Description : Collective Curl Salon and Spa - RemodelAddress : 556 Trejo StRecord Type : Commercial - RemodelDocument Filename : AB71DAD7-1AA7-449C-8232-1ED66A9ADE41.jpeg
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report Approved
# 21-00240
Page Reference AnnotationType Author : Department Status Page Review Comments Applicant Response Comments
Pg 1 Stamp Cody Jones : Building Open 1
Pg 1 Free text Cody Jones : Building Open 1 All Consrtucion and materials need to comply with IBC 2018
Pg 1 Free text Cody Jones : Building Open 1 Doors need to comply with Section 1010. Min width 32"
Pg 1 Line Cody Jones : Building Open 1
Pg 1 Free text Cody Jones : Building Open 1 36" min width
Pg 1 Line Cody Jones : Building Open 1
Pg 1 Free text Cody Jones : Building Open 1 Minimum of one restroom needs to meet ADA requirements.
Pg 1 Free text Cody Jones : Building Open 1 Seating at tables, counters and work areas need to complywith IBC Section 1109.11.
Pg 1 Free text Cody Jones : Building Open 1 Exit signs and emergency lighting to comply with section 1008and 1013.
Pg 1 Free text Cody Jones : Building Open 1 If window is within a 24" arc of either edge of door it will needto be tempered.
Pg 1 Line Cody Jones : Building Open 1
Commercial - Remodel
Approval of plans does not constitute approval of variance from code
Page Reference AnnotationType Author : Department Status Page Review Comments Applicant Response Comments
Pg 1 Comment Bret Stoddard :Electrical Open 1 No electrical details noted. All new wiring must meet the 2017NEC.
Approval of plans does not constitute approval of variance from code
Powered by TCPDF (www.tcpdf.org)
All Consrtucion and materials need to
comply with IBC 2018
Doors need to comply
with Section 1010. Min
width 32"
36" min width
Minimum of
one restroom
needs to
meet ADA
requirements.
Seating at tables, counters and work areas need to comply with IBC
Section 1109.11.
Exit signs and
emergency lighting
to comply with
section 1008 and
1013.
If window is
within a 24"
arc of either
edge of door it
will need to be
tempered.