Loading...
HomeMy WebLinkAboutPLANS REVISED SOUTH CLUBHOUSE - 20-00949 - The Gates Apartments - Solar PanelsSTREET VIEWAERIAL VIEW MODULE: (31) TRINA TSM-DD06H.05(II) 325 325W PV Module INVERTER: (1) SOLAREDGE SE7600H-US String Inverter 240VAC RACKING: UNIRAC Roof Mounted PV System OPTIMIZER: (31) SOLAREDGE P340 DC Optimizers WIND SPEED: 115 MPH EXPOSURE CATEGORY: CA. ALL WORK SHALL COMPLY WITH STATE AND LOCAL CODES. B. DRAWINGS HAVE BEEN DETAILED ACCORDING TO UL LISTING REQUIREMENTS. C. PRIOR TO COMMENCMENT OF WORK CONTRACTOR SHALL VERIFY EXISTING CONDITIONS AND NOTIFY DBM OF ANY INCONSISTENCIES. D. ALL EQUIPMENT SHALL BE INSTALLED AS SHOWN. F. WIRING SHALL NOT BE INSTALLED WITHIN 10 INCHES OF ROOF DECKING EXCEPT WHERE DIRECTLY BELOW PV EQUIPMENT SYSTEM SUMMARY DESIGN CRITERIA SCOPE OF WORK GENERAL NOTES OCCUPANCY & CONSTRUCTION TYPE OCCUPANCY - A3 CONSTRUCTION - V-B SHEET INDEX PAGE NUMBER PAGE TITLE PV01 TITLE PAGE PV02 SITE PLAN PV03 ONE LINE & ELECTRICAL PV04 ARRAY & STRINGING DETAIL PV05 LABEL PLAN SPECS SPECSHEETS AND DOCUMENTS 2017 NATIONAL ELECTRICAL CODE (NEC) 2015 INTERNATIONAL FIRE CODE (IFC) 2015 INTERNATIONAL BUILDING CODE (IBC) 2015 INTERNATIONAL RESIDENTIAL CODE (IRC) DC System Size: 10.075 kW Asphalt/Comp shingle roof pitch: 6/12 Anchored on 48 inch centers using UL listed racking system UV resistant cable ties (not zip ties) used for permanent wire management in accordance with (NEC 110.2,1110.3(A-B), 300.4) Junction boxes mounted flush w/racking APPLICABLE CODES E. WARNINGS PER NEC 690. Set Reviewed By: PV-041115-011207 CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT PORTICADE CONSTRUCTION NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC SI T E I N F O R M A T I O N : Th e G a t e s A p a r t m e n t s S o u t h C l u b h o u s e 37 0 W 7 t h S , Re x b u r g , I D 8 3 4 4 0 SY S T E M I N F O R M A T I O N : 10 . 0 7 5 k W DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC P: (801) 690-4873 E: SUPPORT@DBMSOLAR.COM WWW.DBMSOLAR.COM PROJECT # 2021-PORT DATE: 2/16/2021 DESIGNED BY: J. Fairchild SHEET NAME: PAGE #REVISION: 1PV01 COVER PAGE PHOTOVOLTAIC MODULES **PV Modules cannot be installed over vents 3' 18" 39.53" 66.85" FIRE CODE SETBACKS ARRAY DETAIL A B C D AZIMUTH 180° TILT ANGLE 27° MODULE COUNT 31 90 120 150180210 240 270 300 330 0 30 60 W E S N 80 70 50 4O 2010350 320310 290 280 260 250 230220 200190 170160 140 130 110 100 340 AZIMUTH 180 SITE INDEX**AC DISCONNECT LOCATED 10' OR LESS FROM UTILITY METER 70' 280' 280' 200' UTILITY METER VISIBLE, LOCKABLE, LABELED AC DISCONNECT MSP (INTERIOR) INVERTER & DC DISCONNECT 37'-4" 52'-9" 23'-5" 20' JUNCTION BOX CONDUIT RUN PV MODULES CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT PORTICADE CONSTRUCTION NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC SI T E I N F O R M A T I O N : Th e G a t e s A p a r t m e n t s S o u t h C l u b h o u s e 37 0 W 7 t h S , Re x b u r g , I D 8 3 4 4 0 SY S T E M I N F O R M A T I O N : 10 . 0 7 5 k W DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC P: (801) 690-4873 E: SUPPORT@DBMSOLAR.COM WWW.DBMSOLAR.COM PROJECT # 2021-PORT DATE: 2/16/2021 DESIGNED BY: J. Fairchild SHEET NAME: PAGE #REVISION: 1PV02 PROPERTY DETAIL +- JUNCTION BOX +- ELECTRICAL NOTES PHOTOVOLTAIC AC OUTPUT LABEL AC OUTPUT CURRENT 32A NOMINAL AC VOLTAGE 240V #10 PV WIRE #6 BARE COPPER EGC 1 2 3 A.ALL COMPONENTS SHALL COMPLY WITH NEC AS AMENDED.B.PHASE CONDUCTORS SHALL BE IDENTIFIED C.ALL WIRES SHALL BE PROVIDED WITH STRAIN RELIEF UPON ENTRY INTO BOXES, REFER TO MANUFACTURERS INSTALLATION MANUAL FOR REQUIRED TORQUE VALUES D.THE DC GEC, IF USED, SHALL BE CONTINUOUS FROM THE INVERTER GROUND BUS TO THE MAIN SERVICE GROUNDING ELECTRODE SYSTEME.ATTACHMENT TO GROUND ELECTRODE SHALL USE IRREVERSIBLE CLAMP. F.ALL EXPOSED METAL PARTS SHALL BE GROUNDED USING TIN PLATED COPPER LAY IN LUGS OR GROUNDING CLIPS LISTED FOR THE PURPOSE G.MIN #10 BARE COPPER EGC AT SOURCE CIRCUITS SHALL BE ROUTED SECURELY TO MOUNTING HARDWARE THAT PROTECTS FROM PHYSICAL DAMAGE H.#6 FOR AREAS THAT MAY BE SUBJECT TO DAMAGE I.BOTH ENDS OF ALL METALLIC CONDUIT SHALL BE BONDED PER NEC 250J.INTERCONNECTION PER NEC 690 K.ALL WIRES WILL BE RATED AT THHN/THWN-2 L.CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONSM.PV PRODUCTION TERMINATED IN LOAD SIDES OF ALL AC DISCONNECTS 4 RAPID SHUTDOWN DEVICE DC DISCONNECT MODULES & OPTIMIZERS IN A SERIES STRING15 MODULES & OPTIMIZERS IN A SERIES STRING16 *DC OPTIMIZERS OUTPUT 1Voc PER MODULE & KEEP VOLTAGE AT MAX POWER POINT VOLTAGE OF THE INVERTER* SE7600H-US FUSED AC DISCONNECT60A 120/240V10' OR LESS FROM UTILITY METER ·All Exposed PV rooftop conductors that are not located under the array modules, shall be installed in a listed raceway, and shall include listed junction boxes at both ends of the raceway to transition from exposed conductors to the listed raceways. In Accordance with NEC 690.31(A) & (B)** ·ROMEX AMPACITY LIMITED TO 60° VALUES. IF USED, SIZE ACCORDING TO NEC TABLE 310.15 ·DC Conduit must be marked in accordance with NEC 690.31. Labeling must be every 10' and must comply with NEC 690.31. See PV05 for Label plan ·ALL DC Conductors must be protected with metal conduit VISIBLE, LOCKABLE, LABELED DISCONNECT INTEGRATED ARC FAULT PROTECTION AND RAPID SHUTDOWN FOR NEC 2014 AND 2017, 690.11 AND 690.12 CONDUCTOR SCHEDULE WITH NEC ELECTRICAL CALCULATIONS ID DESCRIPTION CONDUCTOR CONDUIT NO. OF CNDRS. IN CNDT. RATED AMPS EGC TEMP. CORR. FACTOR FILL ADJ. FACTOR CONT. CURRENT MAX. CURRENT BASE AMPACITY DERATED AMPACITY WIRE RUN DISTANCE 1 DC CIRCUIT: SERIES STRING OUTPUT TO JUNCTION BOX PV WIRE FREE AIR N/A 15.00A #6 BARE COPPER 0.91 N/A 15.00A 18.75A 35A 31.85A 20ft 2 DC CIRCUIT (TRANSITIONED): JUNCTION BOX TO INVERTER 10 AWG THWN-2 COPPER 3/4" DIA EMT 4 15.00A 10 AWG THWN-2 COPPER 0.91 .8 15.00A 18.75A 35A 25.48A 20ft 3 INVERTER TO AC DISCONNECT 8 AWG THWN-2 COPPER 3/4" DIA EMT 3 32.00A 10 AWG THWN-2 COPPER 0.91 1.0 32.00A 40.00A 50A 45.50A 5ft 4 AC DISCONNECT TO POINT OF INTERCONNECTION 6 AWG THWN-2 COPPER 3/4" DIA EMT 3 32.00A 8 AWG THWN-2 COPPER 0.91 1.0 32.00A 40.00A 65A 59.15A 5ft PV MODULE SPECIFICATIONSMANUFACTURERTrina MODEL TSM-DD06H.05(II) MAX POWER-POINT CURRENT (Imp)9.65AMAX POWER-POINT VOLTAGE (Vmp)33.7 VOPEN CIRCUIT VOLTAGE (Voc)41.4 VSHORT CIRCUIT CURRENT (Isc)10.07 AMAX SERIES FUSE (OCPD)20 AMAX POWER (Pmax)325 WMAX VOLTAGE (Vdc)1000 V INVERTER SPECIFICATIONS MANUFACTURER SolarEdge MODEL SE7600H-US (240V) MAX DC INPUT VOLTAGE 480 V MAX OUTPUT POWER 7600 W NOMINAL AC OUTPUT VOLTAGE 240 V NOMINAL AC OUTPUT CURRENT 32 AMAX FUSE (OCPD)40 A MAX DC VOLTAGE =480V MAX DC CIRCUIT CURRENT = MAXIMUM RATED DC OUTPUT CURRENT OF DC TO DC CONVERTER (IF INSTALLED) = DC DISCONNECT CALCS 30A 15A PV LOAD CALCULATIONS 200A RATED MAIN PANEL 200A x 120% = 240A 240A - 200A =40A 40A AVAILABLE FOR PV 705.12(B)(2) 40A FUSES 200AMAINOCPD TYPICAL SUPPLY SIDE CONNECTION (TAP) NEC 705.12 (A) TO EXISTING LOADS 200A MAIN BUS200A MAIN OCPD MAIN SERVICE PANEL #XX XXX XXX G #6 CU GEC CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT PORTICADE CONSTRUCTION NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC SI T E I N F O R M A T I O N : Th e G a t e s A p a r t m e n t s S o u t h C l u b h o u s e 37 0 W 7 t h S , Re x b u r g , I D 8 3 4 4 0 SY S T E M I N F O R M A T I O N : 10 . 0 7 5 k W DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC P: (801) 690-4873 E: SUPPORT@DBMSOLAR.COM WWW.DBMSOLAR.COM PROJECT # 2021-PORT DATE: 2/16/2021 DESIGNED BY: J. Fairchild SHEET NAME: PAGE #REVISION: 1PV03 1LD/ ELECTRICAL DETAIL 3" 4" ATTACHMENT SPAN AND SUPPORT PLACEMENT ACCORDING TO MANUFACTURER INSTALLATION MANUAL + -+ -+ -+ - Diagram: Grid-Tied System w/ Optimizers + -+ -+ - PV Source Circuit To Inverter Junction Box #10 PV Wire Equipment Grounding Conductor Solar Edge DC Optimizers Attachment Diagram 48" MAX rail span with staggered attachments to distribute weight across support framing Rail PV Module Module Overhang Cantilever = 33% of MAX rail span 25% 25% 50% ROOF SURFACE FLASHING 5/16" STAINLESS STEEL LAG BOLT AND FLAT WASHER SOLAR MODULE 5'5" 4' 4" NOTE: FOR MORE DETAILS SEE NEC 690.31 (E)(1) 4" BETWEEN ROOF AND PANELS JUNCTION BOX RAIL MOUNT TERMINAL BLOCK HEYCO-TITE UL LISTED/RECOGNIZED AND CSA CERTIFIED LIQUID TIGHT CORDGRIPS Photovoltaic Array String Detail (16) Modules String A (15) Modules String B GROUNDING DETAIL PV ATTIC DETAIL ATTACHMENT DETAIL JUNCTION BOX DETAIL *See Attached Data Sheets For More Information STRINGING DETAIL A B CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT PORTICADE CONSTRUCTION NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC SI T E I N F O R M A T I O N : Th e G a t e s A p a r t m e n t s S o u t h C l u b h o u s e 37 0 W 7 t h S , Re x b u r g , I D 8 3 4 4 0 SY S T E M I N F O R M A T I O N : 10 . 0 7 5 k W DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC P: (801) 690-4873 E: SUPPORT@DBMSOLAR.COM WWW.DBMSOLAR.COM PROJECT # 2021-PORT DATE: 2/16/2021 DESIGNED BY: J. Fairchild SHEET NAME: PAGE #REVISION: 1PV04 ARRAY/STRINGING DETAIL LOCATION: (1) COMBINER BOX (2) JUNCTION BOX LOCATION: STRING INVERTER (IF USED) LOCATION: MAIN SERVICE LOCATION: (1) MAIN SERVICE (3) BREAKER PANEL (4) DISCONNECT SWITCH LOCATION: DC CONDUIT (EVERY 10 FEET) (REFLECTIVE CONDUIT LABEL) PER NEC 690.31(B)(1-4)LOCATION: (1) MAIN SERVICE (5) INVERTER (IF USED) (2) AC COMBINER PANEL MAIN SERVICE & ALL BACK FED PANEL BOARDS LOCATION: (1) MAIN SERVICE (2) AC COMBINER PANEL (3) ALL BACKFED PANELS I LABEL NOTESLABEL NOTES 4.5" H 4.5" 4.5" 4.5" 3" 4.5" FE DCBA MAIN SERVICE PANEL FOR ILLUSTRATION ONLY (NOT ACTUAL MSP) PV SUB PANEL (IF USED) AC DISCONNECT (IF USED) STRING INVERTER (IF USED) JUNCTION BOX (IF USED) A A A AC D E H G H A F I I J J FOR MICRO INVERTERS ONLY (NO KNIFE SWITCH DISCONNECT) J 4.5" PHOTOVOLTAIC AC DISCONNECT MAXIMUM AC OPERATING CURRENT: NOMINAL AC OPERATING VOLTAGE: J G 32A 240V TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY K SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN SOLAR ELECTRIC PV PANELS (2017 NEC 690.56(C)(1)(a)) (YELLOW WITH BLACK LETTERING) K WARNING ELECTRIC SHOCK HAZARD DO NOT TOUCH TERMINALS TERMINALS ON BOTH LINE AND LOAD SIDE MAY BE ENERGIZED IN THE OPEN POSITION WARNING: PHOTOVOLTAIC POWER SOURCE WARNING: DUAL POWER SOURCE SECOND SOURCE IS A PHOTOVOLTAIC SYSTEM "RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM" "PHOTOVOLTAIC SYSTEM EQUIPPED WITH RAPID SHUTDOWN" WARNING: DO NOT ADD ADDITIONAL CIRCUITS TO PANEL CAUTION: PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED WARNING: INVERTER OUTPUT CONNECTION DO NOT RELOCATE SOLAR BREAKER A.RED BACKGROUND WITH WHITE LETTERING OR YELLOW / ORANGE BACKGROUND WITH BLACK LETTERING B.MINIMUM 3/8" LETTER HEIGHT C.ALL CAPITAL LETTERS D.NON BOLD TEXT E.MATERIAL SUITABLE FOR ENVIRONMENT F.SIGNS MUST BE REFLECTIVE G.SIGNS MUST NOT BE HAND WRITTEN MAX DC VOLTAGE =480V MAX DC CIRCUIT CURRENT = MAXIMUM RATED DC OUTPUT CURRENT OF DC TO DC CONVERTER (IF INSTALLED) = DC DISCONNECT CALCS 30A 15A CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT PORTICADE CONSTRUCTION NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC SI T E I N F O R M A T I O N : Th e G a t e s A p a r t m e n t s S o u t h C l u b h o u s e 37 0 W 7 t h S , Re x b u r g , I D 8 3 4 4 0 SY S T E M I N F O R M A T I O N : 10 . 0 7 5 k W DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC P: (801) 690-4873 E: SUPPORT@DBMSOLAR.COM WWW.DBMSOLAR.COM PROJECT # 2021-PORT DATE: 2/16/2021 DESIGNED BY: J. Fairchild SHEET NAME: PAGE #REVISION: 1PV05 LABEL PLAN SOLAR MODULE SPECSHEET Sheet: 1 File: \\PERSONALCLOUD\Projects\Justin's Solar Folders\((COMMERCIAL JOBS))\Porticade\The Gates Apartments\The Gates Apartments North Clubhouse\PS-M A Datasheet_AllmaxM Plus_DD06H(II)_NA_2019_A web.pdf Missing or invalid reference Sheet: 2 File: \\PERSONALCLOUD\Projects\Justin's Solar Folders\((COMMERCIAL JOBS))\Porticade\The Gates Apartments\The Gates Apartments North Clubhouse\PS-M A Datasheet_AllmaxM Plus_DD06H(II)_NA_2019_A web.pdf Missing or invalid reference CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT PORTICADE CONSTRUCTION NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC SI T E I N F O R M A T I O N : Th e G a t e s A p a r t m e n t s S o u t h C l u b h o u s e 37 0 W 7 t h S , Re x b u r g , I D 8 3 4 4 0 SY S T E M I N F O R M A T I O N : 10 . 0 7 5 k W DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC P: (801) 690-4873 E: SUPPORT@DBMSOLAR.COM WWW.DBMSOLAR.COM PROJECT # 2021-PORT DATE: 2/16/2021 DESIGNED BY: J. Fairchild SHEET NAME: PAGE #REVISION: 1SPECS SPEC SHEETS INVERTER SPECSHEET Sheet: 1 File: \\PERSONALCLOUD\Projects\(SPEC SHEETS)\INVERTERS\SolarEdge\SE3000-11400 H Models.pdf Missing or invalid reference Sheet: 2 File: \\PERSONALCLOUD\Projects\(SPEC SHEETS)\INVERTERS\SolarEdge\SE3000-11400 H Models.pdf Missing or invalid reference CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT PORTICADE CONSTRUCTION NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC SI T E I N F O R M A T I O N : Th e G a t e s A p a r t m e n t s S o u t h C l u b h o u s e 37 0 W 7 t h S , Re x b u r g , I D 8 3 4 4 0 SY S T E M I N F O R M A T I O N : 10 . 0 7 5 k W DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC P: (801) 690-4873 E: SUPPORT@DBMSOLAR.COM WWW.DBMSOLAR.COM PROJECT # 2021-PORT DATE: 2/16/2021 DESIGNED BY: J. Fairchild SHEET NAME: PAGE #REVISION: 1SPECS SPEC SHEETS OPTIMIZER SPECSHEET Sheet: 1 File: \\PERSONALCLOUD\Projects\(SPEC SHEETS)\INVERTERS\SolarEdge\SolarEdge P320-505 Optimizers.pdf Missing or invalid reference Sheet: 2 File: \\PERSONALCLOUD\Projects\(SPEC SHEETS)\INVERTERS\SolarEdge\SolarEdge P320-505 Optimizers.pdf Missing or invalid reference File: \\PERSONALCLOUD\Projects\Justin's Solar Folders\((COMMERCIAL JOBS))\Porticade\The Gates Apartments\The Gates Apartments North Clubhouse\PS-M A Datasheet_AllmaxM Plus_DD06H(II)_NA_2019_A web.pdfFile: \\PERSONALCLOUD\Projects\Justin's Solar Folders\((COMMERCIAL JOBS))\Porticade\The Gates Apartments\The Gates Apartments North Clubhouse\PS-M A Datasheet_AllmaxM Plus_DD06H(II)_NA_2019_A web.pdf CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT PORTICADE CONSTRUCTION NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC SI T E I N F O R M A T I O N : Th e G a t e s A p a r t m e n t s S o u t h C l u b h o u s e 37 0 W 7 t h S , Re x b u r g , I D 8 3 4 4 0 SY S T E M I N F O R M A T I O N : 10 . 0 7 5 k W DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC P: (801) 690-4873 E: SUPPORT@DBMSOLAR.COM WWW.DBMSOLAR.COM PROJECT # 2021-PORT DATE: 2/16/2021 DESIGNED BY: J. Fairchild SHEET NAME: PAGE #REVISION: 1SPECS SPEC SHEETS RACKING SPECSHEET Sheet: 1 File: \\PERSONALCLOUD\Projects\(SPEC SHEETS)\RACKING\Unirac\UNIRAC-SOLARMOUNT-Brochure-17.11.29.pdf Missing or invalid reference Sheet: 2 File: \\PERSONALCLOUD\Projects\(SPEC SHEETS)\RACKING\Unirac\UNIRAC-SOLARMOUNT-Brochure-17.11.29.pdf Missing or invalid reference File: \\PERSONALCLOUD\Projects\(SPEC SHEETS)\INVERTERS\SolarEdge\SE3000-11400 H Models.pdf CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT PORTICADE CONSTRUCTION NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC SI T E I N F O R M A T I O N : Th e G a t e s A p a r t m e n t s S o u t h C l u b h o u s e 37 0 W 7 t h S , Re x b u r g , I D 8 3 4 4 0 SY S T E M I N F O R M A T I O N : 10 . 0 7 5 k W DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC P: (801) 690-4873 E: SUPPORT@DBMSOLAR.COM WWW.DBMSOLAR.COM PROJECT # 2021-PORT DATE: 2/16/2021 DESIGNED BY: J. Fairchild SHEET NAME: PAGE #REVISION: 1SPECS SPEC SHEETS