0 V 3 2 0 0 W 1 6 . 6 7 A x x = 3 0 . 4 0 A 90° 5 0 A / x = 1 . 2 5 4 0 . 0 0 A x x = 4 7 . 0 0 A 75°4 0 A #104 0 A #105 0 A #8 3/4" EMT3/4" EMT WIRE FROM - -PV LINKTOINVERTERINVERTER TO ACDISCONNECT ARRAY TO PVLINK123PV WIRETHWN-2THWN-2 4 N / A 2 1 . 0 0 3 1 . 0 0 IN AIR / = = = = S T R I N G A M P S 6 . 6 7 A 1 3 . 3 3 A 3 2 . 0 A x G R N D W I R E T Y P E 4 2 0 V 4 2 0 V 2 4 0 V # 6 # 8 # 8 S B C T H W N - 2 T H W N - 2 0 . 9 6 0 . 7 6 0 . 9 4 21352135++--++--+++-+-+-+-+-+--- G E N E R A C P O W E R C O R E RSRSRSRSRSRSGENERACGENERAC30A30A R O U T E R GENERACGENERACGENERACGENERACGENERACGENERAC GENERAC S2502 PV LINKSUB STRING OPTIMIZER,UL1741 CERTIFIED, NEC690.12 COMPLAINTGENERAC SNAP RSINLINE DISCONNECTSWITCH, UL1741CERTIFIED, NEC690.12 COMPLIANT G E N E R A C P W R C E L L X 7 6 0 2 I N V E R T E R O U T P U T : 2 4 0 V A C , 3 2 . 0 A 9 6 . 5 % C E C W E I G H T E D E F F I C I E N C Y NEMA 3 R , U L 1 7 4 1 S A L I S T E D , I N T E R N A L G F D I W I T H I N T E G R A T E D D C D I S C O N N E C T (01) GENERAC PWRCELL 9(BJ-DCB05ZKBG, IR3DCB) BATTERYUL9540, UL1973, UL1642 CERTIFIED 21EXTERNAL SAFETY RAPIDSHUTDOWN TERMINAL 5 0 A (2) #8 AWG THWN-2(1) #8 AWG GND3/4" EMT CONDUIT N ( N ) 1 2 0 / 2 4 0 V , 2 0 0 A C R I T I C A L B A C K U P L O A D P A N E L , S I N G L E P H A S E U L 1 7 4 1 C E R T I F I E D G ( E ) L O A D S ( E ) L O A D S ( 3 ) # 6 A W G T H W N - 2 ( 1 ) # 8 A W G G N D 1 " E M T C O N D U I T ( N ) P V B R E A K E R N E C 7 0 5 . 1 2 ( B ) ( 2 ) ( 3 ) ( d ) G N M P O I N T O F I N T E R C O N N E C T , L O A D S I D E N E C 7 0 5 . 1 2 ( B ) ( 2 ) ( 3 ) ( d ) E X I S T I N G 2 4 0 V / 1 5 0 A B U S B A R R A T I N G , M A I N S E R V I C E P A N E L , S I N G L E P H A S E , W I T H A N E W 1 2 5 A M A I N D I S C O N N E C T U T I L I T Y C O M P A N Y : P A C I F I C P O W E R U T I L I T Y M E T E R : 6 6 7 8 4 4 9 5 4 0 A MODULE:(10) JINKO SOLAR JKM320M-60HBLINVERTER:(01) GENERAC PWRCELL X760210 NEW JINKO SOLAR JKM320M-60HBLMODULES WITH GENERAC SNAP RS INLINEDISCONNECT SWITCH30A30A(N) 30A BATTERYDISCONNECT, 240VUL1741 CERTIFIED 30A P V M O D U L E F R A M E I R O N R I D G E R A I L I R O N R I D G E U N I V E R S A L F A S T E N I N G O B J E C T I R O N R I D G E G R O U N D I N G P I E R C E S T H R O U G H A N O D I Z E D C O A T I N G S O F M O D U L E F R A M E S A N D R A I L S I R O N R I D G E G R O U N D I N G P I E R C E S T H R O U G H A N O D I Z E D C O A T I N G S O F M O D U L E F R A M E S A N D R A I L S I R O N R I D G E I N T E G R A T E D G R O U N D I N G & L A Y - I N L U G S A R E U L 2 7 0 3 L I S T E D G R O U N D I N G D E T A I L s c a l e : N T S S S S E T S C R E W I N C L U D E D # 1 0 - 2 4 X 3 / 4 " S S H C S B O L T # 1 0 S S E X T E R N A L T O O T H L O C K ( S T A R ) W A S H E R # 1 0 - 2 4 S S L O C K N U T 6 A W G B A R E C U W I R E L A Y - I N L U G T E R M I N A L A L / C U D U A L R A T E D ( T I N P L A T E D C U ) I R O N R I D G E R A I L R A I L S M O D U L E S ( N ) 1 2 5 A ( E ) L O A D S NOTE: -ESS DISCONNECT SHOWN ON THIS SHEETIS IN COMPLIANCE WITH NEC 706.7(D)120% RULEBUS BAR RATING X 120%) - MAIN BREAKER RATIN G =MAX. PV OCPD(150A x 120%) - 125A = 55A 2 STRINGS OF 5 PV MODULES CONNECTED IN SERIES N O T E : - M A I N B R E A K E R D E R A T E D F R O M 1 5 0 A T O 1 2 5 A I N A C C O R D A N C E W I T H N E C 7 0 5 . 1 2 ( B ) ( 2 ) ( 3 ) ( b ) (N) JUNCTION BOXUL1741 CERTIFIEDGENERAC S2502 PV LINKSUB STRING OPTIMIZER,UL1741 CERTIFIED, NEC690.12 COMPLAINT G E N E R A C A P K E 0 0 0 3 2 P W R C E L L 2 C T A C C E S S O R Y K I T RAPI D S H U T D O W N SWITCH T O B E P L A C E D IN C O N S P I C U O U S LO C A T I O N O N E X T E R I O R N O T E : - S I N G L E L A R G E S T L O A D I N B A C K E D U P L O A D P A N E L C A N N O T E X C E E D T H E E S S S T O R A G E C A P A C I T Y C O N T I N U O U S R A T I N G ( 1 8 . 7 5 A ) A N D S U R G E O F ( 2 5 A A C ) F O R 2 S E C O N D S P E R N E C 7 1 0 . 1 5 ( E ) G R O U N D M I N 8 ' M I N 6 ' 5 ' M A X # 6 A W G B A R E A R M O U R E D C A B L E C O L D W A T E R B O N D N O T E : - T H E P O I N T O F C O N N E C T I O N I S N O T A D J A C E N T T O F E E D T H R U L U G S & C O N D U C T O R S A N D I S I N C O M L I A N C E W I T H N E C 7 0 5 . 1 2 N O T E : - 1 . A S P E R T H E 3 1 4 . 1 6 ( A ) S O L A D E C K J U N C T I O N B O X S I Z E S H O U L D B E 3 " X 2 " X 2 " . 2 . 3 0 0 . 1 5 ( F ) F I T T I N G . A F I T T I N G I D E N T I F I E D F O R T H E U S E S H A L L B E P E R M I T T E D I N L I E U O F A B O X O R C O N D U I T B O D Y W H E R E C O N D U C T O R S A R E N O T S P L I C E D O R T E R M I N A T E D W I T H I N T H E F I T T I N G . T H E F I T T I N G S H A L L B E A C C E S S I B L E A F T E R I N S T A L L A T I O N , U N L E S S L I S T E D F O R C O N C E A L E D I N S T A L L A T I O N . 3 . F R O M F R E E A I R W I R I N G M E T H O D S T R A N S I T I O N I N G T O A R A C E W A Y W I R I N G M E T H O D S H A L L C O M P L Y W I T H N E C 3 0 0 . 1 5 , 3 0 0 . 1 7 , 3 1 4 . 1 6 A N D 6 9 . 4 3 A S A P P L I C A B L E 3 3 G N ( N ) B L A D E T Y P E N O N - F U S I B L E A C D I S C O N N E C T N E M A 3 R 6 0 A - 2 P 1 2 0 / 2 4 0 V A C ( V I S I B L E , L O C K A B L E , L A B E L E D ) U L 1 7 4 1 C E R T I F I E D R e v GARY PECK RESIDENCE 950 WESTWOOD DR, REXBURG, ID 83440 PHONE: -(619)921-5738 EMAIL: -gpeck49@aol.com D a t e D e s c r i p t i o n R E V I S I O N S S i g n a t u r e w i t h S e a l P r o j e c t N a m e & A d d r e s s S h e e t S i z e S h e e t N u m b e r A N S I B 1 1 " X 1 7 " E 1 . 2 S h e e t N a m e D R A W N B Y APN: RPR0CHS0020051 237 N 2ND E, REXBURG, IDAHO, 83440 PHONE: (208) 417-9908 LIC# USES EPC N O T E S SITE NOTES:1.A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHAREGULATIONS.2.THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS AUTILITY INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES.3.THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING, MECHANICAL,OR BUILDING ROOF VENTS.4.PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSEDELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION NEC 110.26.5.ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED INACCORDANCE WITH THIS CODE AND THE APPROVED MANUFACTURER'SINSTRUCTIONS SUCH THAT THE ROOF COVERING SERVES TO PROTECT THEBUILDING OR STRUCTURE.EQUIPMENT LOCATIONS:1.ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY NEC 110.26.2.WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTEDOPERATING TEMPERATURE AS SPECIFIED BY NEC 690.31 (A),(C) AND NEC TABLES310.15 (B)(2)(A) AND 310.15 (B)(3)(C).3.JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULESACCORDING TO NEC 690.34.4.ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOTWITHIN SIGHT OF THE AC SERVICING DISCONNECT. 2.2.6 ALL EQUIPMENT SHALL BEINSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO NECAPPLICABLE CODES.5.ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOORUSAGE WHEN APPROPRIATE.STRUCTURAL NOTES:1.RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TOCODE-COMPLIANT INSTALLATION MANUAL. TOP CLAMPS REQUIRE A DESIGNATEDSPACE BETWEEN MODULES, AND RAILS MUST ALSO EXTEND A MINIMUM DISTANCEBEYOND EITHER EDGE OF THE ARRAY/SUBARRAY, ACCORDING TO RAIMANUFACTURER’S INSTRUCTIONS.2.JUNCTION BOX WILL BE INSTALLED PER MANUFACTURERS' SPECIFICATIONS. IFROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCALREQUIREMENTS.3.ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED W/APPROVED CHEMICAL SEALANT PER CODE BY A LICENSED CONTRACTOR.4.ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THESPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER. 2.3.6 WHENPOSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGEREDAMONGST THE ROOF FRAMING MEMBERS.WIRING & CONDUIT NOTES:1.ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE.CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODEREQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING.2.CONDUCTORS SIZED ACCORDING TO NEC 690.8, NEC 690.7.3.VOLTAGE DROP LIMITED TO 1.5%.4.DC WIRING LIMITED TO MODULE FOOTPRINT. MICROINVERTER WIRINGSYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY W/ SUITABLEWIRING CLIPS.5.AC CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE A OR L1- BLACKPHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE PHASE C OR L3-BLUE, YELLOW, ORANGE**, OR OTHER CONVENTION NEUTRAL- WHITE OR GREYIN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TOBE MARKED ORANGE [NEC 110.15].GRO U N D I N G N O T E S : 1. G R O U N D I N G S Y S T E M C O M P O N E N T S S H A L L B E L I S T E D F O R T H E I R P U R P O S E , A N D G R O U N D I N G D E V I S E S E X P O S E D T O T H E E L E M E N T S S H A L L B E R A T E D F O R S U C H U S E . 2. P V E Q U I P M E N T S H A L L B E G R O U N D E D A C C O R D I N G T O N E C 6 9 0 . 4 3 A N D M I N I M U M N E C T A B L E 2 5 0 . 1 2 2 . 3. M E T A L P A R T S O F M O D U L E F R A M E S , M O D U L E R A C K I N G , A N D E N C L O S U R E S C O N S I D E R E D G R O U N D E D I N A C C O R D W I T H 2 5 0 . 1 3 4 A N D 2 5 0 . 1 3 6 ( A ) . 4. E Q U I P M E N T G R O U N D I N G C O N D U C T O R S S H A L L B E S I Z E D A C C O R D I N G T O N E C 6 9 0 . 4 5 A N D M I C R O I N V E R T E R M A N U F A C T O R E R S ’ I N S T R U C T I O N S . 5. E A C H M O D U L E W I L L B E G R O U N D E D U S I N G W E E B G R O U N D I N G C L I P S A S S H O W N I N M A N U F A C T U R E R D O C U M E N T A T I O N A N D A P P R O V E D B Y T H E A H J . I F W E E B S A R E N O T U S E D , M O D U L E G R O U N D I N G L U G S M U S T B E I N S T A L L E D A T T H E S P E C I F I E D G R O U N D I N G L U G H O L E S P E R T H E M A N U F A C T U R E R S ' I N S T A L L A T I O N R E Q U I R E M E N T S . 6. T H E G R O U N D I N G C O N N E C T I O N T O A M O D U L E S H A L L B E A R R A N G E D S U C H T H A T T H E R E M O V A L O F A M O D U L E D O E S N O T I N T E R R U P T A G R O U N D I N G C O N D U C T O R T O A N O T H E R M O D U L E . 7. G R O U N D I N G A N D B O N D I N G C O N D U C T O R S , I F I N S U L A T E D , S H A L L B E C O L O R E D G R E E N O R M A R K E D G R E E N I F # 4 A W G O R L A R G E R [ N E C 2 5 0 . 1 1 9 ] 8. T H E G R O U N D I N G E L E C T R O D E S Y S T E M C O M P L I E S W I T H N E C 6 9 0 . 4 7 A N D N E C 2 5 0 . 5 0 T H R O U G H 2 5 0 . 1 0 6 . I F E X I S T I N G S Y S T E M I S I N A C C E S S I B L E , O R I N A D E Q U A T E , A G R O U N D I N G E L E C T R O D E S Y S T E M P R O V I D E D A C C O R D I N G T O N E C 2 5 0 , N E C 6 9 0 . 4 7 A N D A H J . 9. G R O U N D - F A U L T D E T E C T I O N S H A L L C O M P L Y W I T H N E C 6 9 0 . 4 1 ( B ) ( 1 ) A N D ( 2 ) T O R E D U C E F I R E H A Z A R D S DISC O N N E C T I O N A N D O V E R - C U R R E N T P R O T E C T I O N N O T E S : 1. D I S C O N N E C T I N G S W I T C H E S S H A L L B E W I R E D S U C H T H A T W H E N T H E S W I T C H I S O P E N E D T H E C O N D U C T O R S R E M A I N I N G E N E R G I Z E D A R E C O N N E C T E D T O T H E T E R M I N A L S M A R K E D “ L I N E S I D E ” ( T Y P I C A L L Y T H E U P P E R T E R M I N A L S ) . 2. D I S C O N N E C T S T O B E A C C E S S I B L E T O Q U A L I F I E D U T I L I T Y P E R S O N N E L , B E L O C K A B L E , A N D B E A V I S I B L E - B R E A K S W I T C H 3. P V S Y S T E M C I R C U I T S I N S T A L L E D O N O R I N B U I L D I N G S S H A L L I N C L U D E A R A P I D S H U T D O W N F U N C T I O N T O R E D U C E S H O C K H A Z A R D F O R E M E R G E N C Y R E S P O N D E R S I N A C C O R D A N C E W I T H 6 9 0 . 1 2 ( A ) T H R O U G H ( D ) . 4. A L L O C P D R A T I N G S A N D T Y P E S S P E C I F I E D A C C O R D I N G T O N E C 6 9 0 . 8 , 6 9 0 . 9 , A N D 2 4 0 . 5. M I C R O I N V E R T E R B R A N C H E S C O N N E C T E D T O A S I N G L E B R E A K E R O R G R O U P E D F U S E S I N A C C O R D A N C E W I T H N E C 1 1 0 . 3 ( B ) . 6. I F R E Q U I R E D B Y A H J , S Y S T E M W I L L I N C L U D E A R C - F A U L T C I R C U I T P R O T E C T I O N A C C O R D I N G T O N E C 6 9 0 . 1 1 A N D U L 1 6 9 9 B . INTE R C O N N E C T I O N N O T E S : 1. L O A D - S I D E I N T E R C O N N E C T I O N S H A L L B E I N A C C O R D A N C E W I T H [ N E C 7 0 5 . 1 2 ( B ) ] 2. T H E S U M O F T H E U T I L I T Y O C P D A N D I N V E R T E R C O N T I N U O U S O U T P U T M A Y N O T E X C E E D 1 2 0 % O F B U S B A R R A T I N G [ N E C 7 0 5 . 1 2 ( D ) ( 2 ) ( 3 ) ] . 3. T H E S U M O F 1 2 5 P E R C E N T O F T H E P O W E R S O U R C E ( S ) O U T P U T C I R C U I T C U R R E N T A N D T H E R A T I N G O F T H E O V E R C U R R E N T D E V I C E P R O T E C T I N G T H E B U S B A R S H A L L N O T E X C E E D 1 2 0 P E R C E N T O F T H E A M P A C I T Y O F T H E B U S B A R , P V D E D I C A T E D B A C K F E E D B R E A K E R S M U S T B E L O C A T E D O P P O S I T E E N D O F T H E B U S F R O M T H E U T I L I T Y S O U R C E O C P D [ N E C 7 0 5 . 1 2 ( B ) ( 2 ) ( 3 ) ] . 4. A T M U L T I P L E E L E C T R I C P O W E R S O U R C E S O U T P U T C O M B I N E R P A N E L , T O T A L R A T I N G O F A L L O V E R C U R R E N T D E V I C E S S H A L L N O T E X C E E D A M P A C I T Y O F B U S B A R . H O W E V E R , T H E C O M B I N E D O V E R C U R R E N T D E V I C E M A Y B E E X C L U D E D A C C O R D I N G T O N E C 7 0 5 . 1 2 ( B ) ( 2 ) ( 3 ) ( C ) . 5. F E E D E R T A P I N T E R C O N E C T I O N ( L O A D S I D E ) A C C O R D I N G T O N E C 7 0 5 . 1 2 ( B ) ( 2 ) ( 1 ) 6. S U P P L Y S I D E T A P I N T E R C O N N E C T I O N A C C O R D I N G T O N E C 7 0 5 . 1 2 ( A ) W I T H S E R V I C E E N T R A N C E C O N D U C T O R S I N A C C O R D A N C E W I T H N E C 2 3 0 . 4 2 2 . 7 . 8 B A C K F E E D I N G B R E A K E R F O R E L E C T R I C P O W E R S O U R C E S O U T P U T I S E X E M P T F R O M A D D I T I O N A L F A S T E N I N G [ N E C 7 0 5 . 1 2 ( B ) ( 5 ) ] . N R e v GARY PECK RESIDENCE 950 WESTWOOD DR, REXBURG, ID 83440 PHONE: -(619)921-5738 EMAIL: -gpeck49@aol.com D a t e D e s c r i p t i o n R E V I S I O N S S i g n a t u r e w i t h S e a l P r o j e c t N a m e & A d d r e s s S h e e t S i z e S h e e t N u m b e r A N S I B 1 1 " X 1 7 " E 1 . 3 S h e e t N a m e D R A W N B Y APN: RPR0CHS0020051 237 N 2ND E, REXBURG, IDAHO, 83440 PHONE: (208) 417-9908 LIC# USES EPC W A R N I N G L A B E L S C A U T I O N : P O W E R T O T H I S B U I L D I N G I S A L S O S U P P L I E D F R O M T H E F O L L O W I N G S O U R C E S W I T H D I S C O N N E C T S L O C A T E D A S S H O W N ( 1 0 ) P V M O D U L E S MACINVERTERJ/B PV ARRAY P E R C O D E ( S ) : N E C 2 0 1 1 : 7 0 5 . 1 2 ( B ) ( 2 ) ( 3 ) ( b ) , N E C 2 0 1 7 W A R N I N G ! D O N O T R E L O C A T E T H I S O V E R C U R R E N T D E V I C E I N V E R T E R O U T P U T C O N N E C T I O N ! WARNING: PHOTOVOLTAICPOWER SOURCE(PER CODE: NEC 690.31(G)(3)(4) & NEC 690.13(G)(4))PER CODE(S): NEC 2017: 690.13(B)ELECTRICAL SHOCK HAZARDDO NOT TOUCH TERMINALS.TERMINALS ON LINE AND LOADSIDES MAY BE ENERGIZED INTHE OPEN POSITION WARNING!! P H O T O V O L T A I C A C D I S C O N N E C T ( P E R C O D E : N E C 6 9 0 . 1 4 ( C ) ( 1 ) ) S O L A R P H O T O V O L T A I C S Y S T E M S ( P E R C O D E : N E C 6 9 0 ) L A B E L L O C A T I O N : A C D I S C O N N E C T , P O I N T O F I N T E R C O N N E C T I O N ( P E R C O D E : N E C 6 9 0 . 5 4 ) P H O T O V O L T A I C S Y S T E M A C D I S C O N N E C T R A T E D A C O P E R A T I N G C U R R E N T 3 2 . 0 A M P S A C N O M I N A L O P E R A T I N G V O L T A G E 2 4 0 V O L T S I N V E R T E R # 1 ( G E N E R A C P W R C E L L X 7 6 0 2 ) PHOTOVOLTAIC SYSTEMEQUIPPED WITHRAPID SHUTDOWNLABEL LOCATION:UTILITY SERVICE ENTRANCE/METER, INVERTER/DC DISCONNECTIF REQUIRED BY LOCAL AHJ, OR OTHER LOCATIONS ASREQUIRED BY LOCAL AHJ.PER CODE(S): NEC 2011: ARTICLE 690.56(C): NEC 2017 S O L A R P H O T O V O L T A I C S Y S T E M S ( P E R C O D E : N E C 6 9 0 ) S O L A R P H O T O V O L T A I C S Y S T E M S ( P E R C O D E : N E C 6 9 0 ) PHOTOVOLTAIC DC DISCONNECTMAXIMUM SYSTEM VOLTAGE:MAXIMUM CIRCUIT CURRENT:MAX RATED OUTPUT CURRENT OF THE CHARGECONTROLLER OR DC-TO-DC CONVERTER (IF INSTALLED):VDCADCADC4208.415 INVERTER #1 (GENERAC PWRCELL X7602)LABEL LOCATION:INVERTER(S), DC DISCONNECT(S).PER CODE(S): CEC 2016: 690.53, NEC 2017: 690.53, NEC 2014: 690.53,NEC 2011: 690.53 A S O L A R P V S Y S T E M E Q U I P P E D W I T H R A P I D S H U T D O W N T U R N R A P I D S H U T D O W N S W I T C H T O T H E " O F F " P O S I T I O N T O S H U T D O W N P V S Y S T E M A N D R E D U C E S H O C K H A Z A R D I N T H E A R R A Y S O L A R E L E C T R I C P V P A N E L S A T I N V E R T E R [ I F C 6 0 5 . 1 1 . 3 . 1 ( 1 ) & 6 9 0 . 5 6 ( C ) ( 1 ) ( a ) ] P E R C O D E : N E C 2 0 1 7 I N V E R T E R C R I T I C A L B A C K U P L O A D P A N E L M A I N S E R V I C E P A N E L U T I L I T Y M E T E R B A T T E R Y A C D I S C O N N E C T WESTWOOD DR M A C I B C L Roof and wall penetrations flashed and sealed in accordance with IRC Ch a p t e r 9 A p p r o v e d f l a s h i n g i n s t a l l e d w i t h l a g m o u n t i n g s y s t e m s R o o f a n d w a l l p e n e t r a t i o n s f l a s h e d a n d s e a l e d i n a c c o r d a n c e w i t h I R C C h a p t e r 9 Approved flashing installed with lag mounti n g s y s t e m s